Air-handling Units MANDÍK – INSTALLATION, COMMISSIONING, MAINTENANCE
IZU 1.7 02/2020 MANDÍK a. s., www.mandik.com 13
5| ASSEMBLY AND INSTALLATION
5.1 GENERAL
Installation of the units may only be performed by
an authorized person. The person performing the
assembly must meet technical and legal regula-
tions of the country. E.g. EN 45004, Act 174/68 Coll.
Connections and grounding of the electrical equip-
ment of the electric motor and any electrical wiring
must comply especially with EN 33 2190,
EN 33 2000-4-41, EN 33 2000-5-51,
EN 33 2000-5-54, applicable regulations,
the actual environment with regard to safe
operation.
The unit and its accessories must be commissioned
by an authorized and trained specialist technician
only who is familiar with the equipment and the
hazards associated with it
Before installing the unit, it is necessary to check
construction readiness, power supply system pa-
rameters, the temperature and pressure of cooling/
heating media, completeness and condition of the
unit’s components
defects must be removed prior installation
The unit and its accessories must only be connect-
ed to the mains voltage of 230 V / 400 V, 50 Hz
Access to the switchboard, to which the assemblies
are connected, must be provided. Power compo-
nents in the switchboard (breakers, contactors,
switches, etc.) must be marked clearly with the
device number under the HVAC project!
The presence of the representatives of the installer
and user at the operators’ training is recommended
The unit can not perform any functions of the building, such as a static load of the building and its
related components to the unit operation, place of installation for bridges and electric distribution,
switchboards, etc., apart from exceptions consulted with Mandík, a. s. Failure to do so will void the
warranty provided by Mandík, a. s.
It is recommended to use protective gloves when
installing and handling with the unit
When handling and lifting, the chambers of the
unit must be transported using forklifts and
conveyor belts only and it is necessary to follow
the relevant safety regulations. The unit will not be
transported over people! See Section 4. Handling,
Transport and Storage
Before installation, it is necessary to remove all
supports and reinforcements delivered with the
unit for its transportation
The gas heater burner must be adjusted after
mounting it on the chamber
The overall transport pressure of the ventilator is designed to design external pressure losses – in
front of and behind the fan, see the unit’s technical specications. Accordingly, it is necessary to
observe the installation of the air-handling ducts – without any additional local pressure losses
that may result, after adjusting, higher operating point of the fan and thus power consumption of
the electric motors.