AH-02412 FAMILY
C
2005-04E1
Operating Instructions
12
AH-02412 FAMILY
B.12 buttons including 10 numeric,1 select/clear and 1 acknowledge.
C.Use S/C for displayed heading selection and information clear, the
" " and " " buttons scroll of the manual headings.
D.Original screen: first line shows Alarm= 000 Fault= 000 (note: 0
means normal condition); second line shows current date & time
(yr/mo/day/hr/min/sec).
E.For inconsecutive alarm signal, screen will show 000 but fire
indicator will remain ON. For inconsecutive fault signal, screen
will show 000 and zone fault indicator will OFF.
F.Features as follow:
1.Time setting: After correct time is set up, press "ACK" for
completion.
2.Zone status display:
a.Display current zone status, at normal condition it will show
'No Signal'; press "ACK" and back to last screen.
b.Display any alarm, disconnection or short; the first line shows
event #, zone # and event status. The second line shows the
date and time of the event. Press "ACK" and back to last
screen.
3.Memory data display:
a.255 events memory and display with capital M.
b.Record all kind of status; the first line shows event #, zone #
and event status. The second line shows the date and time of
the event. Press "ACK" and back to last screen.
4.Memory data delete: By input access code, memory data will
clear automatically and then back to last screen.
5.Access code setting: First enter original code (0000) then enter
the access code. To return the original code, press '5' and short
the two pins on the right of PCB 528D inside the panel.
6.System information: It shows model #, zone # and version; press
"ACK" will back to original screen.
>
>
11. Extinguishing Facility (AH-02412E only)
The extinguishing system will be activated after fire alarm has issued
for 0 ~ 60 seconds with adjustable timer (please refer to the logic
switch located on main board, single digit on the right and decimal
digit on the left) and gas discharge will automatically turned off after
10 seconds or by pushing the "Nac" button. While activated, the
LED (Active) on the panel will be ON until the system's supply power
was turned OFF and ON again. When user intends to stop the
extinguishing process just press the "Nac" button. The extinguishing
facility is only activated when both zone in same area have issued
fire alarm.