DANLERS DSSGD MK 10VDC, DSSGD CB 10VDC, DSSGD EU 10VDC Installation guide

  • Hello! I'm a chat assistant and I've read the DANLERS installation notes for DSSGD MK 10VDC, DSSGD CB 10VDC, and DSSGD EU 10VDC ballast dimmers. This document details the installation process, fault finding, and key features of the dimmers, such as their soft start function and compatibility with various grid systems. I'm ready to answer your questions about these devices.
  • What should I do if the lamp dims up and down constantly?
    What can I do if lamps do not dim?
    Why lamps do not switch off?
Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected] Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Also available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1andBSEN55015:1993
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.6ampsovercurrent,1kVovervoltage.Pleaseensure
thatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
1 to 10V ballast Dimmers (grid modules)
DSSGD MK 10VDC DSSGD CB 10VDC DSSGD EU 10VDC
These1to10Vsoftstartballastdimmersaresuitableforttinginto
the MK Grid Plus, Crabtree grid and Eurodata plates.
Thesoftstartfeaturerampsuptheballastcontrolvoltagewhichcan
greatlyincreaselamplife,particularlyforlowvoltagelamps.
Ashortpresswillswitchtheballastoffviatheswitchedlineoutputor
energisetheswitchedlineoutputandrestoretheballastcontrolvoltage
softlytoitsprevioussetting.
Aholdingpresswilldimthecontrolvoltageupanddowninturn.
Theballastcanbeswitchedanddimmedfromseverallocationsby
usingmainsrated,momentary,normally-openpush-to-makeswitches.
RemoteswitchesareavailablefrombothMK(K4885)andCrabtree
(4489).
DANLERS1-10Vdimmerscanpowerupto6amps(1500W)of:
• Highfrequencyballastdimmeduorescentlamps
• Highfrequencyballast(driver)dimmedLEDlampsetc.
Theycancontroluptotwenty1-10Vballasts.
• Assumingeachballastdraws1mA(orless)throughthevoltagecontrollines.
The1to10Vballastdimmersneedthefollowingminimumdepthwallboxes:
• DSSGDMK10VDC 35mm
• DSSGDCB10VDC 40mm
• DSSGDEU10VDC 35mm
06/03/12 INS910 DSSGD10VDC
Loading limits
Wall box depth
Fault nding
Lamp dims up and down constantly:
• Ensuremomentaryremoteswitcheshavebeenused
• Buttonpressedtoohardandjammed.Releasebutton
• Slavewiringmorethan10mlong.Useshieldedortwistedwiring.
Lamps do not dim:
• Disconnectthe1-10Vdimmer,thevoltageacrosstheterminalsof
the1-10vballastshouldbeat10Vandthelampshouldbeonfull,if
nottheremaybeaproblemwiththe1-10Vballast
• Reconnectthe1-10Vlinesandchecktoseeifthevoltagecanbe
variedviathedimmer.
Lamps do not switch off:
• Thedimmercanonlydimthelampsdowntoabout10%viathe
1-10Vlines,thelampsareswitchedoffbythedimmerremoving
thepowertotheballast.TheballastmustbeconnectedtotheSL
outputofthedimmer,notdirectlytoapermanentlivesupply.
• Whenswitchingverysmall,nonresistiveloads,suchasLED
drivers,theloadmayneedtobeaugmentedwithaCAPLOAD
devicewiredbetweentheSwitchedLineandNeutralatthetting.
1.Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
Makesurethepowerisisolatedfromthecircuit.
2. The 1 to 10V ballast dimmer should be connected as:
L Live
N Neutral
SL SwitchedLineoutput(toballast)
R Mains-ratedmomentaryRemoteswitch(optional)
- - ofcontrolvoltage(toballast)
+ +ofcontrolvoltage(toballast)
3.Typicalwiringdiagramshownopposite.
4.Pleasenote:Failuretoconnecttheunitasshownmayresultindamage
to the product.
5.Pleasenote:IfusingRemotemomentaryswitch(es),eachconnecting
cable should be twin core of at least 1mm2 cross section and not
exceed 10 metres in length.
6.Oncethewiringhasbeencompletedandveried,switchonthesupply
and test the operation.
Typical wiring diagrams
1
ballast
10
1
ballast
10
1
ballast
10
control lines
L
230 VAC
Optional
mains rated,
normally open
push button (s)
L
N
N
SL
optional
other
load
* Total load of ballasts plus other load not more than 6 amps
R
1-10V
Dimmer
Installation procedure
/