Emerson Network Card P/N MMI-20019808 User manual

Type
User manual

This manual is also suitable for

User Manual
P/N MMI-20019808, Rev. AC
July 201
2
Micro Motion
®
EtherNet/IP Module
Micro Motion Customer Service
Location Telephone number
U.S.A. 800-522-MASS (800-522-6277) (toll free)
Canada and Latin America +1 303-527-5200 (U.S.A.)
Asia Japan 3 5769-6803
All other locations +65 6777-8211 (Singapore)
Europe U.K. 0870 240 1978 (toll-free)
All other locations +31 (0) 318 495 555 (The Netherlands)
Contents
User Manual I
Contents
Chapter 1 Before You Begin
1.1 About the Micro Motion EtherNet/IP Module............................................................1
1.1.1 Functional overview ....................................................................................1
1.1.2 Communications.........................................................................................2
1.1.3 External view of device ................................................................................3
1.1.4 Default web pages.......................................................................................3
1.1.5 Setting up for the petroleum measurement or concentration
measurement application ...........................................................................3
Chapter 2 Installation
2.1 Components ............................................................................................................5
2.2 Device installation ....................................................................................................5
2.3 Micro Motion Ethernet Config Tool installation (optional) ........................................9
2.3.1 System requirements ..................................................................................9
2.3.2 Installation steps .........................................................................................9
2.4 Final steps ..............................................................................................................10
Chapter 3 Basic Network Configuration
3.1 TCP/IP settings .......................................................................................................13
3.1.1 IP access control........................................................................................15
3.2 Modbus serial network settings ..............................................................................16
Chapter 4 Micro Motion Web Server
4.1 Overview ................................................................................................................17
4.2 General access information ....................................................................................17
4.2.1 Ports..........................................................................................................17
4.2.2 Users .........................................................................................................17
4.3 Micro Motion web pages ........................................................................................17
4.3.1 Home page for standard configuration......................................................18
4.3.2 Home page for concentration measurement configuration.......................19
4.3.3 Home page for petroleum measurement configuration ............................21
II Micro Motion EtherNet/IP Module
Contents
Chapter 5 Troubleshooting
5.1 LED indicators.........................................................................................................23
5.2 Common problems ................................................................................................24
Appendix A Connector Pin Assignments
A.1 Ethernet connector ................................................................................................25
A.2 Power connector ....................................................................................................25
A.3 Micro Motion Ethernet Config Tool connection ......................................................26
A.3.1 Configuration cable...................................................................................26
A.3.2 RJ-11 (EtherNet/IP Module) .......................................................................26
A.3.3 DBF9 (PC) ..................................................................................................27
A.4 Modbus serial network interface.............................................................................27
A.4.1 Bias resistors .............................................................................................27
A.4.2 Termination ..............................................................................................27
A.4.3 Pin assignments (EtherNet/IP Module) ......................................................28
A.5 Typical connection .................................................................................................28
Appendix B Device Profile
B.1 Object classes.........................................................................................................29
B.2 Object details .........................................................................................................29
B.2.1 Identity Object, Class 01h..........................................................................29
B.2.2 Message Router, Class 02h ........................................................................31
B.2.3 Assembly Object, Class 04h.......................................................................31
B.2.4 Port Object, Class F4h................................................................................33
B.2.5 TCP/IP Interface Object, Class F5h .............................................................34
B.2.6 Ethernet Link Object, Class F6h..................................................................36
B.2.7 Diagnostic Object, Class AAh.....................................................................36
B.2.8 Parameter Data Input Mapping Object, Class B0h......................................37
B.2.9 Parameter Data Output Mapping Object, Class B1h ..................................38
B.3 I/O data ..................................................................................................................39
B.3.1 Input assembly for standard configuration ................................................39
B.3.2 Output assembly for standard configuration .............................................40
B.3.3 Input parameters (explicit data) for standard configuration.......................40
B.3.4 Output parameters (explicit data) for standard configuration ...................42
B.3.5 Input assembly for concentration measurement configuration .................43
B.3.6 Output assembly for concentration measurement configuration ..............44
B.3.7 Input parameters (explicit data) for concentration measurement
configuration ............................................................................................44
B.3.8 Output parameters (explicit data) for concentration measurement
configuration ............................................................................................46
B.3.9 Input assembly for petroleum measurement configuration.......................47
B.3.10 Output assembly for petroleum measurement configuration....................48
Contents
User Manual III
B.3.11 Input parameters (explicit data) for petroleum measurement
configuration ............................................................................................48
B.3.12 Output parameters (explicit data) for petroleum measurement
configuration ............................................................................................50
B.4 Get and Set services................................................................................................51
B.4.1 Get Attribute Single service.......................................................................51
B.4.2 Set Attribute Single service........................................................................51
B.5 Data types ..............................................................................................................52
B.6 Codes and integer values........................................................................................52
B.7 Status words...........................................................................................................61
B.7.1 Status Word 1 ...........................................................................................61
B.7.2 Status Word 2 ...........................................................................................61
B.7.3 Status Word 3 ...........................................................................................62
B.7.4 Status Word 4 ...........................................................................................62
B.7.5 Status Word 5 ...........................................................................................63
B.7.6 Status Word 6 ...........................................................................................64
B.7.7 Status Word 7 ...........................................................................................65
Appendix C Specifications
C.1 Physical ..................................................................................................................67
C.1.1 Housing.....................................................................................................67
C.1.2 Dimensions ...............................................................................................67
C.2 Electrical.................................................................................................................67
C.2.1 Power supply.............................................................................................67
C.2.2 Power consumption ..................................................................................67
C.3 Environmental........................................................................................................67
C.3.1 Relative humidity ......................................................................................67
C.3.2 Temperature .............................................................................................67
C.4 Regulatory compliance...........................................................................................68
C.4.1 EMC compliance (CE) ................................................................................68
C.4.2 UL/c-UL compliance ..................................................................................68
C.4.3 Galvanic isolation on Modbus serial interface ............................................68
Appendix D Return Policy
D.1 Requirements.........................................................................................................69
D.1.1 New and unused equipment......................................................................69
D.1.2 Used equipment........................................................................................69
IV Micro Motion EtherNet/IP Module
Contents
Before You Begin
User Manual 1
1 Before You Begin
1.1 About the Micro Motion EtherNet/IP Module
The Micro Motion EtherNet/IP Module is a customization of the Anybus Communicator from
HMS Industrial Networks. The EtherNet/IP Module enables integration of industrial devices into
the Ethernet network with no loss of functionality, control, or reliability. The EtherNet/IP
Module can be used for new or retrofit installations.
This manual contains only the information required to install, configure, and use the EtherNet/
IP Module. Other OEM features are still enabled on the device, but are not documented here.
For information on other features of the device, see the manual entitled Anybus Communicator
User Manual, available on the HMS web site.
1.1.1 Functional overview
The EtherNet/IP Module acts as a gateway between the serial output of a Micro Motion device
and an EtherNet/IP network.
The EtherNet/IP Module is a Modbus master and an Ethernet slave. On the Modbus side, it polls
the transmitter for a standard set of process variables and stores the data locally. See Section
B.3 for a list of available data. On the Ethernet side, it receives requests for data and responds
with the current values.
The following figures illustrate the EtherNet/IP Module in operation.
In Figure 1-1, the EtherNet/IP Module is installed with a Model 1500 or Model 2500
transmitter. See the Product Data Sheet for a list of all supported transmitters. All
sensor connections are supported (integral, 4-wire, 9-wire).
In Figure 1-2, the EtherNet/IP Module is part of an MVD Direct Connect installation.
The web browser is used for transmitter configuration and administration, via a
connection to the Micro Motion web pages on the EtherNet/IP Module.
The configuration loop is used only by the Micro Motion Ethernet Config Tool. In typical
installations, this tool is not needed.
2 Micro Motion EtherNet/IP Module
Before You Begin
Figure 1-1 EtherNet/IP Module with Model 1500 or Model 2500 transmitter
Figure 1-2 EtherNet/IP Module in MVD Direct Connect installation
1.1.2 Communications
The following communications methods and protocols are supported:
EtherNet/IP Module to Micro Motion transmitter: Modbus RTU on RS-485
EtherNet/IP Module to Ethernet network:
EtherNet/IP group 2 and 3 servers
Web server
10/100 Mbit/sec, twisted pair
PLC
EtherNet/IP Module
Transmitter
Other devices
(SCADA, PC, Inverter)
To sensor
PC with Micro Motion Ethernet
Config Tool
Configuration loop
(with configuration cable)
Modbus/RS-485
Ethernet
Web browser
PLC
EtherNet/IP Module
Core processor
Other devices
(SCADA, PC, Inverter)
To sensor
PC with Micro Motion Ethernet
Config Tool
Configuration loop
(with configuration cable)
Modbus/RS-485
Ethernet
Web browser
Barrier
Before You Begin
User Manual 3
1.1.3 External view of device
Figure 1-3 External view of device
1.1.4 Default web pages
The EtherNet/IP Module is preloaded with the Micro Motion standard web pages. These web
pages allow the user to view process data and alerts, to configure the most commonly used
parameters on the transmitter, to perform maintenance procedures, and to download support
files from the device.
1.1.5 Setting up for the petroleum measurement or concentra-
tion measurement application
To support the petroleum measurement or concentration measurement application,
Micro Motion supplies alternate sets of web pages and configuration files. These are available
for download from the Micro Motion web site.
A
Ethernet connector
B
Configuration Switches
C
Status LEDs
D
PC connector (configuration)
E
Modbus serial connector (transmitter)
F
Power connector
G
DIN rail connector
4 Micro Motion EtherNet/IP Module
Before You Begin
Installation
User Manual 5
21
2 Installation
2.1 Components
Ensure that you have all required components:
Micro Motion EtherNet/IP Module
Power connector
Micro Motion EtherNet/IP Resource CD
- Micro Motion EtherNet/IP Module User Manual
- EDS file
- Micro Motion Ethernet Config Tool
Configuration cable
Modbus serial cable and connector (included)
Ethernet cable and connector (not included)
2.2 Device installation
1. If you are using the EtherNet/IP Module with a transmitter, mount the transmitter and
wire it to the sensor and to power.
2. If you are using a Micro Motion MVD Direct Connect flowmeter, mount and wire the
core processor and barrier. See the following illustration to identify the barrier
terminals.
44 (RS-485/B)
43 (RS-485/A)
42 (VDC +)
41 (VDC –
14 (RS-485/B)
13 (RS-485/A)
12 (VDC +)
11 (VDC –
I.S. terminals
for connection to core
processor
Non-I.S. terminals
for connection to remote
host and power supply
Barrier
6 Micro Motion EtherNet/IP Module
Installation
3. If you are using a transmitter:
a. Power up the transmitter.
b. Set the Modbus address on the transmitter to 1.
c. If your transmitter does not support Modbus auto-detect, configure its RS-485
terminals as follows:
- Modbus RTU
- 38400 baud
- 2 stop bits
- No parity
4. If you are using MVD Direct Connect:
a. Power up the core processor and barrier.
b. Set the Modbus address on the core processor to 1.
5. Ensure that the following slot registers are available for use by the EtherNet/IP Module:
- 655–750
- 751–846
If you are currently using these slot registers, you must reprogram your Modbus
interface.
6. Mount the EtherNet/IP Module on the DIN rail.
7. Wire the EtherNet/IP Module to power (24 VDC).
1
2
1
2
Snap on Snap off
Power
1) 24 VDC
2) Ground
1
9
5
6
1
2
4
1
Installation
User Manual 7
8. Install the Modbus serial cable between the EtherNet/IP Module and the RS-485
terminals on the transmitter (or the I.S. barrier, if present).
9. Set the configuration dip switches on the EtherNet/IP module as follows:
- Switches 1–7: Off
- Switch 8: On
This sets the IP addess to 192.168.0.1.
10. If you are using a Model 1500, Model 2500, or Series 3000 transmitter, ensure that the
RS-485 terminals are in RS-485 mode. You may need to cycle power to the transmitter
and wait 15 seconds before applying power to the EtherNet/IP Module.
11. Power up the EtherNet/IP Module. At this point, the module will attempt to make a
Modbus connection to the transmitter. If the Subnet Status LED (LED 5) is green,
continue. If it is not green, see Section 5.1.
12. Set the network settings for the EtherNet/IP Module.
a. Change Ethernet address setting for your PC so that it is on the same subnet as
the device. When prompted, enter the following:
- IP address: 192.168.0.x, where x is something other than 1
- Subnet mask: 255.255.255.0
b. Disable the popup blocker on your web browser.
c. Use a crossover cable (or a standard cable with a switch) and your web browser
to connect to the device, using the IP address assigned in Step 6: 192.168.0.1.
d. At the login screen, log in as user admin. The default password is admin. Ignore
the auto-configuration popup window.
e. On the Network Settings page, change the settings as required, and close the
web browser.
f. At the EtherNet/IP Module, set all dip switches to Off.
g. Cycle power to the EtherNet/IP Module.
1
9
5
6
1
2
4
1
Modbus serial connector
1) Not used
2) Not used
3) Not used
4) Not used
5) Not used
6) Not used
7) Not used
8) RS-485/A
9) RS-485/B
Transmitter
Modbus terminals
RS-485/A RS-485/B
Model 1500 33 34
Model 1700 with analog outputs 5 6
Model 2500 33 34
Model 2700 with analog outputs 5 6
Model 3500 with screw-type or
solder-tail terminals
32a 32b
Model 3500 with I/O cables 25 24
Model 3700 12 11
EtherNet/IP Module
8 Micro Motion EtherNet/IP Module
Installation
13. Connect the EtherNet/IP Module to the Ethernet network.
14. Wait for the auto-configuration process to complete.
IMPORTANT
For initial startup, you must use the auto-configuration process to ensure that device memory is
completely set up.
15. Add the EtherNet/IP Module to the Ethernet network control system. The EDS file is
available on the Resource CD, the EtherNet/IP Module (download from Administration
page), and the MicroMotion web site.
For more information on transmitter installation and wiring, see your transmitter installation
manual. For information on configuring the RS-485 terminals and making an RS-485
connection, see your transmitter configuration manual.
1
3
5
2
4
6
EtherNet connector
1) TD+
2) TD–
3) RD+
4) Termination
5) Termination
Installation
User Manual 9
2.3 Micro Motion Ethernet Config Tool installation
(optional)
If you do not plan to use the Micro Motion Ethernet Config Tool, you do not need to install it.
The Micro Motion Ethernet Config Tool is used for the following tasks:
Configuration of some network settings. Depending on your network, you may be able
to use switches for all required settings.
(Petroleum measurement or concentration measurement application only)
Downloading the alternate web pages and configuration files into the EtherNet/IP
Module.
IMPORTANT
The configuration files and web pages are tightly coupled. Download files provided by Micro
Motion only if you plan to use the Micro Motion web pages, Do not change any settings or
transactions in the configuration file.
2.3.1 System requirements
Pentium 133 MHz or higher
10 MB of free space
8 MB RAM
Windows NT v4.0 or higher, Windows 2000, or Windows XP
Internet Explorer v4.01 SP1 or higher
2.3.2 Installation steps
1. Install the software program. Locate and run the EtherNet/IP Module setup program on
the EtherNet/IP Module Resource CD and follow the on-screen instructions.
10 Micro Motion EtherNet/IP Module
Installation
2. Connect the configuration cable from your PC to the EtherNet/IP Module.
Note
For information on the Micro Motion Ethernet Config Tool user interface, see the Anybus
Communicator manual.
2.4 Final steps
1. From your browser, login to the EtherNet/IP Module as user admin.
2. Use the Device Configuration page to configure the EtherNet/IP Module.
3. Set up I/O at your Ethernet host.
- If you are not using RSLogix, use your standard method. For information on the
I/O assemblies, see Section B.3.
- If you are using RSLogix, select ETHERNET-MODULE - Generic Ethernet Module
and enter the required information. See the following figures.
Note
If Comm Format is anything other than INT, the data sizes will be different from the sizes shown.
1
9
5
6
1
2
4
1
PC connector
1) Ground
2) Ground
3) RS-232 Rx
4) RS-232 Tx
Installation
User Manual 11
Figure 2-1 I/O setup for the EtherNet/IP Module with standard configuration
Figure 2-2 I/O setup for the EtherNet/IP Module with concentration measurement
12 Micro Motion EtherNet/IP Module
Installation
Figure 2-3 I/O setup for the EtherNet/IP Module with petroleum measurement
Basic Network Configuration
User Manual 13
3 Basic Network Configuration
3.1 TCP/IP settings
To participate on the Ethernet network, the EtherNet/IP Module needs a valid TCP/IP
configuration.
The EtherNet/IP Module can retrieve the TCP/IP settings from a DHCP or BootP server. If no such
server is found, the EtherNet/IP Module uses the settings from the system file \ethcfg.cfg. If this
file is not found, or the settings are invalid, the EtherNet/IP Module will halt and report an error
on the status LED. However, the network configuration may still be accessed via the Ethenet
Config Tool.
You can define the TCP/IP settings for the EtherNet/IP Module in four ways:
Micro Motion Network Configuration web page (recommended)
Configuration switches on the device
Ethernet Config Tool
System file \ethcfg.cfg on the device
Micro Motion web page
The Network Configuration page, in the Micro Motion web pages, allows you to set the IP
address, gateway address, and subnet address. If you connect to the EtherNet/IP Module using
a crossover cable and the default IP address, you can set all three parameters. The changes will
take effect at the next connection.
Configuration switches
If the configuration switches on the EtherNet/IP module are set to any non-zero value, the
device is locked to the following network settings:
14 Micro Motion EtherNet/IP Module
Basic Network Configuration
To set the IP address, see the following table.
Ethernet Config Tool
See the Anybus Communicator manual for instructions.
IMPORTANT
If you change the network settings using the Ethernet Config Tool, you will not be able to use
the Micro Motion web pages to change network settings in the future. All future changes to
network settings must beperformed using the Ethernet Config Tool.
ethcfg.cfg file
To set the network settings using the \ethcfg.cfg file:
1. Set all configuration switches on the device to OFF.
2. Make a connection to the device from the Ethernet Config Tool and disable TCP/IP
Settings (Fieldbus parameter section). Alternatively, you can access the TCP/IP
parameters using the TCP/IP Interface Object.
Table 3-1 Network settings, locked
Parameter Value
IP address 192.168.0.x
where x is determined by the switches
Gateway 192.168.0.255
Subnet 255.255.255.0
DHCP OFF
Table 3-2 Network settings using switches
Switch
IP address
1 2 3 4 5 6 7 8
OFF OFF OFF OFF OFF OFF OFF ON 192.168.0.1
OFF OFF OFF OFF OFF OFF ON OFF 192.168.0.2
OFF OFF OFF OFF OFF OFF ON ON 192.168.0.3
... ... ... ... ... ... ... ... ...
ON ON ON ON ON ON ON OFF 192.168.0.254
ON ON ON ON ON ON ON ON Invalid
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78