Ferrups 0800-7500 Installation guide

Category
Uninterruptible power supplies (UPSs)
Type
Installation guide

This manual is also suitable for

INSTALLATION MANUAL
FERRUPS
0800-2000 - 0800-7500
FERRUPS®Installation Manual
0800-2000 through 0800-7500
2 kVA-7.5 kVA 50 and 60 Hz
Uninterruptible Power Systems
IMPORTANT SAFETY INSTRUCTIONS.
SAVE THESE INSTRUCTIONS.
This manual contains important instructions for your UPS.
LTM-1320E
© 1998-1999 Best Power. All rights reserved.
Introduction
This manual is for the types of models listed below.
• All models that do not have a power cord and input plug or that do not have output receptacles. A qualified
electrician must install the AC wiring for these models and connect your protected equipment. Sections
200, 300, and 500 of this manual describe the AC wiring and phase check.
• All models that have a separate battery cabinet. Section 300 describes battery installation.
The installation and use of this product must comply with all national, federal, state, municipal, or local codes
that apply. If you need help, please call the nearest Best Power office.
Best Power
P.O. Box 280
Necedah, WI 54646 U.S.A.
Telephone: 1-608-565-7200
Toll-Free: 1-800-356-5794 (U.S.A. and Canada)
FAX: 1-608-565-2221
International FAX: 1-608-565-7675
Worldwide Service
P.O. Box 11
Necedah, WI 54646 U.S.A.
Telephone: 1-608-565-2100
Toll-Free: 1-800-356-5737 (U.S.A. and Canada)
FAX: 1-608-565-7642
Best Power Technology Mexico, S.A. de C.V.
Golfo de Riga, 34
Colonia Tacuba
Mexico D.F. 11410
MEXICO
Telephone: (52) 5-5-527-8009
Toll-Free 1-800-711-8978
FAX: (52) 5-399-1320
Best Power Technology Pte. Ltd.
30 Prinsep St. #07-00
LKN Prinsep House
SINGAPORE 188647
Telephone: (65) 430-6168
FAX: (65) 430-6170
Sola Australia Ltd.
13 Healey Road
Dandenong, Victoria 3175
AUSTRALIA
Telephone: (61) 3-9706-5022
FAX: (61) 3-9794-9150
Best Power Technology Limited
BEST House
Wykeham Industrial Estate
Moorside Road
Winchester
Hampshire
S023 7RX
ENGLAND
Telephone: (44) 1962-844414
Toll-Free: 0800 378444
FAX: (44) 1962-841846
Best Power Technology Germany GmbH
Am Weichselgarten 23
D-91058 Erlangen
Telephone: (49) 9131-77700
Toll-Free: 0130-84-7712 (in Germany)
FAX: (49) 9131-7770-444
Borri Elettronica Industriale Srl
Via dei Lavoratori, 124
20092 Cinisello Balsamo (Mi)
Milan, ITALY
Telephone: (390) 2-6600661-2
FAX: (390) 2-6122481
3
Contents
100 Before Installing the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
101 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
102 Installation and Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
103 Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
104 Receiving and Moving the FERRUPS and Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . .5
105 Storage and Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
106 Bypass Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
200 Overview of UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
300 AC Installation of the UPS and Bypass Switch (for Qualified Personnel Only) . . . . . . . . . . . . . . . . . . .8
301 Starting AC Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
302 Installing Models with External Bypass Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
303 Installing Models with Internal (Attached) Bypass Switches . . . . . . . . . . . . . . . . . . . . . . . . . .20
400 Connecting the External Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
401 Important Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
402 Tools Needed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
403 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
404 Connecting the Battery Cabinet(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
405 Turning the DCSwitch On and Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
500 Parameters and Phase Check (for Qualified Personnel Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Appendix A: Connections for the Emergency Power Off (EPO) Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
4
100 Before Installing the UPS
101 Dimensions
Table 1: 2 kVA to 7.5 kVA Dimensions
Table 2: Battery Cabinet Dimensions
Table 3: Bypass Switch Dimensions Figure 2
C
B
A
B
A
C
Model Height
(A) Width
(B) Depth with
Internal
(Attached) Bypass
Depth
(C)
2 and 3
kVA 27.25 in.
695 mm 13.5 in.
345 mm 35 in.
890 mm
28.5 in.*
725 mm*
4.5 kVA 30.5 in.
775 mm 13.5 in.
345 mm 31.5 in.
800 mm
25 in.*
635 mm*
6 and
7.5 kVA 38.75 in.
985 mm 13.5 in.
345 mm 39 in.
990 mm
32.5 in.*
825 mm*
32.5 in.*
825 mm*
13.5 in.
345 mm
38.75 in.
985 mm
FBT30
FBT31
FBT32
28.5 in.*
725 mm*
13.5 in.
345 mm
27.25 in.
695 mm
FBT20
FBT21
FBT22
Depth (C)Width (B)Height (A)Model
20 in.
508 mm
E
BPE14
11 in.
280 mm
D
6.75 in.
172 mm
C
14 in.
356 mm
B
21 in.
534 mm
A
20 in.
508 mm
11 in.
280 mm
6.75 in.
172 mm
14 in.
356 mm
21 in.
534 mm
E
BPE12
DCBA
* Add the depth of the battery connection box, 2.6
inches.
* For units with separate battery cabinets, add the depth of the
battery connection box, 2.6 inches.
CB
D
E
A
Figure 3
Figure 1
5
102 Installation and Service Clearances
Table 4: Service Clearances for FERRUPS Figure 4
and Battery Cabinets
Note: If you use flexible conduit to connect the UPS and
battery cabinets, you may be able to achieve the service
clearances by moving the UPS. If this is the case, you
must still leave 12 inches (305 mm) clearance at the front
and back of the UPS for ventilation. Do not block the ventilation
holes on each side of the front panel.
103 Location Requirements
• Install the FERRUPS as close as possible to the equipment it will protect. If this distance is more than 25 feet
(7.6 meters), transient noise can reappear in the electrical distribution system.
• If the FERRUPS batteries are in a separate cabinet, the battery cabinet should be as close to the FERRUPS as
possible. If the batteries will be farther away from the unit than the standard cables allow, call the nearest Best
Power office for assistance.
104 Receiving and Moving the FERRUPS and the Batteries
Note the FERRUPS and battery cabinet weights in the User Manual. Before you unload or move the FERRUPS
or the battery cabinet, make sure your method of moving them is appropriate for their weights.
105 Storage and Operating Environment
Storage Temperature: Store a FERRUPS with internal batteries or a battery cabinet at –20° to +40°
Celsius (–4° to +104° F). Batteries will have a longer shelf life if you store them
below 25° C (77° F). A UPS without internal batteries may be stored at –20° to
+60° Celsius (–4° to +140° F).
Operating Temperature: 0° to 40° Celsius (32° to 104° F), up to 95% relative humidity without
condensation. The batteries last longer if the operating temperature stays below 25°
C (77° F).
Ventilation: The air around the UPS must be clean, dust-free, and free of corrosive chemicals or
other contaminants. The air must be free to circulate around the UPS cabinet and
any battery cabinets. Do not place the UPS or batteries in a sealed room or
container.
High Altitude Operation: The maximum operating temperature drops 1° Celsius per 300 meters above sea
level (2° F per 1000 feet above sea level). Maximum elevation is 3000 meters
(10,000 feet).
12 in.
305 mm
36 in.
915 mm
36 in.
915 mm
12 in.
305 mm
Back (D)Top (C)Front (B)Sides (A)
C
C
C
C
A
AB
D
B
6
106 Bypass Switches
If your FERRUPS model does not have a power cord and plug, you should have a Best Power bypass switch.
The cabinet for these switches may be separate (external) or attached to the back of the UPS (internal).
The bypass switch has four positions (see Table 5 below). In the UPS or LINE positions, AC input power is
still connected to the input terminals inside the UPS once it is installed. To disconnect AC input power
during maintenance or service, turn the bypass switch to SERVICE. For Make-Before-Break switches, please
note that you must press the red button before you can change the switch position.
Table 5: Bypass Switch Positions
Bypass switches may be Make-Before-Break (MBB) or Break-Before-Make (BBM).
Make-Before-Break switches make a new connection before they break the present connection. For example, if
you turned the switch from “UPS” to “LINE,” the bypass switch would connect your protected equipment to AC
input power before disconnecting the equipment from UPS output power. Make-Before-Break switches are not
for use with 208 VAC.
Break-Before-Make switches break the present connection before they make a new one. If you turned a Break-
Before-Make switch from “UPS”to “LINE,” the switch would disconnect your protected equipment from UPS
output power before connecting the equipment to AC input power.
Bypass switches come in four models, and each model has its own ratings for current and voltage. Table 6 below
lists the ratings and weights for Best Power bypass switches.
Table 6: Bypass Switch Ratings and Weights
Switch Position Explanation
LINE Connects the loads (protected equipment) directly to AC line input and disconnects UPS output. AC
line input is still connected to the UPS itself.
OFF Disconnects the protected equipment from both UPS output power and AC input power.
SERVICE
UPS
Like the LINE position, SERVICE connects the loads (protected equipment) directly to AC line input
and disconnects UPS output. However, since SERVICE also disconnects AC input, this is the
appropriate switch position during UPS maintenance or repair.
Connects the UPS output to the protected equipment.
Bypass Switch Model Ratings, Continuous Weight (lbs/kg)
BPE12
(External Bypass Switch) 40A/300VAC (CSA)
50A/300VAC (UL, TÜV) 27 lbs. / 12.3 kg
BPE14
(External) 80A/300VAC 31 lbs. / 14.1 kg
Internal Bypass Switch for
2 kVA and 3 kVA Models 40A/300VAC (CSA)
50A/300VAC (UL, TÜV)
Internal Bypass Switch for
4.5, 6 and 7.5 kVA Models 80A/300VAC
7
200 Overview of UPS Installation
Figure 6 below shows a typical installation for FERRUPS units that do not have an input power cord and plug.
This diagram shows a unit with a separate battery cabinet and a separate bypass switch. In units with internal
bypass switches, the switch is attached to the back of the UPS, and the UPS is already wired to the switch.
Typical Installation with an External (Separate) Bypass Switch
Figure 6
Building
Service
Panel
External Bypass Switch
Load
Distribution
Panel
UPS
UPS
OFF
OFF
SERVICE
SERVICE
LINE
LINE
UPS
OFF
SERVICE
LINE
UPS
Output
DC Switch
(on Back of Cabinet)
8
300 AC Installation of the UPS and Bypass Switch
(for Qualified Personnel Only)
301 Starting ACInstallation
1.Find the FERRUPSID label on the back panel, and note the following:
Model Number:__________ Input Voltage:__________ Output Voltage:__________
2.Next, find the bypass switchs ID label, and write down the following:
Model Number:__________ Make-Before-Break (MBB) or Break-Before-Make (BBM)? __________
External (Separate) or Internal (Attached)? __________
3. Now, answer the questions below. Remember that the FERRUPS provides single-phase power only.
a. Does the input voltage at the AC service panel match the input voltage on the UPS ID label?
Service panel voltage: ________ = UPS Input Voltage: ________ lYes lNo
b. Does the output voltage on the UPS ID label match the voltage your loads (protected equipment) will
need?
Load voltage: ________ = UPS Output Voltage: ________ lYes lNo
If the answer to either a. or b. is No, call the nearest Best Power office for assistance.
CAUTION
Read the cautions below before you begin AC installation:
A.All UPS units contain hazardous AC and DC voltages. Because of this, a qualified electrician must install
the UPS and AC line service. The electrician must install AC line according to local and national codes.
B.This equipment relies on protection devices in the building installation. These devices must be installed
within sight of the UPS.
C.Before you install, maintain, or service the UPS, always remove or shut off all sources of AC and DC
power and shut off the UPS. You must disconnect AC line input at the service panel, turn the DC switch
OFF and shut the UPS down to make sure it will not supply output voltage.
D.Whenever AC and/or DC voltage is applied, there may be AC voltage at the UPS terminals; this is true
because the UPS can supply power from AC input or from its batteries. To avoid equipment damage or
personal injury, always assume that there may be voltage at the UPS terminals.
E.Before you install the bypass switch, make sure that the bypass switch is OFF.
F.To reduce the risk of fire or electric shock, install the FERRUPS and the batteries in a temperature-
controlled and humidity-controlled indoor area free of conductive contaminants. See Section 105 for
operating environment specifications.
9
4. Now use the information you wrote down in steps 1-3 to find the Installation Wiring Diagram that applies to
your FERRUPSinstallation. If the bypass switch is external (separate), use Table 7. If it is internal (attached),
use Table 8.
Table 7: Installation Wiring Diagrams for Units with External Bypass Switches
* With a step-up or step-down transformer.
** Call Best Power for a) single-phase installations that do not have the same input and output voltage, or b) split-
phase installations that require 220 or 127 VAC.
Table 8: Installation Wiring Diagrams for Units with Internal Bypass Switches
* With a step-up or step-down transformer.
** Call Best Power for a) single-phase installations that do not have the same input and output voltage, or b) split-
phase installations that require 220 or 127 VAC.
Figure 12 and Figure 13AMake-Before-Break or Break-Before-Make208 or 480 Source*/ 240 Input
Figure 11 and Figure 13A
Call Best Power.**
Figure 11 and Figure 13E
Call Best Power.**
Figure 11 and Figure 13D
Figure 11 and Figure 13C
Figure 11 and Figure 13A
Figure 11 and Figure 13B
Figure 11 and Figure 13B
Make-Before-Break or Break-Before-Make
Break-Before-Make only.
Make-Before-Break or Break-Before-Make
Break-Before-Make only.
Make-Before-Break or Break-Before-Make
Make-Before-Break or Break-Before-Make
Break-Before-Make only.
Break-Before-Make only.
Break-Before-Make only.
240 input and 120/240 output
240 input and 208 output**
230 input and 230 output
220 input and 127 output**
220 input and 220 output
220 input and 220 output (Mexico)
208 input and 120/240 output
208 input and 120/208 output
208 input and 208 or 240 output
Figure 10 and Figure 13A or 13H
Figure 10 and Figure 13E or 13G
Figure 10 and Figure 13D or 13F
Figure 10 and Figure 13C
Figure 10 and Figure 13A
Make-Before-Break or Break-Before-Make
Make-Before-Break or Break-Before-Make
Make-Before-Break or Break-Before-Make
Break-Before-Make only.
Make-Before-Break or Break-Before-Make
240 input and 240 output
230 input and 230 output
220 input and 220 output
(except Mexico)
127 input and 127 output
120 input and 120 output
Use These Diagrams:Bypass Switch TypeInput and Output VAC
Call Best Power.**
Figure 17
Break-Before-Make only.
Make-Before-Break or Break-Before-Make
220 input and 127 output**
240 input and 208 output**
208 or 480 Source*/ 240 Input
Figure 16Make-Before-Break or Break-Before-Make
For 208 VAC,
Break-Before-Make only.
208 input and 208 output
208 input and 120/208 output
208 in put and 120/240 output
220 input and 220 output (Mexico)
230 input and 230 output
240 input and 120/240 output
Figure 15Make-Before-Break or Break-Before-Make
For 127 VAC, Break-Before-Make only.
120 input and 120 output
127 input and 127 output
220 input and 220 output (except Mexico)
230 input and 230 output
240 input and 240 output
Use This Diagram:Bypass Switch TypeInput and Output VAC
10
5.Now, refer to the wiring diagram that you selected in step 3, and use Tables 9 and 10 below to find the
proper size circuit breaker for your installation. Table 9 shows the required input circuit breaker size for U.S.
installations. Table 10 shows the input current for each voltage; size input overcurrent protection according
to local codes. In the U.S., use the circuit breaker size and Table 11to size the wiring. In other areas, size
wiring according to local code, making sure you use 75° C copper wire.
Table 9: Required Input Circuit Breaker Sizes for U.S. Installations (60 Hz)
Table 10: Input Current (Size input overcurrent protection according to local codes.)
UPS
Model 115V110VFrequency 240V230V220V208V127V120V
2 kVA22 amps22 amps60 Hz 12 amps12 amps12 amps12 amps22 amps22 amps
22 amps22 amps50 Hz 12 amps12 amps12 amps12 amps22 amps22 amps
3 kVA30 amps30 amps60 Hz 16 amps16 amps16 amps16 amps30 amps30 amps
30 amps30 amps50 Hz 16 amps16 amps16 amps16 amps30 amps30 amps
4.5
kVA40 amps40 amps60 Hz 20 amps20 amps20 amps20 amps40 amps40 amps
40 amps40 amps50 Hz 20 amps20 amps20 amps20 amps40 amps40 amps
6 kVA60 Hz 28 amps28 amps28 amps28 amps
50 Hz 28 amps28 amps28 amps28 amps
7.5
kVA60 Hz 36 amps36 amps36 amps36 amps
45-amp45-amp7.5 kVA
35-amp35-amp6 kVA
25-amp25-amp50-amp4.5 kVA
20-amp20-amp40-amp3 kVA
15-amp15-amp30-amp2 kVA
240V208V120V
UPS
Model
11
Table 11: United States Recommended AWG and mm2Wire Sizes
6.Size the UPS output overcurrent protection device (fuse or circuit breaker) according to local code
requirements. Do not exceed the ratings in Table 12. The table below shows the maximum permitted
overcurrent protection device ratings; these are also the ratings recommended for U.S. applications.
Table 12: Maximum Permitted UPS Output Overcurrent Protection Device Rating
7.If your model has an externalbypass switch, go on to Section 302below.
If your model has an internal(attached) bypass switch, go to Section 303on page 20.
For this Input
Circuit Breaker
Size...
Use this Size 75° C
Copper Wire
AWG mm2
15, 20 12 3.31
25, 30 10 5.26
35, 40, 45, 50 8 8.36
60 6 13.30
70, 80 4 21.15
90, 100 3 26.67
110 2 33.62
125 1 42.11
For U.S. installations, read this Important Note!
This table lists the AWG and mm2wire size for each circuit breaker
size shown on the wiring diagrams. The minimum recommended
circuit breaker sizes for each model and voltage application are
listed on the wiring diagrams.
The conductor size shall be no smaller than the 75° C wire size
based on the ampacities given in Tables 310-316 of the National
Electrical Code, ANSI/NFPA 70-1993, and article 220. All circuit
conductors, including the neutral and equipment grounding
conductors, must be the same size (ampacity) wire. Code may
require a larger AWG size than shown in this table because of
temperature, number of conductors in the conduit, or long service
runs. Follow local code requirements. 150 1/0 53.49
33 A35 A45 A60 / 35 A60 A80 / 40 A80 / 45 A7.5 kVA
27 A28 A40 A48 / 28 A48 A70 / 35 A70 / 40 A6 kVA
20 A21 A30 A36 / 21 A36 A50 / 25 A50 / 30 A4.5 kVA
14 A14 A20 A24 / 14 A24 A35 / 20 A35 / 20 A3 kVA
9 A10 A15 A16 / 10 A16 A25 / 15 A25 / 15 A2 kVA
230220208 only127/220127 only
120 and/or
240
120/208
UPS
Model
12
302 Installing Models with External Bypass Switches
1. Mount the bypass switch within sight of the UPS. If you do not have a Best Power bypass switch, or if the
fuse box or panel is out of sight, you must install a separate disconnect switch next to the UPS.
2. Remove the six screws in the bypass switch front panel and remove the panel. Remove the foam packing
material that is inside the bypass switch. Then, remove knockouts in the bottom of the bypass switch for AC
Line Input, AC to UPS Input, AC from UPS Output, and AC to the UPS-protected equipment (loads).
3. Next, remove the top portion of the UPS cover.
To remove the top UPS cover, first pull the top front panel out slightly until it clicks once; the holes in the
right side of the panel can help you do this. Do not strain the ribbon cable behind this panel. If you need
to remove the panel completely, you can disconnect the ribbon cable, but the display will not operate until
you reconnect it. Remove the three screws on each side of the UPS and one screw on the top of the UPS
(toward the back). Then, lift the cover off the UPS. See Figure 7.
4. Remove the knockouts in the FERRUPS back panel for AC Input and AC Output.
5. Install the conduit adapters. AC Input and AC Output conductors must be run through separate conduit. UPS
output circuits shall be installed in dedicated conduit systems and not shared with other electrical circuits.
CAUTION
To prevent electrical shock or damage to your equipment, make sure the FERRUPS is OFF before you
remove the cover. The circuit breaker or disconnect switch must also be off at the AC input service panel.
Remove these
screws. Pull this panel forward until it
clicks once. DO NOT STRAIN
THE RIBBON CABLE BEHIND
THIS PANEL. If you need to
remove the panel,
disconnect the ribbon cable first.
The display will not operate with
the cable disconnected.
These panels are not
attached when you receive
the UPS. To attach them,
see the Startup section of
the
User Manual
.
Remove three
screws on this
side.
CAUTION
To prevent electrical shock or damage to your equipment, make sure the AC input is OFF at the service
panel and the bypass and AC Disconnect switches are OFF before you connect any wires to the bypass
switch terminal strip.
Figure 7
13
6.Find the terminal strip inside the bypass switch. Using the label on the back of the bypass switchs access
panel and the Installation Wiring Diagram for your UPS, make the terminal strip connections and tighten all
connections securely. Use copper wire that is the appropriate size for the current draw. See Figure 8 for a
sample label.
Figure 8
7.Find the proper output neutral-to-ground connection in Figure 13 on pages 18-19. At the UPS terminal strip,
connect the neutral-to-ground (neutral-to-earth) wire to the proper output terminal before making any other
connections to the UPS. The neutral-to-ground wire is a green and yellow wire labeled WIA-0424. One end
of this wire is already connected to ground (earth) on the UPS terminal strip.
8.Notice that there is a cable routed out of the left side of the bypass switch cabinet. The wires in this cable
must be connected to the UPS logic board to provide bypass status signals to the UPS. To connect the wires,
follow the steps below. If you plan to use the Emergency Power Off feature, see Appendix A.
a) Route the wires through the UPS grommet shown below and to connector J13 on the logic board.
b) Pull the 8-pin connector at J13 apart as shown. The portion you remove from the connector has 8 possible
connection points.
Grommet for
bypass switch
and EPO wires
Tie-wrap bypass
switch and EPO
wires here
Connect bypass
switch and EPO
wires to J13
DIN Rail
87
EPO
Inverter
Disable
(MBB -
Red and
Black
Wires)
Bypass
Status
(White
and
Black
Wires)
Not
Used
Loosen
these
screws.
Tighten
them
after making
connections.
654321
Figure 9
123 5 71111121213 1516
N
4
N
6 891010
N N L2L1L2 L2 L2L1 L1 L1
14
AC TO UPS
PROTECTED
LOADS AC FROM
UPS OUTPUT LINE AC INPUT AC TO
UPS INPUT
USE COPPER CONDUCTORS ONLY.
!LAB-1918
REFER TO WIRING DIAGRAMS IN THE INSTALLATION MANUAL.
Terminal
Strip
J13 Connector
14
c) Loosen the standard screws on the J13 connector as shown in Figure 9.
d) If your bypass switch is Make-Before-Break (MBB), connect the red and black pair of wires to the
terminals marked 3 and 4 in Figure 9, with the red wire going to 3 and the black wire going to 4.
e) For all external bypass switches, connect the white and black pair of wires to 5 and 6, with the white wire
going to 5 and the black wire going to 6.
Note:If you need to make a connection for an Emergency Power Off signal, complete the steps in
Appendix Abefore you go on.
f) Tighten the screws to secure the connections (torque specification is 2.61 inch-pounds/0.3 N-m), and
reattach the connector to J13 on the logic board.
g) Use the tie-wraps provided to secure the cable. See Figure 9.
9.Using the Installation Wiring Diagram (Figure 10, 11,or 12) for your UPS, make the UPS terminal strip
connections and complete the ACinstallation wiring. Read the notes with each diagram carefully. See
Figure 13for UPS terminations.
Make all connections exactly as shown on the Installation Wiring Diagram to make sure the phasing is
correct. Good ground connections are necessary to reduce electrical noise and make UPS and load operation
safe. Follow the grounding guidelines on the installation wiring diagram.
Torque for these connections should be 10.6-12.3 inch-pounds (1.2-1.4 Newton-meters).
10.If your UPS has one or more separate battery cabinets, go on to Section 400to install them. If not, go to
Section 500to set UPS parameters and perform the phase check.
15
NOTE 1:The customer must provide input overcurrent protection
as stated in NECSection 240-21 or local codes. Size the
protection device according to local code requirements. (See
Tables 9 and 10 on page 10.)
NOTE 2:The UPS bypass switch must be installed within sight of
the UPS. To properly install, complete the voltage and phase
check procedure in Section 500. The wires coming from the
side of the switch must be connected as described in step 8
on pages 13-14.
NOTE 3:The customer must provide and install this ground
(earth) connection per NEC Sections 250-5(d), 250-26, 250-91
and 250-92, or local code requirements. This grounding electrode
conductor must be at least #8 AWG (8.36 mm2) per NECtable
250-94. If the UPS input circuit conductors are larger than #8
AWG (8.36 mm2), Best Power requires the grounding electrode
conductor to be the same size (ampacity) as the largest UPS
input circuit conductor. See NEC Section 110-3(b). Conduit is not
considered an acceptable grounding electrode conductor. Best
Power does not recommend routing the grounding electrode
conductor through metallic conduit. This conductor may require
protection from physical damage according to local code
requirements.
NOTE 4:All AC circuit conductors, including the neutral and
equipment grounding conductors, must be the same size
(ampacity), have the same rating (75° C copper wire), and be
sized according to the input circuit breaker. The UPS input and
output conductors must be run through separate conduits.
NOTE 5:The customer must provide output overcurrent
protection. See NECSection 240-21 or local requirements. See
Table 12 on page 11 for maximum output overcurrent protection
device ratings.
NOTE 6:See Figure 13 for proper output wiring termination and
neutral-to-ground (neutral-to-earth) connection.
NOTE 7:For maximum protection against electrical noise, use
isolated ground receptacles. See NECSection 250-74, Exception
#4.
NOTE 8:See Section 102 for installation and service clearances
before installing the UPS. Use flexible conduit on the UPS or the
external battery cabinet if either must be moved.
NOTE 9:External UPS battery cabinets are optional. See
Section 400 for installation instructions.
NOTE 10:UPS output circuits shall be installed in dedicated
conduit systems and not shared with other electrical circuits.
NOTE 11:The load fuse or circuit breaker should be sized to
match the load current requirements. See Table 12.
!
BUILDING GROUNDING
ELECTRODE OR
PROTECTIVE EARTH
SYSTEM
NL1
NC
NC
AC LINE INPUT
AC TO
UPS INPUT
AC FROM
UPS OUTPUT
AC TO LOADS
Note 2
Note 3
Note 2
Note 1 Note 4 Note 4
Note 7
TO
LOADS
Note 5
Note 4 Note 10
Note 9
Note 10
Note 11
L1 N
N
N
L1
NL1
L1
L1
1010111112 131415
Note 8
Note 6
IG
2341
96785
Note 4
L1L1
L2/
NL2/
NX1X2X3X4X5X6
N NC
Figure 10: Installation Wiring Diagram for 2, 3, 4.5, 6, and 7.5 kVA FERRUPSModels
with External Bypass Switch (L - N)
• 120 input and 120 output • 127 input and 127 output (Break-Before-Make only)
• 220 input and 220 output (except Mexico) • 230 input and 230 output
• 240 input and 240 output
16
Figure 11: Installation Wiring Diagram for 2, 3, 4.5, 6, and 7.5 kVA FERRUPSModels
with External Bypass Switch (L1, L2, N)
• 208 Input, 120/240 Output • 208 Input, 208 or 240 Output
• 208 Input, 120/208 Output • 60 Hz 220 Input, 220 Output (Mexico)
• 120 or 240 Input, 120/240 Output
!
BUILDING GROUNDING
ELECTRODE OR
PROTECTIVE EARTH
SYSTEM
N L2L1
N N
N
AC LINE INPUT
AC TO
UPS INPUT
AC FROM
UPS OUTPUT
AC TO LOADS
Note 2
Note 3
Note 2
Note 1 Note 4 Note 4
Note 7
TO
LOADS
Note 5
Note 4 Note 10
L1L1
L2/
NL2/
NX1X2X3X4X5X6
Note 9
Note 10
Note 11
N
L2
L2 L2
L2
L2
L1
L1 L1
L1
L1
1011111212 131516
Note 8
Note 6
IG
2341
9 6785
Note 4
NOTE 1:The customer must provide input overcurrent protection
as stated in NECSection 240-21 or local codes. Size the
protection device according to local code requirements. (See
Tables 9 and 10 on page 10.)
NOTE 2:The UPS bypass switch must be installed within sight of
the UPS. To properly install, complete the voltage and phase
check procedure in Section 500. The wires coming from the
side of the switch must be connected as described in step 8
on pages 13-14.
NOTE 3:The customer must provide and install this ground
(earth) connection per NEC Sections 250-5(d), 250-26, 250-91
and 250-92, or local code requirements. This grounding electrode
conductor must be at least #8 AWG (8.36 mm2) per NECtable
250-94. If the UPS input circuit conductors are larger than #8
AWG (8.36 mm2), Best Power requires the grounding electrode
conductor to be the same size (ampacity) as the largest UPS
input circuit conductor. See NEC Section 110-3(b). Conduit is not
considered an acceptable grounding electrode conductor. Best
Power does not recommend routing the grounding electrode
conductor through metallic conduit. This conductor may require
protection from physical damage according to local code
requirements.
NOTE 4:All AC circuit conductors, including the neutral and
equipment grounding conductors, must be the same size
(ampacity), have the same rating (75° C copper wire), and be
sized according to the input circuit breaker. The UPS input and
output conductors must be run through separate conduits.
NOTE 5:The customer must provide output overcurrent
protection. See NECSection 240-21 or local requirements. See
Table 12 on page 11 for maximum output overcurrent protection
device ratings.
NOTE 6:See Figure 13 for proper output wiring termination and
neutral-to-ground (neutral-to-earth) connection.
NOTE 7:For maximum protection against electrical noise, use
isolated ground receptacles. See NECSection 250-74, Exception
#4.
NOTE 8:See Section 102 for installation and service clearances
before installing the UPS. Use flexible conduit on the UPS or the
external battery cabinet if either must be moved.
NOTE 9:External UPS battery cabinets are optional. See
Section 400 for installation instructions.
NOTE 10:UPS output circuits shall be installed in dedicated
conduit systems and not shared with other electrical circuits.
NOTE 11:The load fuse or circuit breaker should be sized to
match the load current requirements. See Table 12.
17
Figure 12: Installation Wiring Diagram for 2, 3, 4.5, 6, and 7.5 kVA FERRUPSModels
with External Bypass Switch (L1, L2, N)
60 Hz 208 or 480 VAC Source with Input Step-Up or Step-Down Isolation Transformer
240 UPS Input - 120/240 UPS Output
!
N N
N
AC LINE INPUT
AC TO
UPS INPUT
AC FROM
UPS OUTPUT
AC TO LOADS
Note 2 Note 4
Note 7
TO
LOADS
Note 5
Note 4 Note 11
Note 9
Note 11
Note 12
N
L2
L2 L2
L2
L2
L1
L1 L1
L1
L1
1011111212 131516
Note 8
Note 6
IG
23416785
Note 4
Note 1
BUILDING GROUNDING
ELECTRODE OR
PROTECTIVE EARTH
SYSTEM
N
Note 3
Note 4
Note 2
Note 10
L1L2
9
L1L1
L2/
NL2/
NX1X2X3X4X5X6
NOTE 1:The customer must provide input overcurrent protection
as stated in NECSection 240-21 or local codes. Size the
protection device according to local code requirements. (See
Tables 9 and 10 on page 10.)
NOTE 2:The UPS bypass switch must be installed within sight of
the UPS. To properly install, complete the voltage and phase
check procedure in Section 500. The wires coming from the
side of the switch must be connected as described in step 8
on pages 13-14.
NOTE 3:The customer must provide and install this ground
(earth) connection per NEC Sections 250-5(d), 250-26, 250-91
and 250-92, or local code requirements. This grounding electrode
conductor must be at least #8 AWG (8.36 mm2) per NECtable
250-94. If the UPS input circuit conductors are larger than #8
AWG (8.36 mm2), Best Power requires the grounding electrode
conductor to be the same size (ampacity) as the largest UPS
input circuit conductor. See NEC Section 110-3(b). Conduit is not
considered an acceptable grounding electrode conductor. Best
Power does not recommend routing the grounding electrode
conductor through metallic conduit. This conductor may require
protection from physical damage according to local code
requirements.
NOTE 4:All AC circuit conductors, including the neutral and
equipment grounding conductors, must be the same size
(ampacity), have the same rating (75° C copper wire), and be
sized according to the input circuit breaker. The UPS input and
output conductors must be run through separate conduits.
NOTE 5:The customer must provide output overcurrent
protection. See NECSection 240-21 or local requirements. See
Table 12 on page 11 for maximum output overcurrent protection
device ratings.
NOTE 6:See Figure 13 for proper output wiring termination and
neutral-to-ground (neutral-to-earth) connection.
NOTE 7:For maximum protection against electrical noise, use
isolated ground receptacles. See NECSection 250-74, Exception
#4.
NOTE 8:See Section 102 for installation and service clearances
before installing the UPS. Use flexible conduit on the UPS or the
external battery cabinet if either must be moved.
NOTE 9:External UPS battery cabinets are optional. See
Section 400 for installation instructions.
NOTE 10:For 208 VAC, use a step-up transformer. For 480
VAC, use a step-down transformer. Use an isolation transformer
with a 120/240 grounded center-tapped neutral output.
Do not
use a buck/boost transformer.
NOTE 11:UPS output circuits shall be installed in dedicated
conduit systems and not shared with other electrical circuits.
NOTE 12:The load fuse or circuit breaker should be sized to
match the load current requirements. See Table 12.
18
!
L1
60 Hz
127 Out or 220 Out (Mexico)
NL2
L2
See Notes 1, 2.
CAUTION
CAUTION
254
127
220
Parameter 4 8 set to 254*
13C
!
L1
50 or 60 Hz
208 or 120/208Out
L2
See Notes 1, 2.
CAUTION
208
Parameter 4 8 set to 208*
13B
!
L1
50 or 60 Hz
220 Out
L2
See Notes 1, 2.
CAUTION
220
Parameter 4 8 set to 220*
13D
!
L1
50 or 60 Hz
120/240 Out
X2
NN
X4
L2
N-G BOND
GREEN/YELLOW
See Notes 1, 2.
Do not connect 120V loads
between X3 and X6.
CAUTION
240
120
Parameter 4 8 set to 240*
13A
X1 X3 X5 X6 X2 X4X1 X3 X5 X6
N-G BOND
GREEN/YELLOW
X2 X4X1 X3 X5 X6
N-G BOND
GREEN/YELLOW
X2 X4X1 X3 X5 X6
N-G BOND
GREEN/YELLOW
!
L1
50 or 60 Hz
220 Out
N
N-G BOND
GREEN/YELLOW
220 VOLTS L-N
See Notes 1, 2.
CAUTION
220
Parameter 4 8 set to 220*
13F
!
L1
50 or 60 Hz
230 Out
L2
See Notes 1, 2.
CAUTION
230
Parameter 4 8 set to 230*
13E
X2 X4X1 X3 X5 X6 X2 X4X1 X3 X5 X6
N-G BOND
GREEN/YELLOW
120
Figure 13: UPS Output Wiring Connections
Find the output wiring configuration (Figure 13A - 13H) for your UPS input voltage and frequency and
UPS output voltage(s). Make the neutral-to-ground (neutral-to-earth) connection first. Then, wire the
output from the UPS as shown. In Section 500, you will set parameter 4 8 to the correct output voltage.
19
!
L1
50 or 60 Hz
240 Out
N
N-G BOND
GREEN/YELLOW
240 VOLTS L-N
See Notes 1, 2.
CAUTION
240
Parameter 4 8 set to 240*
13H
!
L1
50 or 60 Hz
230 Out
N
N-G BOND
GREEN/YELLOW
230 VOLTS L-N
See Notes 1, 2.
CAUTION
230
Parameter 4 8 set to 230*
13G
X2 X4
X1 X3 X5 X6 X2 X4X1 X3 X5 X6
Notes for Figures 13A-13H
NOTE 1: Connect the UPS’ green and yellow neutral-to-ground (neutral-to-earth) wire (N-G bond) to the UPS output
terminal indicated.
NOTE 2: See Table 12 on page 11 for maximum output overcurrent device ratings.
See Section 500 to set the Output Voltage Reference parameter.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33

Ferrups 0800-7500 Installation guide

Category
Uninterruptible power supplies (UPSs)
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI