Leviton ECS00-DDW User manual

Type
User manual

Leviton ECS00-DDW is a versatile emergency lighting control device. With universal mounting, it can be installed in a variety of locations, including in 4-11/16" junction boxes with blank covers. The ECS00-DDW is designed for switching loads and can handle up to 10A of ballast current. It features automatic diagnostic capabilities, indicated by a green LED, ensuring proper operation during an emergency. Additionally, the device provides a 2.5-second emergency light-on period when the room switch is turned off, functioning as a test switch replacement.

Leviton ECS00-DDW is a versatile emergency lighting control device. With universal mounting, it can be installed in a variety of locations, including in 4-11/16" junction boxes with blank covers. The ECS00-DDW is designed for switching loads and can handle up to 10A of ballast current. It features automatic diagnostic capabilities, indicated by a green LED, ensuring proper operation during an emergency. Additionally, the device provides a 2.5-second emergency light-on period when the room switch is turned off, functioning as a test switch replacement.

Emergency Power and Method of Operation
The emergency luminaire power is derived from a 24 hour central emergency
power source. The local utility power company normally supplies the power
through a UL1008 Transfer Switch or equal, but during a utility power failure,
the transfer switch automatically switches to the emergency power source.
The room switch turns on and off both regular and emergency luminaires
simultaneously. This is accomplished by having the room switch leg power
activate the Emergency Power Control, ECS00-110.
Wire input #1 or #2 and neutral are connected internally to a sensing circuit.
During a power interruption on the sensing input, this circuit causes contact X
to drop into a N.C. position and turns on the emergency load(s). Review wiring
diagram for details.
The unit is equipped with a green LED, which indicates if regular utility power is
available and eld sensing wiring is connected correctly.
Emergency Lighting Control
For Switching Loads Universal Mount
Cat. No. ECS00-110
Ratings: 120VAC/277VAC, 60Hz, 10A Ballast
INSTALLATION INSTRUCTIONS ENGLISH
DI-020-ECS00-05A
WARNINGS:
TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST
THAT THE POWER IS OFF BEFORE WIRING!
TO AVOID PERSONAL INJURY OR PROPERTY DAMAGE, DO NOT install to control a receptacle, or a
load in excess of the specied rating.
To be installed and/or used in accordance with electrical codes and regulations.
If you are not sure about any part of these instructions, consult an electrician.
CAUTIONS:
No user serviceable components. DO NOT attempt to service or repair.
Use this device WITH COPPER OR COPPER CLAD WIRE ONLY.
ECS00-110 Universal Mount Wall or Ceiling Installation
ECS00-110 can also be mounted in plenum, when tiles are removable.
Electrical Specications
• Model ECS00-110
• Universal Mount-120/277
• 120V or 277V Sensing Input
• 120V or 277V Load
• 10 Amp Load Rating
• N.C. Contact
Mechanical Specications
Mounts in 4-11/16” Junction Box with
blank cover
• UL94V-0 Flame Rating
• Shipping Weight: 8 oz
Temperature: 32˚F - 140˚F
• Color : Black
Size (with mounting ears):
3 3/4 in.(L) x 1 3/4 in. (W) x 1 1/2 in.(H)
Automatic Diagnostic Feature
The unique feature of the ECS00-110 is the ability to place the unit above the
accessible ceiling tile because the unit does not require an accessible test
switch. Instead, when the room switch is turned off, the emergency luminaires
stay on for 2.5 seconds and indicate that an emergency power source was
available and that the ECS00-110, ballast, and lamp(s) are all functioning
correctly. This feature replaces a test switch and is approved for this purpose.
Wiring Installation
WARNING: TO AVOID FIRE, SHOCK OR DEATH, turn off power at circuit
breaker on both normal power circuit, 24 hour night light/emergency generator
circuit and test that power is off before wiring.
NOTES:
• It is recommended to number eld wiring.
Regular room lighting load does not effect ECS00-110 current rating. Room
switch is only used to control ECS00-110 10 mA relay current coil, and regular
lighting load. Regular line HOT connected to breaker and ECS-110 is only
drawing milli-amps to sense if normal power is available.
In order to provide a safe light level, when regular power is interrupted, it
is recommended that a minimum of two 4 ft uorescent tubes providing
appproximately 5000 lumen are controlled by a 24 hour emergency circuit
and are spaced no farther than 24 ft in any direction from each other in a
normal 9 ft white ceiling environment. The ECS00-110 is a universal type unit,
convenient and fast to install virtually anywhere.
Recommended Box Size
4 11/16 in. with blank cover.
1.5 in.
1.5 in.
ECS00-110 Universal Mount Fire Ceiling Installation
1.5 in.
1.5 in.
1. Install a self-adhesive 2 in. x 3 in. caution label in each xture or load
controlled by an ECS00-110 unit, cautioning that this load is supplied from
two different power sources, regular and emergency.
2. Review wiring diagram and connect wires, one group at a time, in
accordance with the numeric identication.
Model: ECS00-110
GREEN LED
UTILITY POWER
Emergency
Load
EMERGENCY HOT BLUE
EMERGENCY
SWITCH LEG
YELLOW
EMERGENCY NEUTRAL
5
6
120V 1 BLACK
277V 2 ORANGE
REGULAR LINE HOT
*
RED
WHITE
1
3
4
20 AMP
BREAKER
XSWITCH LEG
ROOM SWITCH
OPTIONAL N.O. OCCUPANCY
SENSOR CONTACT.
*
Regular Load
REGULAR LINE
NEUTRAL
REGULAR LINE
HOT
2
120V
277V
REGULAR
PANEL
20 AMP
BREAKER
EMERGENCY
PANEL
UL1008
Transfer Switch
WEB VERSION
© 2023 Leviton Mfg. Co., Inc.
Common Wiring Scenarios
One Light Fixture in a room
For some installations which require only a single emergency light in an area
with no regular lighting.
Two 3-Way Switches
When using two 3-way switches in a room to control the lighting from
two locations.
Dual Light Level Switching
For installations with dual light level controls. Can only be used when separate
ballasts are used for A leg and B leg. If using modern bi-level ballasts, contact
manufacturer for appropriate part number.
Wiring as shown will cause only “A ballasts to operate as emergency xtures. If
all tubes are desired for emergency: use two ECS00-110’s or contact
the manufacturer.
Model: ECS00-110
Emergency
Load
EMERGENCY HOT BLUE
EMERGENCY
SWITCH LEG
YELLOW
EMERGENCY NEUTRAL
5
6
120V 1 BLACK
277V 2 ORANGE
REGULAR LINE HOT
*
RED
WHITE
1
3
4
20 AMP
BREAKER
SWITCH LEG
ROOM SWITCH
OPTIONAL N.O. OCCUPANCY
SENSOR CONTACT.
*
REGULAR LINE
NEUTRAL
REGULAR LINE
HOT
2
120V
277V
REGULAR
PANEL
20 AMP
BREAKER
EMERGENCY
PANEL
UL1008
Transfer Switch
RL
RL
Sensing, Switching
& Relay Logic
Model: ECS00-110
Emergency
Load
EMERGENCY HOT BLUE
EMERGENCY
SWITCH LEG
YELLOW
EMERGENCY NEUTRAL
5
6
120V 1 BLACK
277V 2 ORANGE
REGULAR LINE HOT
*
RED
WHITE
1
3
4
20 AMP
BREAKER
A
OPTIONAL N.O. OCCUPANCY
SENSOR CONTACT.
*
REGULAR LINE
NEUTRAL
REGULAR LINE
HOT
2
120V
277V
REGULAR
PANEL
20 AMP
BREAKER
EMERGENCY
PANEL
UL1008
Transfer Switch
RL
RL
Sensing, Switching
& Relay Logic B
B
A
A
Model: ECS00-110
Emergency
Load
EMERGENCY HOT BLUE
EMERGENCY
SWITCH LEG
YELLOW
EMERGENCY NEUTRAL
5
6
120V 1 BLACK
277V 2 ORANGE
REGULAR LINE HOT
*
RED
WHITE
1
3
4
20 AMP
BREAKER
A
OPTIONAL N.O. OCCUPANCY
SENSOR CONTACT.
*
REGULAR LINE
NEUTRAL
REGULAR LINE
HOT
2
120V
277V
REGULAR
PANEL
20 AMP
BREAKER
EMERGENCY
PANEL
UL1008
Transfer Switch
RL
RL
Sensing, Switching
& Relay Logic Regular Load
B
What to do if...
ECS00-110 does not function properly on startup perform the following tests:
Test Normal Operation: Ensure branch circuit breaker is connected and utility power is available. If GREEN LED is not illuminated, conrm wiring connections and
continuity to branch panels.
Test Emergency Operation: Ensure emergency source is connected and RED LED is illuminated. Turn room switch to “OFF” position, and ensure that emergency
lights stay illuminated for at least 2.5 seconds. If emergency lights do not stay on for at least 2.5 seconds, conrm wiring connections and perform testing on
emergency panel and emergency power source.
No maintenance is required to keep the ECS00-110 functional. However, regular testing should be performed when the lamps or ballasts have been replaced or
when facility remodeling has taken place.
For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only) www.leviton.com
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benet of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship
under normal and proper use for ve years from the purchase date. Levitons only obligation is to correct such defects by repair or replacement, at its option. For details visit www.
leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product
is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in
accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and tness for a particular purpose, but if any implied
warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and tness for a particular purpose, is limited to ve years. Leviton
is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or prots or
delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
FCC STATEMENT
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Any changes or modications not expressly approved by Leviton could void the user’s authority to operate this equipment.
IC STATEMENT
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:
(1) this device may not cause interference,
(2) this device must accept any interference, including interference that may cause undesired operation of the device.
IMPORTANT! Any changes or modications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
This Class A digital apparatus complies with Canadian ICES-003.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada ULC to the attention
of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1-800-405-5320.
TRADEMARK DISCLAIMER:
Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the
trademarks of their respective owners; such use is not meant to imply afliation, sponsorship, or endorsement.
Relay Panel Low Voltage Switching Line Drawing
From lighting control panel to emergency power control,
three #12 wires are necessary: 1) Hot, 2) Switch Leg, 3) Neutral
REGULAR
ROOM
LIGHTS
DESIGNATED
EMERGENCY
LIGHTS
NORMAL
POWER
PANEL
EMERGENCY
POWER
PANEL
UL 924
ECS00-110
CONTROL
ECS00-110
CONTROL
ECS00-110
CONTROL
LIGHTING
CONTROL
PANEL
LOW VOLTAGE
SWITCH TO ADDITIONAL
ECS00-110 CONTROLS
UL 1008
Transfer Switch
Regular
Utility Power
Emergency
Power Source
Neutral
Not Shown
Single Line Drawings
On a 20 Amp circuit, one or more emergency power controls
(Model ECS00-110) can be used to control emergency lighting loads.
One ECS00-110 is required per switch leg. A single ECS00-110 can carry a
maximum of 10 Amps of emergency lighting load.
ECS00-110
EMERGENCY
20 AMP
BREAKER
TO ADDITIONAL
ECS00-110 CONTROLS
ECS00-110 ECS00-110 ECS00-110 ECS00-110
Standard Line Voltage Switching Line Drawing
NORMAL
POWER
PANEL
UL 924
ECS00-110
CONTROL
DESIGNATED
EMERGENCY
EMERGENCY
POWER
PANEL
REGULAR
ROOM
LIGHTS
ECS00-110
CONTROL
ECS00-110
CONTROL
UL 1008
Transfer Switch
Regular
Utility Power
Emergency
Power Source
S
Neutral
Not Shown
TO ADDITIONAL
ECS00-110 CONTROLS
WEB VERSION
  • Page 1 1
  • Page 2 2

Leviton ECS00-DDW User manual

Type
User manual

Leviton ECS00-DDW is a versatile emergency lighting control device. With universal mounting, it can be installed in a variety of locations, including in 4-11/16" junction boxes with blank covers. The ECS00-DDW is designed for switching loads and can handle up to 10A of ballast current. It features automatic diagnostic capabilities, indicated by a green LED, ensuring proper operation during an emergency. Additionally, the device provides a 2.5-second emergency light-on period when the room switch is turned off, functioning as a test switch replacement.