DANLERS DSSGD CB 10VDC Installation guide

Type
Installation guide

This manual is also suitable for

Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected] Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Also available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1andBSEN55015:1993
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.6ampsovercurrent,1kVovervoltage.Pleaseensure
thatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
1 to 10V ballast Dimmers (grid modules)
DSSGD MK 10VDC DSSGD CB 10VDC DSSGD EU 10VDC
These1to10Vsoftstartballastdimmersaresuitableforttinginto
the MK Grid Plus, Crabtree grid and Eurodata plates.
Thesoftstartfeaturerampsuptheballastcontrolvoltagewhichcan
greatlyincreaselamplife,particularlyforlowvoltagelamps.
Ashortpresswillswitchtheballastoffviatheswitchedlineoutputor
energisetheswitchedlineoutputandrestoretheballastcontrolvoltage
softlytoitsprevioussetting.
Aholdingpresswilldimthecontrolvoltageupanddowninturn.
Theballastcanbeswitchedanddimmedfromseverallocationsby
usingmainsrated,momentary,normally-openpush-to-makeswitches.
RemoteswitchesareavailablefrombothMK(K4885)andCrabtree
(4489).
DANLERS1-10Vdimmerscanpowerupto6amps(1500W)of:
• Highfrequencyballastdimmeduorescentlamps
• Highfrequencyballast(driver)dimmedLEDlampsetc.
Theycancontroluptotwenty1-10Vballasts.
• Assumingeachballastdraws1mA(orless)throughthevoltagecontrollines.
The1to10Vballastdimmersneedthefollowingminimumdepthwallboxes:
• DSSGDMK10VDC 35mm
• DSSGDCB10VDC 40mm
• DSSGDEU10VDC 35mm
06/03/12 INS910 DSSGD10VDC
Loading limits
Wall box depth
Fault nding
Lamp dims up and down constantly:
• Ensuremomentaryremoteswitcheshavebeenused
• Buttonpressedtoohardandjammed.Releasebutton
• Slavewiringmorethan10mlong.Useshieldedortwistedwiring.
Lamps do not dim:
• Disconnectthe1-10Vdimmer,thevoltageacrosstheterminalsof
the1-10vballastshouldbeat10Vandthelampshouldbeonfull,if
nottheremaybeaproblemwiththe1-10Vballast
• Reconnectthe1-10Vlinesandchecktoseeifthevoltagecanbe
variedviathedimmer.
Lamps do not switch off:
• Thedimmercanonlydimthelampsdowntoabout10%viathe
1-10Vlines,thelampsareswitchedoffbythedimmerremoving
thepowertotheballast.TheballastmustbeconnectedtotheSL
outputofthedimmer,notdirectlytoapermanentlivesupply.
• Whenswitchingverysmall,nonresistiveloads,suchasLED
drivers,theloadmayneedtobeaugmentedwithaCAPLOAD
devicewiredbetweentheSwitchedLineandNeutralatthetting.
1.Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
Makesurethepowerisisolatedfromthecircuit.
2. The 1 to 10V ballast dimmer should be connected as:
L Live
N Neutral
SL SwitchedLineoutput(toballast)
R Mains-ratedmomentaryRemoteswitch(optional)
- - ofcontrolvoltage(toballast)
+ +ofcontrolvoltage(toballast)
3.Typicalwiringdiagramshownopposite.
4.Pleasenote:Failuretoconnecttheunitasshownmayresultindamage
to the product.
5.Pleasenote:IfusingRemotemomentaryswitch(es),eachconnecting
cable should be twin core of at least 1mm2 cross section and not
exceed 10 metres in length.
6.Oncethewiringhasbeencompletedandveried,switchonthesupply
and test the operation.
Typical wiring diagrams
1
ballast
10
1
ballast
10
1
ballast
10
control lines
L
230 VAC
Optional
mains rated,
normally open
push button (s)
L
N
N
SL
optional
other
load
* Total load of ballasts plus other load not more than 6 amps
R
1-10V
Dimmer
Installation procedure
  • Page 1 1