Technical data
4.2 Technical data
UltraGas
®
(70,90)
Type (70) (90)
• Nominal output 80/60°C with natural gas
1
kW 12,2 - 63,3 14,4 - 83,3
• Nominal output 40/30°C with natural gas
1
kW 13,6 - 69,9 16,1 - 91,5
• Nominal output 80/60°C with liquid gas
3
kW 15,4 - 63,3 17,4 - 83,3
• Nominal output 40/30°C with liquid gas
3
kW 17,1 - 69,9 19,3 - 91,5
• Nominal load with natural gas
1
kW 12,5 - 65,5 14,7 - 86,0
• Nominal load with liquid gas
3
kW 16,0 - 65,5 18,0 - 86,0
• Working pressure heating max./min. bar 4,0 / 1,0 4,0 / 1,0
• Working temperature max.. °C 85 85
• Boiler water capacity l 157 149
• Min. water circulation l/h 0 0
• Boiler Weight (without water) kg 249 268
• Boiler efficiency at partial load 30% (according to EN 303)
(related to net / gross calorific value)
% 107,1 / 96,5 107,2 / 96,6
• Standard efficiency (according to DIN 4702 part 8) 40/30°C % 109,6 / 98,7 109,6 / 98,7
(net calorific value / gross calorific value) 75/60°C % 107,1 / 96,5 107,1 / 96,5
• Heat loss rate at 70°C Watt 290 290
• Standard emission rate Nitrogen oxides mg/kWh 32 39
Carbon monoxide mg/kWh 3 3
• Co
n
tent of CO
2
in the exhaust gas max./min. power % 9,0 / 8,8 9,0 / 8,8
• Dimensions See table of dimensions
• Connections Flow /Return Zoll R 1 ½" R 1 ½"
Gas Zoll R ¾" R ¾"
Flue gas / combustion
air Ø
mm C100/150 C100/150
• Gas flow pressure min./ max.
Natural gas E/LL mbar 18-50 18-50
Liquid gas mbar 37-50 37-50
• Gas connection value at 0°C / 1013 mbar:
Natural gas E - (Wo = 15,0 kWh/m
3
) Hu = 9,97 kWh/m
3
m
3
/h 6,6 8,6
Natural gas LL- (Wo = 12,4 kWh/m
3
) Hu = 8,57 kWh/m
3
m
3
/h 7,6 10,0
Propangas (Hu = 25,9 kWh/m
3
) m
3
/h 2,5 3,3
• Operation voltage V/Hz 230/50 230/50
• Control voltage V/Hz 24/50 24/50
• Min./Max. electrical power consumption Watt 27 / 93 28 / 138
• Standby Watt 12 12
• IP rating (integral protection) IP 20 20
• Acoustic capacity
- Heating noise (EN 15036 part 1) (room air-dependent) dB(A) 64 67
- Exhaust noise is radiated from the mouth
(DIN 45635 part 47) (room air-dependent/room air-independent)
dB(A) 55 59
• Acoustic pressure level (depending on installation)
2
dB(A) 57 59
• Condensate quantity (Natural gas ) at 40/30°C l/h 6,2 8,1
• pH value of the condensate ca. 4,2 ca. 4,2
• Value for flue calculation
Temperature class T120 T120
Flue gas mass flow kg/h 109,0 143,0
Flue gas temperature at nominal output and operation 80/60°C °C 63 65
Flue gas temperature at nominal output and operation 40/30°C °C 43 43
Mass flow combustion air Nm
3
/h 81 106
Feed pressure for combustion air/ flue gas system Pa 130 130
Maximal Draft / negative pressure flue gas outlet Pa - 50 - 50
1
Data reladet to H
u
. The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWH/m
3
operation at a
Wobbe oefficient of 12,0 up to 15,7 kWh/m
3
is possible without new settings.
2
See also notes at „Engineering“.
3
Data reladet to H