SELF-POWERED:
1. For SA models, plug the battery into the circuit board per (Figure 3) self-powered sign.
WLX
04/14/2010
CEILING/END MOUNT - SINGLE OR DOUBLE FACE:
1. Loosen the four (4) plastic screws (one in each corner) on the front cover / faceplate and then remove the faceplate.
For double face exits the other faceplate is attached from the inside with screws recessed behind the front ones.
2. Remove the canopy/nipple assembly by unscrewing the nut from the inside of the cabinet (Figure 4)
3. Feed the supply wires through the threaded nipple - leave at least 8 inches of slack wire.
4. Securely mount the canopy in place (mounting holes fit standard electrical boxes)
5. Mount the exit sign on the installed canopy, passing the threaded nipple and slack wires through the drilled hole.
6. Secure the exit sign to the threaded nipple using the supplied lock-washer and nut (Figure 4).
7. Connect voltage supply per diagram supplied (Figure 3). Insulate unused wire! CAUTION! - Failure to insulate
unused wire may result in a shock hazard or unsafe condition as well as equipment failure.
8. Route wires and secure them in place.
9. Peel the backing off the double sided tape from inside the cover. Select the pictogram, align and stick to the inside of
the cover.
10. Replace the cover and tighten the four (4) plastic screws.
11. Turn on the voltage supply.
WALL MOUNT - SINGLE FACE:
1. Loosen the four (4) plastic screws (one in each corner) on the front cover / faceplate and then remove the cover.
(Figure 1)
2. Install the four (4) mounting feet to the back of the cabinet (Figure 2)
3. Mount the exit securely in place using the four (4) mounting screw holes (one located in each corner -
screws not supplied).
4. Drill appropriate sized hole(s) in the enclosure for electrical entrance.
Use a rated watertight connector/conduit hub(s) to connect AC supply to the enclosure.
5. Pass power wires through previously drilled holes(s) and connector(s).
6. Connect supply per diagram provided (Figure 3). Insulate unused wire! CAUTION! - Failure to insulate unused
wire may result in a shock hazard or unsafe condition as well as equipment failure.
7. Route wires and secure them in place.
8. Peel the backing off the double sided tape from inside the cover. Select the pictogram, align and stick to the inside of
the cover.
9. Replace the cover and tighten the four (4) plastic screws.
10. Turn on the voltage supply.
INSTRUCTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Disconnect power before performing work on electrical equipment.
3. Use caution when servicing batteries.
4. Equipment should be mounted in locations and at heights where unauthorized personnel will not readily subject it to
tampering.
5.
6. Do not use this equipment for other than its intended purpose.
7. Servicing of this equipment should be performed by qualified service personnel.
8. SAVE THESE INSTRUCTIONS!
The use of accessory equipment not recommended by Beghelli USA, may cause an unsafe condition, and
will void the unit’s warranty.
Beghelli U.S.A., 3810 Executive Way, Miramar, Florida, Tel: (954) 442-6600 Fax: (954) 442-6677