MK K1402M is a master trailing edge dimmer module, designed to work with K1401S and K1402S slave modules. It can be used to control resistive and capacitive/electronic transformer lighting loads only. The device features 8 operating modes, including dimmer with switch-on memory, cyclic dimmer, stairwell lighting, and 0/1-10V control. It has a maximum load rating of 1kW/900VA and can be used with up to 4 slave dimmers.

MK K1402M is a master trailing edge dimmer module, designed to work with K1401S and K1402S slave modules. It can be used to control resistive and capacitive/electronic transformer lighting loads only. The device features 8 operating modes, including dimmer with switch-on memory, cyclic dimmer, stairwell lighting, and 0/1-10V control. It has a maximum load rating of 1kW/900VA and can be used with up to 4 slave dimmers.

Page 1
K1402M
®
®
1kW Trailing Edge Dimmer Module - Master
Installation & Operating Instructions
SAFETY:
Danger 220-240 Volts: Always disconnect the electricity supply
before commencing any work on the installation of device or
changing lamps or bulbs.
The device should be installed by a competent person or a qualified
electrician in accordance with the device’s installation instructions and the
appropriate current national wiring regulations.
It is essential that all connections are made as instructed, that cables are
not stressed and that terminals are fully tightened.
The mains supply to this product must be protected by an appropriate
fuse or MCB.
TECHNICAL INFORMATION:
Reduction of the dimmer power:
If this product is used in an ambient temperature exceeding 40°C, the
maximum allowable load will need to be reduced according to the table
below. This will prevent the internal thermal protection in the product from
activating and switching the load off.
Vorsicht! Erhöhte
Strahlung
Vorsicht! Kontamination Vorsicht! Kontamination Vorsicht, Gefahr durch
Abquetschen
Vorsicht, Gefahr durch
Abschneiden
Vorsicht, Gefahr durch
Abstürzen
Vorsicht, Gefahr durch
ätzende Stoffe
Vorsicht, Gefahr durch
elektrischen Strom
Vorsicht, Gefahr durch
elektrischen Strom
Vorsicht, Gefahr durch
elektromagnetische
Strahlung
Vorsicht, Gefahr durch
explosionsgefährliche
Stoffe
Vorsicht, Gefahr durch
feuergefährliche Stoffe
Vorsicht, Gefahr durch
giftige Stoffe
Vorsicht, Gefahr durch
heiße Oberfläche
Vorsicht, Gefahr durch
Laserstrahlung
Vorsicht, Gefahr durch
Radioaktivität
Vorsicht, Gefahr durch
Rutschen
Vorsicht, Gefahr durch
Stolpern
Vorsicht, Gefahr durch
Verwickeln
Vorsicht, Warnung vor
einer Gefahrstelle
Vorsichtig verschieben!
- veraltet -
Während der
Schweißarbeiten,
Arbeitsstelle beobachten
Wandbrände nicht von
oben löschen
Wandbrände von unten
nach oben löschen
Wandhydrant Wandhydrant (2.
Vorschlag)
Wandhydrant, mit Angabe
des Anschlusses
Wareneingang -
Freigegeben
Wareneingang - Gesperrt Wärmeabzugseinrichtung
-10
0
10
20
30
40
50
60
70
80
90
100
0
200
400
600
800
1000
Ambient temperature in °C
Maximum Rated Load (W)
GENERAL:
Master-Slave Operation
The K1402M master trailing edge dimmer can be used with up to 2 x
K1401S leading edge slaves and 2 x K1402S trailing edge slaves.
The slave dimmers will automatically follow the operating mode and load
state of the master.
Slave units are connected to the master as follows:
A1, B1
,
C
R
for connection of K1402S trailing edge slave
dimmers only
A2, B2
,
L
R
for connection of K1401S leading edge slave
dimmers only
Slave Units must only be connected to other slaves of the same type
Hohlwand-Installationsklei
nverteiler
Hörgeschädigtensysmbol Hubschrauber-Landeplatz
, Warnung vor
Rotorblättern
Hunde tragen während
Rolltreppenbenutzung
Hupen Hupen geboten
-2.Vorschlag-
Hygienischen Atemschutz
benutzen
Im Brandfall keinen
Aufzug benutzen!
Im Brandfall werden sie
alarmiert! Wenn Sie einen
Brand entdecken, Brand
Impulslichtbogenschweiß
en
Imputz-Installationsdose Inert-Gas-Einrichrung
Infektiöse Stoffe
[Unterklasse 6.2] [IMO]
Information für die
Feuerwehr
Information,
Informationsstelle
Informieren Sie sich bitte
über die Lage der
Treppen, Notausgänge.
Inline-Skating nicht
gestattet
Installationskanal
Instrumente Instrumentiertische,
-flächen
Internationaler
Landanschluss
Ionisierende
Strahlungsenergie
Isolierende
Schutzhandschuhe für
Arbeiten unter
Kalibriert
Kaltlicht; Elektromedizin,
Beleuchtung über
Lichtleiter
Karzinogenität
(Gefahrenkategorien 1A,
1B und 2)
Keimzell-Mutagenität
(Gefahrenkategorien 1A,
1B und 2)
Kein Handhaken
verwenden
Kein Trinkwasser Kein Trinkwasser (ISO)
Note: The outputs of the K1402M and K1402S trailing edge
dimmers may be connected in parallel to drive a single load
greater than 1kW/900VA.
Controls P1 and P2:
used to set the load brightness or timer functions
(dependent upon the operating mode)
T1-T3 connections:
for connection of the push button control
switches
0-10V / Gnd
connections:
for 0/1-10V dimmer controls
A1, B1, A2, B2 Slave output connections
L N
+12V
0-10V
Gnd
SE
T1
T2
T3
Mode
1
5
37
8 2
6 4
A1 B1 A2 B2 Slave-Out
R, C R, L
K1402M
1kW Trailing Edge Dimmer - Master
For use with K1401S and K1402S slaves modules
R, C
60-1000VA 50-900VA
P1 P2
®
®
EN 60669-2-1
Made in Germany
50061979-001
ε
220-240V~ / 50Hz
220V~ / 60 Hz
F
Operating Mode Selector Switch
LoadL N
General:
Operating voltage:
220-240V~ / 50Hz
220V~ / 60Hz
Ambient operating temperature: -5 to +40°C
Standards: EN 60669-2-1
Dimensions, (w x h): 108 x 55mm, 6 DIN modules
Technical Specification:
Control wiring lengths:
Maximum of 100m in total
Use 0.5-0.75mm mains rated cable
Load compatibility:
Resistive and Capacitive/Electronic
transformer lighting loads only
Minimum load: 60W / 50VA
Load rating:
Resistive / Incandescent 1000W
Mains Halogen 1000W
Low Voltage Halogen with
Electronic transformers
900VA
Page 2
INSTALLATION:
The dimmer module is designed for mounting into distribution and
consumer units containing 35 mm DIN rail according to EN50022.
Please observe the following points during installation:
All master and slave dimmers must be connected to the same supply
phase.
The mains supply to the dimmer(s) must be protected by a suitable fuse
or MCB rated no greater than 16A
Do not exceed maximum control line length of 100m and do not run
slave control lines parallel to mains and network cables.
Always observe the transformers recommended loading guidelines.
Load transformers at or close to their full rated capacity. Do not connect
a small load to a larger transformers, (e.g. a 35W lamp on a 600VA
transformer)
Ensure that slaves are wired to the correct control terminals and that
the polarity is observed
Vorsicht! Erhöhte
Strahlung
Vorsicht! Kontamination Vorsicht! Kontamination Vorsicht, Gefahr durch
Abquetschen
Vorsicht, Gefahr durch
Abschneiden
Vorsicht, Gefahr durch
Abstürzen
Vorsicht, Gefahr durch
ätzende Stoffe
Vorsicht, Gefahr durch
elektrischen Strom
Vorsicht, Gefahr durch
elektrischen Strom
Vorsicht, Gefahr durch
elektromagnetische
Strahlung
Vorsicht, Gefahr durch
explosionsgefährliche
Stoffe
Vorsicht, Gefahr durch
feuergefährliche Stoffe
Vorsicht, Gefahr durch
giftige Stoffe
Vorsicht, Gefahr durch
heiße Oberfläche
Vorsicht, Gefahr durch
Laserstrahlung
Vorsicht, Gefahr durch
Radioaktivität
Vorsicht, Gefahr durch
Rutschen
Vorsicht, Gefahr durch
Stolpern
Vorsicht, Gefahr durch
Verwickeln
Vorsicht, Warnung vor
einer Gefahrstelle
Vorsichtig verschieben!
- veraltet -
Während der
Schweißarbeiten,
Arbeitsstelle beobachten
Wandbrände nicht von
oben löschen
Wandbrände von unten
nach oben löschen
Wandhydrant Wandhydrant (2.
Vorschlag)
Wandhydrant, mit Angabe
des Anschlusses
Wareneingang -
Freigegeben
Wareneingang - Gesperrt Wärmeabzugseinrichtung
Important:
Inductive loads (i.e. conventional wire-wound transformers,
etc.) must not be connected to trailing edge dimmers.
Control Wiring for operating Modes 1-7:
Control switches T1-3 for operating modes 1-7 should be push-to-make
momentary contact switches.
Up to 10 operating switches may be wired in parallel with Neon indicators
being allowed on control line T1 only
Example1: Multiple control buttons:
L
T
T1
T
T2
T
T
T
T3
T
Example 2: Wiring for Multiple Master Dimmers with common Central-ON
and Central-OFF
L
N
T
T
T
T
T1 T2 T3
L N
T1 T2 T3
L N
MASTER DIMMER 1 MASTER DIMMER 2
Load
Load
T1 = Separate Dimming control for each master
T2 = Central-ON for both master dimmers
T3 = Central-OFF for both master dimmers
Control Wiring for operating Mode 8:
Control switch T1 for operating mode 8 should be a standard single pole
light switch with dimming via the rotary 0/1-10V potentiometer connected
between 0-10V and Gnd on the Master dimmer
L
N
T1 T2 T3
+12V
0-10V
Gnd
SE
L N
T
Control input
0...10V
Button input
T1 - T3
Mains connection
220-240V~ / 50Hz
220V~ / 60Hz
Load
Switch
Load
Switch
MASTER DIMMER
L N
+12V
0-10V
Gnd
SE
T1
T2
T3
Mode
1
5
37
8 2
6 4
A1 B1 A2 B2 Slave-Out
R, C R ,L
K1402M
1kW Trailing Edge Dimmer - Master
For use with K1401S and K1402S slaves modules
R, C
60-1000VA 50-900VA
P1 P2
®
®
EN 60669-2-1
Made in Germany
50061979-001
ε
220-240V~ / 50Hz
220V~ / 60 Hz
F
L N
T5A H250V~
IN
Out
IN
Out
Slave
A AB B
K1401S
1kW Leading Edge Dimmer - Slave
For use with K1401M and K1402M master modules
R, L
60-1000VA 50-900VA
®
®
EN 60669-2-1
Made in Germany
50061978-001
ε
220-240V~ / 50Hz
220V~ / 60 Hz
L N
IN
Out
IN
Out
Slave
A AB B
K1402S
1kW Trailing Edge Dimmer - Slave
For use with K1401M and K1402M master modules
R, C
®
®
60-1000VA 50-900VA
EN 60669-2-1
Made in Germany
50061980-001
ε
220-240V~ / 50Hz
220V~ / 60 Hz
F
L N
F
F
F
220-240V~ / 50Hz
220V~ / 60Hz
Master-dimmer operating Mode 1 – 8
Control connection (A,B)
slave dimmer
Page 3
OPERATION:
Operating Mode 5
Time-On period
P1
1sec
70sec
8min
1hr
2.3hr
Turn-Off warning period
P2
1sec
35sec
60sec
80sec
8min
Operating Mode 6
Time-On period
P1
1sec
70sec
8min
1hr
2.3hr
Load brightness
P2
Minimum
Maximum
Function of buttons T1-T3
Function buttons T1-T3 are used to operate the dimmer functions
according to the set operating mode as detailed below.
Up to 10 buttons may be wired in parallel on the control wiring.
Mode Action T1 T2 T3
1 - 4
Short press ON / OFF
Long Press Dim Up / Down
Central ON
(Maximum)
Central OFF
5 - 6
Short press
reset time-on
period
Long Press
Central ON
(Maximum)
Central OFF
7
Short press ON / OFF set scene 1 set scene 2
Long Press Dim Up / Down
Central ON
(Maximum)
Central OFF
8
Switching
ON
ON
Switching
OFF
OFF
Central ON
(Maximum)
Central OFF
TROUBLESHOOTING:
If your product does not work properly please check the
following items,
Mains supply MCB and voltage.
Cable connections and wiring.
Ensure that connected lamps are operational and have not blown.
Ambient temperature and ensure dimmer is not overloaded.
Note: Normal voltage and frequency fluctuations on the mains supply can manifest
as flicker on the lamps and does not represent a fault with the product.
Contact Details
If you require advice on the installation or use of these products please
contact the appropriate technical service helpline:
UK and Ireland
+44 (0)1268 563720
UAE (+971) 4 807320
Singapore 1800 461 6333
Malaysia 1800 88 4507
Hong Kong 2953 6379
India (+91) 44 2616 1234
OTHER INFORMATION:
Disposal:
At the end of their useful life the packaging and product should be
disposed of via a suitable recycling centre. Do not dispose of with your
normal household waste. Do not burn.
Guarantee:
MK Electric undertakes to replace or repair at its discretion goods should
they become defective within 2 years solely as a result of faulty materials
and workmanship. Understandably if the product has not been installed,
operated or maintained in accordance with the instructions, has not been
used appropriately or if any attempt has been made to rectify, dismantle or
alter the product in any way the guarantee will be invalidated.
The guarantee states MK Electric’s entire liability. It does not extend to
cover consequential loss or damage or installation costs arising from the
defective product. This guarantee does not restrict, infringe or in any way
affect the normal statutory or other rights of the consumer.
50061984-001_A
Operating Modes:
Mode Function P1 P2
1
Dimmer with
switch-on memory
Minimum
Brightness
Maximum
Brightness
2
Dimmer without
switch-on memory
Minimum
Brightness
Maximum
Brightness
3
Cyclic dimmer with
switch-on memory
Minimum
Brightness
Maximum
Brightness
4
Cyclic dimmer without
switch-on memory
Minimum
Brightness
Maximum
Brightness
5
Stairwell lighting with low
level turn off warning
Time-On period
(1sec - 2.3hrs)
Turn-Off warning
(1sec - 8min)
6
Stairwell lighting without
turn off warning
Time-On period
(1sec - 2.3hrs)
Brightness
7 Scene Controller Scene 1 level Scene 2 level
8 0/1-10V control n/a n/a
®
®
MK Electric
The Arnold Centre, Paycocke Rd, ,
Basildon Essex SS14 3EA UK
Telephone +44 (0)1268 563000
Fax +44 (0)1268 563404
MK Electric (Middle East)
Honeywell ME, FZE, P.O. Box 18530,
Jebel All, Dubai U.A.E.
Telephone (+971) 4 807 3200
Fax (+971) 4 881 5733
MK Electric (Singapore) Pte Ltd
8 Pandan Crescent, UE Tech Park,
#01-06 (LL4), Singapore 128464
Telephone (+65) 6461 6333
Fax (+65) 6461 6336 / 6338
MK Electric (Malaysia) Sdn Bhd
(Co. No. 39068-A). Komplek Perusahaan LTAT,
Jalan Pengapit 15/19, 40000 Shah Alam,
Selangor Darul Ehsan, Malaysia
Telephone (+603) 5519 4507
Fax (+603) 5510 8867
MK Electric (China) Ltd
25/F, Honeywell Tower, Olympia Plaza,
255 King’s Road, North Point, Hong Kong
Telephone (+852) 2331 9133
(+852) 2834 1988
Fax (+852) 2151 9465
Honeywell ED&S India Ltd
Crescendo, 995 B, Second Avenue, ,,
Annanagar, Chennai, India PIN: 60040
Telephone (+91) 44 2616 1234
(+91) 44 6632 6789
Fax (+91) 44 2616 1235
www.electrical.honeywell.com
Novar ED&S Ltd, (A Honeywell Company)
Arlington Business Park, Bracknell,
Berkshire, RG12 1EB, UK
Copyright Novar ED&S Ltd 2011. All rights reserved.
  • Page 1 1
  • Page 2 2
  • Page 3 3

MK K1402M Installation guide

Category
Dimmers
Type
Installation guide

MK K1402M is a master trailing edge dimmer module, designed to work with K1401S and K1402S slave modules. It can be used to control resistive and capacitive/electronic transformer lighting loads only. The device features 8 operating modes, including dimmer with switch-on memory, cyclic dimmer, stairwell lighting, and 0/1-10V control. It has a maximum load rating of 1kW/900VA and can be used with up to 4 slave dimmers.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI