The Fireplace Jetmaster 850 Installation Instructions Manual

Category
Fireplaces
Type
Installation Instructions Manual
JETMASTER GAS CONVECTOR INSTALLATION INSTRUCTIONS
A TYPICAL IN-BUILT INTO TIMBER FRAMING
9/2013
4.G.4A
Front Back
Convector
Box
Gather
Y
Gather
C
E
G
D
A
A1
A2
B
F
ALL INSTRUCTIONS TO COMPLY WITH NZS5261:2003
Due to continued product improvement, The Fireplace Ltd reserves the right to change product specications without prior notication
Table 1
Fig. 2
JETMASTER IGC BOX DIMENSIONS
Drawings Not To Scale
Dimensions in mm
Fig. 1
IMPORTANT: Read all instructions carefully before starting installation. Failure to follow these
instructions may result in a fire hazard and will void the warranty.
This appliance must be serviced every 12 months by a registered gas tter.
Model A A1 A2 B C D E F G Y
700 700 800 750 341 650 290 200/250 630 265 235
850 850 950 900 341 650 290 250/300 630 265 235
1050 1050 1150 1100 341 570 290 250/300 550 265 235
1200 1200 1300 1250 341 570 290 250/300 550 265 235
1500 1500 1600 1550 341 570 290 250/300 550 265 235
Head Office & Showroom
12 Tawari St, Mt Eden, Auckland
0800 843 347 | 0800 The Fire
www.thefireplace.co.nz
4.G.4B
B
AC
All front nogs
to be installed
on edge
Air
Vents
Note: these dimensions are the absolute minimum sizes -
widths (A & C) maybe increased if desired. It is important to
ensure the Jetmaster firebox is seated on top of the finished
floor protector level.
Fig. 3
*Allow temporary lintel height until firebox & flue is installed
Table 4
TRIM OUT DIMENSIONS
Dimensions in mm
MODEL A B C Temporary
Lintel*
700 850 730 450 1200
850 1000 730 450 1200
1050 1200 650 450 1200
1200 1350 650 450 1200
1500 1650 650 450 1200
GAS TRAY OPERATING OPTIONS
* M.V. - Millivolt: no electricity required
SFB / DLX Manual *M.V. Wall Switch
700
850
1050  
1200  
1500  
Table 2
MODEL Gas Input MJ/Hr
NG LPG
700 SFB 45 38
850 SFB 50 43
1050 SFB 65 65
1200 SFB 75 70
1500 SFB 85 80
GAS INPUT
Table 3
MARGIN SET
4.G.4C
CAVITY / FRAMING PREPARATION
200650mm
Non combustible material
(Promina, Eterpan LD, Supalux)
fix to timber frame
fix to timber frame
10mm recess behind fascia
50mm 50mm
1. Refer to the minimum framing dimensions as per Table 4 / Fig 3. Allow a temporary 1200mm lintel
height, until the convector box and flue is installed. Install front nogs on edge to increase chimney
chase dimension.
2. For timber frame, use 6mm Hardiflex board to line the FLOOR, REAR AND SIDES of framed cavity of
framed cavity to be taken to a minimum height of 1200mm from the firebox base.
3. Air Vents to be minimum cross sectional area of 5000sq.mm in total. Use 100 x 50mm air vent or similar
each side of the firebox. For wooden floors locate in floor, for concrete floors locate in walls. All air vents
to be bird and rodent proof.
4. If intending to recess the firebox, the maximim recess value is 100mm. Refer to Fig. 7.
5. If a On/Off Wall Switch is being installed, a power cable (3m supplied) must be run from the on/off
switch to the firebox. Gas Models 1050, 1200 & 1500 are operated by a Millivolt power source. DO NOT
connect a 240V supply to these gas burners (see table 2 for full details).
If a wall switch is being installed for the 700 and/or 850 models, these are operated by 240V AC and
require an electrician to wire, connect and test.
Under no circumstance is the width of the vertical margin legs to be less than 50mm and the height
of the margin lintel to be less than 200mm (see Fig 4).
Where an internal wall board finish is required around the fire, ensure allowance is made to place non-
combustible internal wall lining (eg: Promina, Supalux, Eterpan) shown shaded. Directly touching the firebox
with any board or plaster finish will cause cracking from heat expansion. Allow 2mm minimum space away
from the firebox.
Fig. 4
CROSS SECTION
FIREBOX INSTALLATION 4.G.4D
Fig. 5
100
100
Y
Min 2 x 80mm dia. or
equal square or rectangle
shape area wall or floor
mounted air vents
(min 5000sqmm)
Rock-wool
insulation
Min 50mm from
combustible
material
6mm Hardiflex
1200mm from base of box
6mm Hardiflex
Secure firebox with dynabolts
for earthquake restraints
min. 300mm
Floor Protector
(level with firebox)
Allow 1200mm temporary lintel height
until firebox & flue system is installed
Non combustible material
(Promina, Eterpan LD,
Supalux)
150 x 50mm timber lintel
Gib
min 25mm from combustible material
1. Fit and seal gather, using fire cement (exhaust cement) and bolts (supplied), to the convector box. Note:
Pop rivet back of gather to convector box if required.
2. Locate and position convector box and gather in cavity.
3. Earthquake restraints holes are located under the cover where the receiver and battery pack are situated.
4. Attach rock wool to the sides & back of the convector box and gather. DO NOT BLOCK OFF the air entry
between the inner flue pipe and flue pipe casing or the air circulation between the vent holes in the cavity.
5. Drill a hole or use the knock outs in the convector box for the Gas Line and if a wall switch is being
installed for the cable.
6. A minimum 300mm non combustible floor protector (hearth) is recommended in front of the convector
box. Ensure that the material used is level with the convector box base.
PLAN 4.G.4E
Fig. 6
RECESS PLAN
Maximum Firebox Recess Value = 100mm
Fig. 7
200
50
100
min 2 x 80mm diam. equal square or rectangle shape area
wall or floor mounted air vents
6mm Hardiflex
Rock-wool
insulation
Gib
Floor Protector
min 50mm from combust. material
Allow gas line
into firebox
Non combustible material
(Promina, Eterpan LD,
Supalux)
maximum 100mm recessed
allow 2mm minimum
space away from firebox Hebel Block
200
300
200
min 2 x 80mm diam. equal square or rectangle shape area
wall or floor mounted air vents
6mm Hardiflex
Rock-wool
insulation
Gib
Floor Protector
min 50mm from combust. material
6mm Hardiflex
Allow gas line
into firebox
‘C’ + 100mm
Recess
(see table 4)
4.G.4F
FLUE INSTALLATION
Air Ventilation Through Chimney Chase Air Ventilation Through Top Flashing
Drawings Not To Scale
Air Vent
min 2 x 80mm diam. or equal square or rectangle shaped area
Non combustible material
Hebel Block or
12 mm Promina board
or similar under the flashing
Casing cover
is necessary
120 mm
minimum
120 mm
minimum
Spigot flashing to suit
flue pipe casing
Note: All external air vents & ceiling penetrations must be bird & rodent proofed with permanently fixed screens
Drip
Line
Drip
Line
Fig. 8
Minimum 25mm gap between
flue pipe casing
& combustible surface
CHIMNEY CHASE AIR VENTILATION
Fig. 9
Pr ojection (mm)
25 25
25
1. Install first length of flue pipe crimped end down, inside gather collar. Rivet flue pipe in 3 places around
gather collar. Place bottom flue spider bracket around gather flue pipe collar, secure in position by
tightening up coach bolt/screw (supplied).
2. Install second length of the flue pipe crimped end down and fix by riveting in at least 3 places around the
flue pipe joint.
3. Install first length of the flue pipe casing by positioning on installed bottom flue spider bracket crimped
end up.
4. Position flue spacer at the flue pipe joint.
5. Repeat steps 1 - 4. As per manufacturers recommendation, the flue pipe shall extend not less than 3.6m
above the fire box.
6. The flue is required to be at least 500mm above the nearest point on any part of the buildings roof and
neighbouring buildings if within a 3m radius. Refer to NZS 5261:2003; 2.6.13 for further information.
7. The last length of flue pipe needs to extend past the flue pipe casing by at least 150mm or flush with the
top of the casing cover spigot when fitted - sizing/measuring and cutting down should be carried out prior
to the flue pipe casing being fitted over the flue pipe.
8. Before fitting casing cover, place the spider in opposition with the spider post facing down between the
flue pipe and flue pipe casing. Secure spider in position. Place the casing cover over the flue pipe, press
down firmly onto the spider. Check airway around the casing cover is clear, then secure in position using
three stainless steel rivets.
9. Fit cowl to top of flue - DO NOT RIVET IN POSITION. In high wind areas, it is recommended that the cowl
be secured in position with a stainless steel self tapping screw, this will enable the cowl to be removed for
cleaning. Discuss Bird Proofing needs with your installer. N.B. in extreme wind areas it may be necessary
to consult The Fireplace Ltd or your local agent for further technical assistance Ph: 0800 843 347.
10. If flue is concealed in a chase, allow for air vents (2 x 80mm diam. or equivalent) at the highest possible
point on the chimney chase or alternatively, allow a min 25mm air space between the casing cover spigot
and the outer casing. Refer to Figure 8 and 9.
4.G.4G
Projection (mm)
flue pipe
flue pipe casing
25
25
Typical Cowl
Casing Cover
Air
Top Spider
Approved Flashing
Air Vents
min. 25mm gap between flue
pipe casing & combustible
surface
min. 25mm dia. or equal
square or rectangle
Note: All external air vents &
ceiling penetrations must be bird
& rodent proofed with permanently
fixed screens
Drawing Not To Scale
Fig. 10
FLUE PENETRATION
EXTERNAL REQUIREMENTS
Refer to NZS5261:2003
or less
Any nearby structure
1000
1000
500
500
min. 200 between
flue terminals
increase as necessary until
nothing within 500mm of flue
terminal
end of the flue shall
be at least 500mm
from the nearest part
of the roof
MINIMUM HEIGHT OF FLUE SYSTEM EXIT
Fig. 11
As per AS/NZS 5261:2003 2.6.1.3 Flue Terminals
If you are using a decorative surround constructed of combustible material, it must be located within the
shaded area defined in Fig. 13.
Fig. 13
Drawing Not To Scale
4.G.4H
CLEARANCE TO COMBUSTIBLE MANTELS
Mantel / Surround projection from wall
Top Clearance (mm)
Height from top of firebox to underside of mantel/surround
Projection (mm)
Combustible
Materials
Non-Combustible
Materials
0
25
45
50
90
100 150
170
200 250 300
350
100
200
300
400
500
230
320
380
425
460
483
X
Y
X
Y
X
Y
Flue Pipe
Min. 25mm Clearance
Min. 25mm Clearance
Flue Pipe Casing
Fig. 12
Table 5
Note: A minimum 25mm clearance from flue pipe casing to combustible material must be maintained.
Dimensions in mm
CHIMNEY CHASE MINIMUM TRIM OUT
MODEL FLUE SYSTEM MINIMUM TRIM OUT DIMENSION
X (min) Y (min)
700 200/250 300 300
850 250/300 350 350
1050 250/300 350 350
1200 250/300 350 350
1500 250/300 350 350
Head Office & Showroom
12 Tawari St, Mt Eden, Auckland
0800 843 347 | 0800 The Fire
www.thefireplace.co.nz
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

The Fireplace Jetmaster 850 Installation Instructions Manual

Category
Fireplaces
Type
Installation Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI