Notifier FCM-1 Installation guide

Category
Fire protection
Type
Installation guide
N500-46-00฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 4 ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀I56-1169-07
฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀©฀2001฀Notifier
WARNING
All฀relay฀switch฀contacts฀are฀shipped฀in฀the฀standby฀state฀(open)฀state,฀but฀may฀have฀transferred฀to฀the฀activated฀(closed)฀state฀during฀
shipping.฀To฀ensure฀that฀the฀switch฀contacts฀are฀in฀their฀correct฀state,฀modules฀must฀be฀made฀to฀communicate฀with฀the฀panel฀before฀
connecting฀circuits฀controlled฀by฀the฀module.
Relay฀Contact฀Ratings:
CURRENT฀RATING MAXIMUM฀VOLTAGE LOAD฀DESCRIPTION APPLICATION
3฀A
2฀A
.9฀A
.9฀A
.5฀A
1฀A
.5฀A
.7฀A
30฀VDC
30฀VDC
110฀VDC
125฀VAC
30฀VDC
30฀VDC
125฀VAC
75฀VAC
Resistive
Resistive
Resistive
Resistive
Inductive฀(L/R=5ms)
Inductive฀(L/R=2ms)
Inductive฀(PF=.35)
Inductive฀(PF=.35)
Non฀Coded
Coded
Non฀Coded
Non฀Coded
Coded
Coded
Non฀Coded
Non฀Coded
LABEL
J1฀UNDER฀LABEL
BACK฀OF
MODULE
N500-46-00฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 1 ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀I56-1169-07
FCM-1฀Supervised฀Control฀Module
INSTALLATION฀ AND฀ MAINTENANCE฀ INSTRUCTIONS
12฀Clintonville฀Rd
฀฀Northford,฀CT฀06472-1653
(203)฀484-7161
Before฀Installing
This฀ information฀ is฀ included฀ as฀ a฀ quick฀ reference฀ installation฀
guide.฀Refer฀to฀the฀control฀panel฀installation฀manual฀for฀detailed฀
system฀information.฀If฀the฀modules฀will฀be฀installed฀in฀an฀existing฀
operational฀system,฀inform฀the฀operator฀and฀local฀authority฀that฀
the฀system฀will฀be฀temporarily฀out฀of฀service.฀Disconnect฀power฀
to฀the฀control฀panel฀before฀installing฀the฀modules.
NOTICE:This฀manual฀should฀be฀left฀with฀the฀owner/user฀of฀this฀
equipment.
General฀Description
FCM-1฀SupervisedControl฀Modules฀are฀intended฀for฀use฀in฀intel-
ligent,฀ two-wire฀ systems,฀ where฀ the฀ individual฀ address฀ of฀ each฀
module฀is฀selected฀using฀the฀built-in฀rotary฀switches.฀This฀module
is฀used฀to฀switch฀an฀external฀power฀ supply,฀ which฀can฀be฀ a฀DC฀
powersupply฀or฀an฀audio฀amplifier฀(up฀to฀80฀VRMS),฀to฀notifica-
tion฀ appliances.฀ It฀ also฀ supervises฀ the฀ wiring฀ to฀ the฀ connected
loads฀and฀reports฀their฀status฀to฀the฀panel฀as฀NORMAL,฀OPEN,฀or฀
SHORT฀CIRCUIT.฀The฀FCM-1has฀two฀pairsof฀output฀termination฀
points฀ available฀ for฀ fault-tolerant฀ wiring฀ and฀ a฀ panel-controlled฀
LED฀indicator.฀This฀module฀can฀be฀used฀to฀replace฀a฀CMX-2฀mod-
ule฀that฀has฀been฀configured฀for฀supervised฀wiring฀operation.
Compatibility฀Requirements
To฀ensure฀proper฀operation,this฀module฀shall฀be฀connectedto฀a฀
compatible฀Notifier฀system฀control฀panels฀only฀(list฀available฀from฀
Notifier).
Mounting
The฀ FCM-1฀ mounts฀ directly฀ to฀ 4 ฀ square฀ electrical฀ boxes฀ (see฀
Figure฀2A).฀The฀box฀must฀have฀a฀minimum฀depth฀of฀21/8 .฀Surface฀
mounted฀electrical฀boxes฀(SMB500)฀are฀available.
Wiring
NOTE: ฀฀฀ All฀wiring฀must฀conform฀to฀applicable฀localcodes,฀ordi-
nances,฀ and฀ regulations.฀ When฀ using฀ control฀ modules฀
in฀ nonpower฀ limited฀ applications,฀ the฀ CB500฀ Module฀
Barrier฀ must฀ be฀ used฀ to฀ meet฀ UL฀ requirements฀ for฀ the฀
separation฀of฀power-limited฀and฀nonpower-limited฀termi-
nals฀ and฀ wiring.฀ The฀ barrier฀ must฀ be฀ inserted฀ into฀ a฀ 4
x4 x21/8 junction฀box,฀and฀the฀control฀modulemust฀be฀
placedinto฀the฀barrier฀and฀attached฀to฀the฀junction฀box
(Figure฀ 2A).฀ The฀ power-limited฀ wiring฀ must฀ be฀ placed
into฀the฀isolated฀quadrant฀of฀the฀module฀barrier฀(Figure฀
2B).
1.฀ Install฀module฀wiring฀in฀accordance฀with฀the฀job฀drawings฀and฀
appropriate฀wiring฀diagrams.
Figure฀1A.฀Removing
rotary฀switch฀stop:
Figure฀2A.฀Module฀mounting฀with฀barrier:
A78-2611-11
A78-2610-08
Specifications
Normal฀Operating฀Voltage: ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 15฀to฀32฀VDC
Maximum฀Current฀Draw: ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 6.5฀mA฀(LED฀on)
Average฀Operating฀Current: ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 390µA฀(LED฀flashing)
External฀Supply฀Voltage:฀ ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ (between฀Terminals฀T3฀and฀T4)
Maximum: ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 80฀Volts฀(RMS฀or฀DC)
Drain฀on฀External฀Supply: ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 2฀mA฀Maximum฀(using฀internal฀EOL฀relay)
Temperature฀Range: ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 32°F฀to฀120°F฀(0°C฀to฀49°C)
Humidity:฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 10%฀to฀93%฀Noncondensing
Dimensions: ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 41/2”฀H฀x฀4”฀W฀x฀11/4”฀D฀(Mounts฀to฀a฀4”฀square฀by฀21/8”฀deep฀box.)
Accessories:฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ SMB500฀Electrical฀Box;฀CB500฀Barrier
2.฀ Set฀the฀address฀on฀the฀module฀per฀job฀drawings.
฀฀฀฀ Note:฀ Some฀ panels฀ support฀ extended฀ addressing.฀ In฀ order฀ to฀
set฀the฀module฀above฀address฀99฀on฀compatible฀systems,฀care-
fully฀remove฀the฀stop฀on฀the฀upper฀rotary฀switch฀with฀thumb฀
in฀the฀direction฀shown฀in฀Figure฀1A.
3.฀ Secure฀ module฀ to฀ electrical฀ box฀ (supplied฀ by฀ installer),฀ as฀
shown฀in฀Figure฀2A.
IMPORTANT:฀ When฀ using฀ the฀ FCM-1฀ for฀ fire฀ fighter฀ telephone
applications,฀ remove฀ Jumper฀ (J1)฀ and฀ discard.฀ The฀ Jumper฀ is
located฀on฀the฀back฀under฀the฀ productlabel฀as฀shownin฀Figure
1B.
9
8
7
6
54
3
2
1
0
0
1
2
3
4
56789
TENS
ONES
ADDRESS
LOOP
0
78
6
5
4
3
21
910
11
12
13
14
15
ISOLATED
QUADRANT
0
1
2
3
4
9
8
7
6
5
0
TENS
ONES ADDRESS
LOOP
9
8
7
6
5
4
3
21
0
9
8
7
6
5
4
3
21
10
11
12
13
14
15
0
1
2
3
4
9
8
7
6
5
0
TENS
ONES ADDRESS
LOOP
9
8
7
6
5
4
3
21
0
9
8
7
6
5
4
3
21
10
11
12
13
14
15
Figure฀1B.฀Jumper฀location:
A78-2318-18
Figure฀2B:฀
A78-2318-07
www.PDF-Zoo.com
MODULE
FROM฀PANEL฀OR
(+)
(—)
TO฀NEXT
(+)
(—)
DEVICE
(+)
(—)
CONTROL
(—)
(+)
(—)
(+)
TO฀NEXT฀CONTROL฀MODULE฀
LAST฀MODULE฀MUST฀RETURN
WIRES฀FOR฀SUPERVISION
MODULE฀POLARITIES฀ARE
SHOWN฀IN฀ALARM
CONNECT฀MODULES฀TO฀LISTED฀COMPATIBLE
AUDIO฀CIRCUIT
3฀&฀4.฀BREAK฀WIRE฀TO฀ENSURE
SUPERVISION฀OF฀CONNECTIONS.
DO฀NOT฀LOOP฀WIRE฀AROUND฀TERMINALS
ALL฀WIRING฀SHOWN฀IS฀SUPERVISED.
(+)
NOTIFIER฀CONTROL฀PANELS฀ONLY
PREVIOUS฀DEVICE
47฀K฀EOL
RESISTOR
ELR-47K
32฀VDC฀MAX.
TWISTED฀PAIR฀
IS฀RECOMMENDED
COMMUNICATION฀LINE
(—)
AUDIO฀AMPLIFIER,฀70.7฀Vrms฀MAX.
USE฀ONLY฀MODELS฀AA-30,฀AA100฀OR฀AA-120.฀AMPLIFIER
MUST฀PROVIDE฀WIRING฀SUPERVISION฀PER฀NFPA.
SPEAKER฀SWITCHING฀CIRCUIT฀-฀NFPA฀STYLE฀W
SPEAKERS฀MUST฀BE฀LISTED฀FOR฀FIRE฀PROTECTION.฀REFER
TO฀THE฀RELAY฀CONTACT฀RATING฀TABLE฀FOR฀MAXIMUM฀LOAD.
WIRES฀MUST฀BE฀SUPERVISED฀PER฀NFPA
WHEN฀A฀70.7V฀AUDIO฀AMPLIFIER฀IS฀USED,฀TERMINALS฀1฀AND฀2฀ARE฀POWER฀LIMITED,
WHILE฀TERMINALS฀3-9฀ARE฀NONPOWER฀LIMITED.฀IN฀THIS฀CASE฀THE฀CB500฀BARRIER฀
IS฀REQUIRED.฀OTHERWISE,฀ALL฀TERMINAL฀WIRING฀IS฀POWER฀LIMITED.¹
THE฀CB500฀
INCLUDES฀A฀LABEL฀INDICATING฀WHICH฀TERMINALS฀ARE฀NONPOWER฀LIMITED.฀THIS
LABEL฀MUST฀BE฀PLACED฀OVER฀THE฀POWER-LIMITED฀TERMINAL฀INFORMATION฀ON฀
THE฀NAMEPLATE฀LABEL,฀PRESENT฀ON฀THE฀MODULE฀HOUSING.฀฀
AUDIO฀CIRCUIT฀WIRING฀MUST฀BE฀TWISTED฀PAIR฀AS฀A฀MINIMUM.
SEE฀NOTIFIER฀INSTALLATION฀MANUAL฀FOR฀DETAILED฀INFORMATION.
SUPERVISION
9
8
7
6
54
3
2
1
0
0
1
2
3
456789
TENS
ONES
ADDRESS
LOOP
0
78
6
5
4
3
21
910
11
12
13
14
15
MODULE
FROM฀PANEL฀OR
(+)
(—)
TO฀NEXT
(+)
(—)
DEVICE
(+)
(—)
CONTROL
TO฀NEXT฀CONTROL฀MODULE฀
LAST฀MODULE฀MUST฀RETURN
WIRES฀FOR฀SUPERVISION
MODULE฀POLARITIES฀ARE
SHOWN฀IN฀ALARM
CONNECT฀MODULES฀TO฀LISTED฀COMPATIBLE
AUDIO฀CIRCUIT
3฀&฀4.฀BREAK฀WIRE฀TO฀ENSURE
SUPERVISION฀OF฀CONNECTIONS.
DO฀NOT฀LOOP฀WIRE฀AROUND฀TERMINALS
ALL฀WIRING฀SHOWN฀IS฀SUPERVISED.
(+)
NOTIFIER฀CONTROL฀PANELS฀ONLY
PREVIOUS฀DEVICE
47฀K฀EOL
RESISTOR
IS฀INTERNAL
AT฀TERMINALS
8฀AND฀9
32฀VDC฀MAX.
TWISTED฀PAIR฀
IS฀RECOMMENDED
COMMUNICATION฀LINE
(—)
AUDIO฀AMPLIFIER,฀70.7฀Vrms฀MAX.
USE฀ONLY฀MODELS฀AA-30,฀AA100฀OR฀AA-120.฀AMPLIFIER
MUST฀PROVIDE฀WIRING฀SUPERVISION฀PER฀NFPA.
SPEAKER฀SWITCHING฀CIRCUIT฀-฀NFPA฀STYLE฀X
SPEAKERS฀MUST฀BE฀LISTED฀FOR฀FIRE฀PROTECTION.฀REFER
TO฀THE฀RELAY฀CONTACT฀RATING฀TABLE฀FOR฀MAXIMUM฀LOAD.
WIRES฀MUST฀BE฀SUPERVISED฀PER฀NFPA
WHEN฀A฀70.7V฀AUDIO฀AMPLIFIER฀IS฀USED,฀TERMINALS฀1฀AND฀2฀ARE฀POWER฀LIMITED,
WHILE฀TERMINALS฀3-9฀ARE฀NONPOWER฀LIMITED.฀IN฀THIS฀CASE฀THE฀CB500฀BARRIER฀
IS฀REQUIRED.฀OTHERWISE,฀ALL฀TERMINAL฀WIRING฀IS฀POWER฀LIMITED.¹
THE฀CB500฀
INCLUDES฀A฀LABEL฀INDICATING฀WHICH฀TERMINALS฀ARE฀NONPOWER฀LIMITED.฀THIS
LABEL฀MUST฀BE฀PLACED฀OVER฀THE฀POWER-LIMITED฀TERMINAL฀INFORMATION฀ON฀
THE฀NAMEPLATE฀LABEL,฀PRESENT฀ON฀THE฀MODULE฀HOUSING.฀฀
AUDIO฀CIRCUIT฀WIRING฀MUST฀BE฀TWISTED฀PAIR฀AS฀A฀MINIMUM.
SEE฀NOTIFIER฀INSTALLATION฀MANUAL฀FOR฀DETAILED฀INFORMATION.
SUPERVISION
(—)
(+)
(—)
(+)
BYPASS฀CAPACITORS฀:฀฀100฀฀¹฀f,฀16V
A2143-20฀฀฀NONPOLARIZED
฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀<10฀฀฀A฀LEAKAGE
9
8
7
6
54
3
2
1
0
0
1
2
3
456789
TENS
ONES
ADDRESS
LOOP
0
78
6
5
4
3
21
910
11
12
13
14
15
MODULE
FROM฀PANEL฀OR
(+)
(-)
TO฀NEXT
(+)
(-)
DEVICE
(+)
(-)
CONTROL
(-)
(+)
47K฀EOL
RESISTOR
ELR-47K
UL฀LISTED฀EOL฀RELAY
SHOWN฀ENERGIZED
24฀VDC฀COIL
A77-716-02
TO฀NEXT฀CONTROL฀MODULE฀OR฀END-OF-LINE-RELAY.
ONE฀RELAY฀REQUIRED฀FOR฀EACH฀CIRCUIT.
SOME฀CONTROL฀PANELS฀HAVE฀RELAY฀BUILT฀IN฀AND
DO฀NOT฀REQUIRE฀EXTERNAL฀WIRING.฀REFER฀TO฀
NOTIFIER฀MANUAL.
MODULE฀POLARITIES฀ARE
SHOWN฀IN฀ALARM
CONNECT฀MODULES฀TO฀LISTED฀COMPATIBLE
32฀VDC฀MAX.
IS฀RECOMMENDED
24฀VDC฀CIRCUIT
3฀&฀4.฀BREAK฀WIRE฀RUN฀TO฀PROVIDE
SUPERVISION฀OF฀CONNECTIONS.
DO฀NOT฀LOOP฀WIRE฀ON฀TERMINALS
ALL฀WIRING฀SHOWN฀IS฀SUPERVISED฀AND฀POWER฀LIMITED
(-)
(+)
TWISTED฀PAIR
NOTIFIER฀CONTROL฀PANELS฀ONLY
COMMUNICATION฀LINE
PREVIOUS฀DEVICE
(-)
(+)
24฀VDC฀POWER฀SUPPLY
ISOLATED,฀REGULATED,฀POWER฀
LIMITED฀PER฀NFPA฀70.
LISTED฀FOR฀FIRE฀PROTECTION฀WITH฀
BATTERY฀BACKUP.
9
8
7
6
54
3
2
1
0
0
1
2
3
456789
TENS
ONES
ADDRESS
LOOP
0
78
6
5
4
3
21
910
11
12
13
14
15
MODULE
FROM฀PANEL฀OR
(+)
(—)
TO฀NEXT
(+)
(—)
DEVICE
(+)
(—)
CONTROL
(—)
(+)
(—)
(+)
UL฀LISTED฀EOL฀RELAY
SHOWN฀ENERGIZED
24VDC฀COIL
A77-716B
MODULE฀POLARITIES฀ARE
SHOWN฀IN฀ALARM
CONNECT฀MODULES฀TO฀LISTED฀COMPATIBLE
24฀VDC฀CIRCUIT
3฀&฀4.฀BREAK฀WIRE฀RUN฀TO฀PROVIDE
SUPERVISION฀OF฀CONNECTIONS.
DO฀NOT฀LOOP฀WIRE฀ON฀TERMINALS
ALL฀WIRING฀SHOWN฀IS฀SUPERVISED
AND฀POWER฀LIMITED
(+)
NOTIFIER฀CONTROL฀PANELS฀ONLY
PREVIOUS฀DEVICE
EOL฀RESISTOR฀IS
INTERNAL฀AT
TERMINALS฀8฀&฀9
32฀VDC฀MAX.
TWISTED฀PAIR
IS฀RECOMMENDED
COMMUNICATION฀LINE
(—)
24฀VDC฀POWER฀SUPPLY
ISOLATED,฀REGULATED,฀POWER฀
LIMITED฀PER฀NFPA฀70.
LISTED฀FOR฀FIRE฀PROTECTION฀WITH฀
BATTERY฀BACKUP.
TO฀NEXT฀CONTROL฀MODULE฀OR฀END-OF-LINE-RELAY.
ONE฀RELAY฀REQUIRED฀FOR฀EACH฀CIRCUIT.
SOME฀CONTROL฀PANELS฀HAVE฀RELAY฀BUILT฀IN฀AND
DO฀NOT฀REQUIRE฀EXTERNAL฀WIRING.฀REFER฀TO฀
NOTIFIER฀MANUAL.
9
8
7
6
54
3
2
1
0
0
1
2
3
456789
TENS
ONES
ADDRESS
LOOP
0
78
6
5
4
3
21
910
11
12
13
14
15
N500-46-00฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 3 ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀I56-1169-07
Figure฀5.฀Typical฀wiring฀for฀speaker฀supervision฀and฀switching,฀NFPA฀Style฀Y:
Figure฀6.฀Typical฀fault฀tolerant฀wiring฀for฀speaker฀supervision฀and฀switching,฀NFPA฀Style฀Z:฀
A78-2284-11
A78-2285-10
CONNECT฀MODULES฀TO฀LISTED฀COMPATIBLE
NOTIFIER฀CONTROL฀PANELS฀ONLY
N500-46-00฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀ 2 ฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀I56-1169-07
Figure฀3.฀Typical฀notification฀appliance฀circuit฀configuration,฀NFPA฀Style฀Y:
Figure฀4.฀Typical฀fault฀tolerant฀notification฀appliance฀circuit฀configuration,฀NFPA฀Style฀Z:
A78-2283-12
A78-2282-12