System Sensor RR1 User manual

Category
Smoke detectors
Type
User manual
RR1 Polarity Reversal
Relay Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
M500-12-00 1 I56-1168-02
General Description
The RR1 polarity reversing relay module is intended for
use with 2-wire and 4-wire detectors with built-in
sounder, such as System Sensor 2100AT, 2112/24ATR
and 2112/24AITR, and other compatible models. It is de-
signed to allow all the detectors in the same loop to
sound when one of the detectors goes into alarm.
NOTICE: This manual shall be left with the owner/user of
this equipment.
NOTE: If your panel configuration does not match any of
the provided wiring diagrams, please contact System Sen-
sor technical services at 1-800-SENSOR2 for assistance.
Installation
Choose a mounting location in the control panel within
reach of the provided wire leads. Use a water/isopropyl al-
cohol mixture (50/50) to clean the mounting surface. Allow
surface to dry and remove paper backing from the Velcro
and catch. Stick the Velcro in the panel and the catch on
the back of the module, then mount the module inside the
control panel. Route terminals to the appropriate terminals
as noted below.
Wiring
1. Connect the relay module trigger wires to the fire alarm
output terminals.
IMPORTANT: Polarity must be observed!
A. Continuous alarm/bell output: (Figures 1 and 2)
Connect red wire to positive and black wire to negative.
B. Alarm relay, normally open contact output: (Figures 3
and 4)
1) Connect one end of the alarm relay contact output
and the black wire to positive and negative of
power, respectively. Auxiliary power supply is used
as a power source for 2-wire detectors and power
to the detectors is used as a power source for 4-
Specifications
Operating Voltage Range: 9.5 to 32 VDC
Maximum Operating Current: 29mA
Relay Contacts: 2A at 30 VDC, 0.5A at 120 VAC
Operating Temperature Range: 0˚ to 55˚ C (32° to 131° F)
Operating Humidity Range: 5% to 95%
Dimensions: 1
1
/2 x 1
3
/4
Wire connections: 18 AWG stranded, tinned, 16 long
wire detectors.
2) Connect the red wire to other end of alarm relay
contact output.
2. Connect the outgoing wires of the relay module to the
smoke detector power-in terminals (brown to positive,
white to negative).
3. Connect the blue and purple wires of the RR1 to any of
the power sources as specified in the applicable wiring
diagram (see Figures 1-4).
4. 2-wire models:
Connect the yellow and orange wires to the positive and
negative of the initiating loop, respectively.
4-wire models:
Connect the yellow and orange wires to the positive and
negative of power to detectors, respectively.
5. Connect the smoke detector initiating circuit to the
alarm loop.
WARNING
When calculating total current draw of the control panel,
remember to add current consumption (29mA) for the
power reversal relay module (RR1).
Testing
Before testing, notify the proper authorities that the system
is undergoing maintenance and will temporarily be out of
service.
Test in accordance with NFPA 72 Chapter 7 test methods,
inspections, and testing frequency.
1. To test the RR1 module, confirm that the smoke detec-
tors do not sound without an alarm.
2. Initiate an alarm with smoke or approved test method
on any detector connected to the control panel via the
RR1 module. In alarm, all the detectors that are installed
in the corresponding loop shall sound.
3. Reset the detectors by removing power to the loop.
NOTE: If using a power supervision relay, be
aware of the following: In an alarm condition, a
wiring-fault trouble state may also register at
the panel when the RR1 is used.
The RR1 cannot be used with a coded (or
pulsed) power supply. For proper RR1 opera-
tion, distinct wiring methods are required. See
page 4 for specifics.
Figure 2. RR1 module with 4-wire smoke detectors:
Figure 1. RR1 module with 2-wire smoke detectors:
OPTIONAL CLASS A WIRING
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
POWER
TO
DETECTORS
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
POWER REVERSAL
RELAY MODULE (RR1)
CONTINUOUS
BELL/
ALARM
OUTPUT
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
+
+
T1RED
BLK
BLUE
ORG
PURPLE
YELLOW
BROWN
WHITE
T2
T8
T6
T3
T5
T4
T7
P
W
R
A
U
X
P
W
R
A
U
X
+
+
A
A
NC
C
NO
+
INITIATING
LOOP
+
A
A
NC
C
NO
}
To auxiliary power/detector power/IAC/Bell
output or any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
EOL
+
+
A
+
RA400Z
A
-
+
+
+
A
+
A
-
RA400Z
+
P
W
R
P
W
R
CONTINUOUS
BELL/
ALARM
OUTPUT
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
+
T1RED
BLK
BLUE
ORG
PURPLE
YELLOW
BROWN
WHITE
T2
T8
T6
T3
T5
T4
T7
+
Not
Used
Not
Used
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
POWER REVERSAL
RELAY MODULE (RR1)
To auxiliary power/IAC/Bell output or
any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
A78-2336-10
A78-2336-09
M500-12-00 2 I56-1168-02
NOTE: If your panel configuration does not match any of the following wiring diagrams, please contact System Sensor
technical services at 1-800-SENSOR2 for assistance
NOTE: If optional Class A wiring is used, second power reversal relay module (RR1) must be added to enable concurrent
loop polarity reversal.
Figure 4. RR1 module with alarm relay and 4-wire smoke detectors:
Figure 3. RR1 module with alarm relay and 2-wire smoke detectors:
A78-2336-12
A78-2336-11
EOL
+
+
A
+
RA400Z
A
-
+
+
+
A
+
A
-
RA400Z
+
P
W
R
P
W
R
ALARM
RELAY
(N/O contact)
OUTPUT
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
T1RED
BLK
BLUE
ORG
PURPLE
YELLOW
BROWN
WHITE
T2
T8
T6
T3
T5
T4
T7
+
+
+
Not
Used
Not
Used
AUX.
POWER
SUPPLY
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
POWER REVERSAL
RELAY MODULE (RR1)
To auxiliary power/IAC/Bell output or
any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
OPTIONAL CLASS A WIRING
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
POWER
TO
DETECTORS
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
+
T1RED
BLK
BLUE
ORG
PURPLE
YELLOW
BROWN
WHITE
T2
T8
T6
T3
T5
T4
T7
P
W
R
A
U
X
P
W
R
A
U
X
+
+
A
A
NC
C
NO
+
INITIATING
LOOP
+
A
A
NC
C
NO
}
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
POWER REVERSAL
RELAY MODULE (RR1)
To auxiliary power/detector power/IAC/Bell
output or any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
ALARM
RELAY
(N/O contact)
OUTPUT
M500-12-00 3 I56-1168-02
NOTE: If optional Class A wiring is used, second power reversal relay module (RR1) must be added to enable concurrent
loop polarity reversal.
Three-Year Limited Warranty
System Sensor warrants its enclosed relay module to be free from defects
in materials and workmanship under normal use and service for a period
of three years from date of manufacture. System Sensor makes no other
express warranty for this relay module. No agent, representative, dealer, or
employee of the Company has the authority to increase or alter the obliga-
tions or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the
relay module which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing
with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
M500-12-00 4 I56-1168-02
© System Sensor 1998
Minimum Conditions Required for Proper Operation of the RR1 Upon Fire Alarm
For 2-Wire Model Smoke Detectors (Model 2100AT)
Auxiliary power supply for smoke detector sounders upon alarm and one of the following:
1. Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required
–or–
2. Auxiliary power supply for RR1 and auxiliary relay with normally open contact activated by fire alarm only
For 4-Wire Model Smoke Detectors (Models 2112/24AT, 2112/24ATR, 2112/24AITR)
1. Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required
–or–
2. Auxiliary relay with normally open contact activated by fire alarm only
NOTE: Outputs must be continuous (non-coded, non-pulsed.) The RR1 will not function properly in panels that provide
only single combined burglary and fire alarm output unless the minimum conditions noted above are present.