MCX102DR v1.0 Expander Installation Guide Rev.A.doc 2018-05-29
Strona 1 z 2
Roger Access Control System
MCX102DR Expander Installation Guide
Firmware: 1.0.2
Hardware version: v1.0
Document version: Rev. A
Manual dedicated for: MCX102DR and MCX102DR-BRD
This manual contains minimum information that is necessary to properly
install device. For more information refer to RACS 5 documentation
which is available at www.roger.pl
INTRODUCTION
Before MCX102DR will be installed in final location, it should be
connected to installer computer (laptop) and configured by means of
RogerVDM utility program. Connection between programming computer
and programmed device requires RUD-1 USB interface. During
configuration the RS485 address should be set along with other
configuration parameters. Optionally, the MCX’s address can be set
using programming jumpers (see Hardware Address Setting section
later in this manual). If used, the hardware address has higher priority
than address programmed by RogerVDM program.
Note: During some programming procedures, the so called “device
restart” is required. It can be executed by pressing RESET (MCX102DR)
or RST (MCX102DR-BRD) button. Optionally, device can be restarted by
disconnecting and reconnecting its power supply.
CONFIGURATION
1. Connect MCX102DR to RUD-1 interface as indicated on Fig.1.
2. Run RogerVDM program.
3. Click Device->Connect.
4. Select proper device model, firmware version and communication
port (COM) emulated by RUD-1 interface.
5. Click Connect and program will display main configuration window
with parameters read from the connected device.
6. Set device address (100-115) and other configuration parameters.
7. Click Send to device to upload modified configuration parameters to
the connected device.
8. Optionally, save configuration parameters to file using Save to file
button.
9. Click Device->Disconnect.
10. Configuration is accomplished - disconnect programmed device
from RUD-1 interface.
Fig. 1 Connecting MCX102DR to RUD-1 interface.
HARDWARE ADDRESS SETTING
Alternatively, the RS485 address can be set using “1”, “2”, “4”, “8” and
“16” programming jumpers (see Fig. 2). If all these jumpers are left
open, MCX102DR operates with address set by RogerVDM. If set, the
hardware address has higher priority than address set by RogerVDM
program.
Note: Whenever hardware address is changed device must be restarted
in order to make new address valid.
Fig. 2 Setting RS485 hardware address.
MEMORY RESET
Memory Reset restores all factory default configuration parameters
including address ID=100.
1. Remove any existing connections from A, B, CLK and DTA screw
terminals.
2. Put jumper on “64” contact.
3. Restart device.
4. Once the device is restarted the LED STATUS (red), LED OPEN and
LED SYSTEM will turn ON.
5. Remove jumper from “64” contacts.
6. LED OPEN and LED SYSTEM will turn OFF.
7. Memory Reset is accomplished – default parameters are restored.
FIRMWARE UPDATE
1. Connect MCX102DR to RUD-1 interface according to Fig.1.
2. Put a jumper on FDM contacts (for FDM contact location see Fig.3).
3. Restart device.
4. Run RogerISP software.
5. Select serial port emulated by RUD-1 interface.
6. Click and activate USB-RS485 Converter option.
7. Select HDD location where new firmware is stored (*.hex file).
8. Click Program and follow instructions on the screen.
9. Once the firmware is uploaded remove the FDM jumper.
10. Restart device.
11. Execute Memory Reset.
OTHER INFORMATION