Powerware 500VA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

Powerware
®
FERRUPS
FE/QFE UPS
Installation Guide
500 VA18kVA,50and60Hz
Powerware
®
FERRUPS
FE/QFE UPS
Installation Guide
500 VA18kVA,50and60Hz
www.powerware.com
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment
Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
For Users in Germany
We hereby certify that the uninterruptible power system (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, 1.4 kVA, 1.8 kVA,
2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) complies with the RFI suppression
requirements of Vfg. 243/1991 and Vfg. 46/1992. The German Postal Service was notified that the equipment is being
marketed. The German Postal Service has the right to retest the equipment and verify compliance.
Hiermit wird bescheinigt, daß die unterbrechungsfreie Stromversorgung (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA,
1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) in Übereinstimmung mit
den Bestimmungen der Vfg. 243/1991 und Vfg. 46/1992 funkentstört ist. Der Deutschen Bundespost wurde das
Inverkehrbringen dieses Gerätes angezeigt und die Berechtigung zur Überprüfung der Serie auf Einhaltung der
Bestimmung eingeräumt.
Powerware reserves the right to change specifications without prior notice.
Powerware is a registered trademark of Powerware Corporation.
Copyright 2002 Powerware, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any
way without the express written approval of Powerware.
i
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
TABLE OF CONTENTS
1 Introduction 1....................................................
Plug-Receptacle Installation 1.....................................................
Hardwired Installation 1.........................................................
2 Safety Warnings 3................................................
3 Setup 17.........................................................
Dimensions 17.................................................................
Equipment Clearances 19.........................................................
Location Requirements 20.........................................................
Storage and Operating Environment 21................................................
4 Electrical Installation 23............................................
Bypass Switches 24.............................................................
5 External Bypass Switch Installation 29.................................
Installation Wiring Diagrams for External Bypass Switches 34...............................
6 Internal Bypass Switch Installation 45.................................
Installation Wiring Diagrams for Internal Bypass Switches 48................................
7 Battery Cabinet Installation 53.......................................
Before Installing the Batteries 54....................................................
Installing and Connecting the Batteries 56.............................................
Replacing the Batteries 63........................................................
Recycling the Used Battery 64......................................................
8 Phase Check 65...................................................
Table of Contents
ii
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
1
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
CHAPTER 1
INTRODUCTION
The Powerware FERRUPS uninterruptible power system (UPS) is
available in plug-receptacle or hardwired models. The plug-receptacle
models have an input plug and receptacles on the rear panel. The
hardwired models have terminal strips that an electrician has to wire to
AC input.
See the following sections for steps on how to use this manual for your
UPS installation.
Plug-Receptacle Installation
Only a few sections in this manual are required for installing
plug-receptacle models:
:
Be sure to read all safety warnings before installing the UPS as stated
in Chapter 2, “Safety Warnings.”
:
Complete Chapter 3, “Setup” for setting up the location of the UPS.
:
If you purchased an external battery cabinet, an electrician must wire
the battery to the UPS as described in Chapter 7, “Battery Cabinet
Installation.”
:
Continue to the startup section in the Powerware FERRUPS FE/QFE
UPS (500 VA–18kVA) User’s Guide.
Hardwired Installation
Most of the sections in this manual are required for the electrician to
install the hardwired models:
:
Be sure to read all safety warnings before installing the UPS as stated
in Chapter 2, “Safety Warnings.”
:
Complete Chapter 3, “Setup” for setting up the location of the UPS.
:
Chapter 4, “Electrical Installation” describes the electrical
requirements for hardwiring the UPS.
:
Continue to either Chapter 5, “External Bypass Switch Installation”
or Chapter 6, “Internal Bypass Switch Installation” depending on the
thetypeofbypassswitchbeinginstalled.
Introduction
2
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
:
If you purchased an external battery cabinet, see Chapter 7, “Battery
Cabinet Installation” for wiring connections.
:
Complete the phase check as described in Chapter 8, “Phase Check.”
:
Continue to the startup section in the Powerware FERRUPS FE/QFE
UPS (500 VA–18kVA) User’s Guide.
3
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
CHAPTER 2
SAFETY WARNINGS
Read the following precautions before you install the UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you
should follow during installation and maintenance of the UPS and batteries. Please
read all instructions before operating the equipment and save this manual for future
reference.
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed
by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER
SERVICEABLE PARTS inside the UPS.
WARNING
: This UPS contains its own energy source (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
: Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
: To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient
temperature must not exceed 40°C (104°F). Do not operate near water or
excessive humidity (95% max).
: To comply with international standards and wiring regulations, the total equipment
connected to the output of this UPS must not have an earth leakage current
greater than 1.5 milliamperes.
Safety Warnings
4
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
CAUTION
: Batteries can present a risk of electrical shock or burn from high short-circuit
current. Observe proper precautions. Servicing should be performed by qualified
service personnel knowledgeable of batteries and required precautions. Keep
unauthorized personnel away from batteries.
: Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
: Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE
SIKKERHEDSANVISNINGER
FARE
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og
vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af
UPS’ens indvendige dele kan repareres af brugeren.
ADVARSEL!
: Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
: Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
: Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit
for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk
stød. Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær
vand eller høj fugtighed (maksimalt 95%).
: I overensstemmelse med internationale normer og bestemmelser for el-installation
må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke
overskride en jordafdelingsspænding på mere end 1,5 milliampere.
17
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
CHAPTER 3
SETUP
This chapter explains the requirements for setting up the UPS:
:
UPS, battery cabinet, and bypass switch dimensions
:
Equipment clearances
:
Location requirements
:
Moving the UPS and batteries
:
Storage and operating environment
Dimensions
Table 1. FERRUPS FE/QFE 500 VA–3.1 kVA Dimensions
Dimensions (See Figure 1)
UPS Model
Height (A) Width (B) Depth (C)
500 VA, 700 VA, and 850 VA 122 (30.5 cm) 102 (25.5 cm) 21.252 (54.0 cm)
1.15 kVA and 1.4 kVA 15.12 (38.5 cm) 15.22 (39.0 cm) 20.22 (51.5 cm)
1.8 kVA, 2.1 kVA, and 3.1 kVA 21.22 (54.0 cm) 15.252 (39.0 cm) 22.92 (58.5 cm)
E
A
B
C
F
D
Figure 1. UPS Dimensions
Setup
18
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
Table 2. FERRUPS FE/QFE 4.3–18 kVA Dimensions
Dimensions (See Figure 1)
UPS Model
Height (D) Width (E) Depth without
Internal Bypass (F)
Depth with Internal
Bypass Switch (F)
4.3 kVA and 5.3 kVA 29.52 (75.0 cm) 15.52 (39.5 cm) 252 (63.5 cm) 332 (84.0 cm)
7 kVA, 10 kVA, 12.5 kVA, and 18 kVA 36.52 (93.0 cm) 192 (48.5 cm) 322 (81.5 cm) 402 (102.0 cm)
Table 3. Battery Cabinet Dimensions
Dimensions (See Figure 2)
Model
Height Width Depth
ASY-0468 12.252 (31.5 cm) 15.752 (40.0 cm) 28.52 (72.5 cm)
ASY-0386 372 (94.0 cm) 192 (48.5 cm) 322 (81.5 cm)
ASY-0387 492 (124.5 cm) 152 (38.5 cm) 322 (81.5 cm)
ASY-0385 and ASY-0685 512 (129.5 cm) 302 (76.5 cm) 322 (81.5 cm)
Figure 2. Battery Cabinet Dimensions
Table 4. Bypass Switch Dimensions
Dimensions (See Figure 3)
Model
A B C D E
BPE-01 122 (30.5 cm) 62 (15.2 cm) 132 (33.0 cm) 102 (25.4 cm) 32 (7.6 cm)
BPE-02 162 (40.6 cm) 82 (20.3 cm) 172 (43.2 cm) 122 (30.5 cm) 72 (17.8 cm)
BPE-04 and BPE-05 172 (43.2 cm) 122 (30.5 cm) 182 (45.7 cm) 162 (40.6 cm) 92 (22.9 cm)
Setup
19
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
DD
A
B
BPE-01 BPE-02, 04, and 05
C
E
A
B
C
E
Figure 3. Bypass Switch Dimensions
Equipment Clearances
All cabinet sizes require the following clearances to allow for servicing
and adequate ventilation:
Table 5. Clearances for the UPS and Battery Cabinets
Dimensions (see Figure 4)
Sides (G) Front (H) Top (I) Back (J)
362 (91.5 cm) 362 (91.5 cm) 122 (30.5 cm) 42 (10.0 cm)
NOTE A minimum clearance of 4
2
(10 cm) is required on the sides, front, and back
and 12
2
(30.5 cm) above the UPS for proper ventilation.
NOTE For 4.3–18 kVA models with an internal bypass switch, measure from the back
of the switch.
Setup
20
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
J
I
I
G
G
H
H
Figure 4. Installation and Service Clearances
Location Requirements
Install the FERRUPS as close as possible to the equipment to be
protected. If the UPS is more than 25 ft (7.6m) from the equipment,
transient noise can reappear in the electrical distribution system. The
UPS should be well ventilated and away from direct sunlight or other
heat source.
The environment can affect the reliability and performance of both the
UPS and the batteries. Verify the storage and operating environmental
requirements on page 21.
If additional FERRUPS system batteries are in a separate external battery
cabinet, the cabinet should be located as close as possible to the
FERRUPS UPS. If the batteries will be further from the unit than the
standard cables allow, contact your service representative or your local
distributor for assistance.
Setup
21
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
Storage and Operating Environment
Storage Temperature: Store the batteries (in the UPS or external battery
cabinet) at
-20° to +40°C(-4° to +104°F). Batteries will have a longer
shelf life if they are kept below 25°C(77°F). The UPS or external battery
cabinet without batteries may be stored at
-20° to +60°C(-4° to
+140°F).
Ventilation: The air around the UPS must be clean and free of dust,
corrosive chemicals, and other contaminants. The air must be free to
circulate around the UPS and battery cabinet(s).
NOTE Do not place the UPS or batteries in a sealed room or container.
Operating Temperature: The UPS can operate from 0° to +40°C(+32° to
+104°F). Do not operate near water or excessive humidity (95% max).
For full battery life, keep the UPS at an ambient temperature of 25°C
(77°F).
High Altitude Operation: The maximum operating temperature drops 1°C
per 300m (2°F per 1000 ft) above sea level. Maximum elevation is
3000m (10,000 ft).
Setup
22
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
23
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
CHAPTER 4
ELECTRICAL INSTALLATION
NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on
page 53 to install optional battery cabinets or to the startup section in the
Powerware
FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide
.
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the
hardwired installation. Risk of electrical shock.
Before installing your UPS, complete the following information:
1. From the ID label on the UPS rear panel:
Model number:
Input voltage:
Output voltage:
2. From the bypass switch label:
Model number:
Internal or External?
Make-Before-Break (MBB) or Break-Before-Make (BBM)?
3. Verify that the UPS input and output voltages are what is
required for your application:
Does the input voltage for the UPS at the AC service panel
match the input voltage in Step 1?
Does the output voltage in Step 1 match the output voltage of
the equipment you are using with the UPS?
NOTE The FERRUPS provides single-phase power only.
4. If you answered NO to either question in Step 3, contact your
service representative or your local distributor for assistance.
Electrical Installation
24
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
Bypass Switches
Bypass switches are available in two types: external (a separate cabinet
that is wall-mounted) or internal (attached to the back of the UPS). The
bypass switch has three positions as described in Table 6.
Table 6. Bypass Switch Positions
Switch Position Description
LINE Connects the load directly to AC input power and disconnects UPS output.
AC input power is still connected to the UPS input.
OFF Disconnects the load from the UPS output power and AC input power.
UPS Connects the UPS output to the load.
NOTE In all three positions, AC input power is still connected to the input terminals
inside the UPS (once the UPS is installed). Use the AC disconnect switch (located on
the right side of the bypass switch) to disconnect AC input power during maintenance
or service.
Bypass switches may be MBB or BBM.
An MBB switch makes a new connection before it breaks the original
connection. For example, if you turn an MBB switch from UPS to LINE,
the bypass switch connects the load to AC input power before
disconnecting the load from UPS output power.
NOTE MBB switches are not for use with 208 Vac.
A BBM switch breaks the original connection before it makes a new one.
If you turn a BBM switch from UPS to LINE, the switch disconnects the
load from UPS output power before connecting the load to AC input
power.
Electrical Installation
25
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
Table 7 and Table 8 show the bypass switch models available for the
FERRUPS UPS.
Table 7. External Bypass Switch Specifications
Model
Number
Ratings (UL/CSA)
Continuous
Ratings (TÜV)
Continuous
Weight
BPE-01 30A/300 Vac 30A/300 Vac 8.25 lb/3.7 kg
BPE-02 40A/300 Vac 50A/300 Vac 19.75 lb/9 kg
BPE-04 80A/300 Vac 80A/300 Vac 30 lb/13.6 kg
BPE-05 104A/300 Vac 120A/300 Vac 32.75 lb/14.9 kg
Table 8. Internal Bypass Switch Specifications
Model Number Ratings (UL/CSA) Continuous Ratings (TÜV) Continuous
BPI-02 40A/300 Vac 50A/300 Vac
BPI-03 46A/ 300 Vac 55A/300 Vac
BPI-04 80A/ 300 Vac 80A/300 Vac
BPI-05 104A/300 Vac 120A/300 Vac
Figure 5 shows a UPS with a separate battery cabinet and an external
bypass switch. Continue to Chapter 5, “External Bypass Switch
Installation” on page 29 for electrical connections.
Electrical Installation
26
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
Connect to (DC)
External Batteries
Building
Service
Panel
Load
Distribution
Panel
External
Bypass Switch
On
AC
Disconnect
Line
Off
Bypass
Switch
UPS
Off
UPS
Figure 5. Typical Hardwired Installation with External Bypass Switch
Electrical Installation
27
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
Figure 6 shows a UPS with a separate battery cabinet and an internal
bypass switch. Internal bypass switches are available only for FE/QFE
4.3–18 kVA models. Continue to Chapter 6, “Internal Bypass Switch
Installation” on page 45 for electrical connections.
Off
Building
Service
Panel
Load
Distribution
Panel
Connect to (DC)
if there are
External Batteries
Back of UPS
Internal Bypass Switch
AC
Disconnect
Line
Bypass
Switch
UPS
Off
On
Figure 6. Typical Hardwired Installation with Internal Bypass Switch
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76

Powerware 500VA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI