Using EcoSystem 1 Ballasts and Drivers in HomeWorks QS Systems
Application Note #697
Revision F
November 2021
1 www.lutron.com/support
Overview
Lighting fixtures that utilize Lutron EcoSystem digitally addressable fluorescent dimming ballasts and LED drivers can
be controlled in a HomeWorks QS system by using either DIN Rail Power Modules with EcoSystem (LQSE-2ECO-D)
or GRAFIKEye QS with EcoSystem (QSGRx-yE). Power Modules with EcoSystem are capable of controlling up to
128EcoSystem drivers / ballasts (64maximum per EcoSystem link). GRAFIK Eye QS with EcoSystem units are capable of
controlling up to 64 EcoSystem drivers / ballasts. Zones can be grouped together into zones either in the HomeWorksQS
software (for DIN rail power modules) or locally at the main unit (for GRAFIK Eye QS units). The DIN rail power modules
support up to 64 zones per EcoSystem link and the GRAFIK Eye QS units support up to 16 zones. EcoSystem
drivers / ballasts communicate over a 2-wire, non-polarized, topology-free, digital communication bus.
The purpose of this document is to explain how to design, program, activate, and troubleshoot a HomeWorks QS system
that utilizes EcoSystem drivers / ballasts. This document has two main sections: one focused on the Power Module with
EcoSystem solution and the other focused on the GRAFIK Eye QS with EcoSystem solution. Refer to the appropriate section
based on the control hardware being used in the application.
Note: Only HomeWorks QS software version 6.0.0 or later supports the use of Power Modules with EcoSystem and
GRAFIK Eye QS with EcoSystem.
Note: For optimal performance, Lutron recommends using HomeWorks QS software version 9.0.0 or later to program
EcoSystem devices. For more information, refer to Section 1.4.
Table of Contents
1.0 Power Module with EcoSystem ................................................................................................................. 2
1.1 Installation and Wiring ............................................................................................................................... 2
1.1.1 Wiring Tips ..................................................................................................................................... 2
1.1.2 Additional Notes ............................................................................................................................. 3
1.2 Adding and Configuring the Power Module in the Design Tab ...................................................................... 3
1.2.1 Creating EcoSystem Loads .............................................................................................................. 3
1.2.2 Adding Power Modules and Assigning Loads to EcoSystem Links ..................................................... 5
1.3 Activating the Power Modules and EcoSystem Drivers/Ballasts .................................................................... 6
1.3.1 Activate Power Modules .................................................................................................................. 6
1.3.2 Activate EcoSystem Drivers / Ballasts ............................................................................................... 6
1.4 Programming EcoSystem Zones in the HomeWorks QS Software............................................................... 10
1.4.1 Area Scene Programming Recommendations ................................................................................. 11
1.5 Replacing EcoSystem Modules ................................................................................................................ 12
2.0 GRAFIK Eye QS with EcoSystem ............................................................................................................ 13
2.1 Installation and Wiring ............................................................................................................................. 13
2.1.1 Wiring Tips ................................................................................................................................... 13
2.1.2 Additional Notes ........................................................................................................................... 13
2.2 Adding and Configuring the GRAFIK Eye QS with EcoSystem in the Design Tab ......................................... 14
2.3 Program and Activation Tabs ................................................................................................................... 15
Appendix A – Dimming Range of EcoSystem LED Drivers ......................................................................... 16
Lutron Contact Numbers ................................................................................................................................ 17
1 EcoSystem drivers are no longer available to order as of September 1, 2021.