Danfoss ECL Comfort 300 - C47 Operating instructions

Type
Operating instructions
ECL COMFORT
ECL Comfort
Users Guide
C47
This guide is associated to ECL Card 087B4821
Installer:
By:
Date:
ECL COMFORT
ECL Comfort
Installation and
Maintenance
Mixing and hot-water controller
C47
VI.7C.Q1.02
2002.03
Your personal week plan:
Heating 0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
Hot Water
0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
The factory setting is indicated in grey.
823-
5 - 8 18 - 22
6-8 16 - 22
823-
Table of Contents
Daily use
Section
1 Choose favourite display
2 Select controller mode
3 Adjust room and hot water charging temperature
4 Set personal daily plan
5 Advantages of the ECL Card
6 Hot points
7 Definitions
Installation and maintenance. Grey sections 10 and
onwards. Turn the guide over.
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Daily use, turn the guide over sections 01 - 07
1 Choose favourite display
2 Select controller mode
3 Adjust room and hot water charging temperature
4 Set personal day plan
5 Advantages of the ECL Card
6 Hot points
7 Definitions
Table of Contents
Sections of the Installers part of this guide
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Before you start
Installation
10 Identifying the system type
11 Mounting the ECL Comfort controller
12 Electrical connections 230 V a.c.
13 Electrical connections 24 V a.c.
14 Placing and mounting the temperature sensors
15 Inserting the ECL Card
Basic Set-up
16 Adjusting the ECL Card settings
17 Setting the time and date - Line A
18 Monitoring temperatures and system units - Line B
19 Manual control - Line B
20 Setting the heat curve - Line C
21 Heating cut-out - Line 1
22 Flow temperature limits - Line 2
23 Room temperature influence - Line 3
24 Setting the PI-regulation - Line 4 - 7
25 Hot water cut-in and cut-out - Line 1 and 2
27 Setting the PI-regulation - Line 4 - 7
Control & Overviews
29 Check list
30 ECL Card settings
31 Service parameters
Extended Service
32 Adjusting the service parameters
Miscellaneous
34 Copying with the ECL Card
Note:
The functions can only be realized as of ECL Card CI08 and
controller version V1.08.
The shown diagram is a fundamental and simplified
example and does not contain all components that are
necessary in heating systems.
If the system you are about to install is different than the
shown diagram of a standard heating system, feel free to
sketch an outline for comparison. Adaptation of heating
systems, See section 10.
List of components:
ECL Comfort 300
S1 Outdoor temperature sensor
S2 Flow temperature sensor - heating
S3 Return temperature sensor - heating
S4 Heating temperature sensor - hot water
S5 Lower tank sensor or return temperature, hot water
S6 Upper tank sensor
P1 Circulation pump - heating
P2 Charging pump - hot water
P3 Circulation pump - hot water
M1 Motorized valve - heating
M2 Motorized valve - hot water
Installation & maintenance
The ECL Card, grey side
for installation and maintenance.
Lines A to C, and lines 1 to
7 for basic settings, see overview
section 30.
Extended service parameters,
see section 31
The ECL Card: Installer’s
instruction
The grey side of the card must face
you when you change settings. For
daily use and during start-up the
yellow side of the card must face you.
Circuit indicator
Circuit
selector
Shift
button
Adjustment Controller
mode
The circuit indicator shows the selected circuit.
The ECL Card
For daily use and your personal adjustments the yellow side
of the ECL Card must be facing you.
The display
Each line, A, B, C, 1, 2 etc. of the ECL Card has its own
display. See section 1.
Controller mode
Manual operation (Used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
Room
temperature /
hot water
System
information
Actual dayplan /
day plan of
circulation pum
Day plans
A
B
C
1
2
3
4
5
6
7
Hot water - circuit IIHeating - circuit I
Line indicator
Circuit
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
8
9
10
199
6
1
2
3
4
6
1
2
3
6
1
1
ON
2
035
B
3
ON
2
ON
0
0 3 6 9 12 15 18 21 24
1
70
5
C
3
6
0 3 6 9 12 15
0
5
0
8
0 3 6 9 12 15 18 21 24
0
7
0
5
1
1
ON
2
036
B
3
ON
2
ON
8
0 3 6 9 12 15 18 21 24
1
913
5
-
C
3
8
0 3 6 9 12 15 18 21 24
0
7
0
4
6
0 3 6 9 12 15
0
5
0
913
20
8
A
07
6
A
5
VI.7C.Q1.02
2002.03
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller series is designed by Danfoss
for temperature control of heating, hot-water and cooling
systems.
The ECL Comfort controller ensures you of the following;
Room, hot-water, or cooling temperatures will be
adjusted to your personal settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
Sketch your application
The ECL Comfort controller series is designed for a wide
range of heating, hot-water, and cooling systems with
different configurations and capacities.
If your system differs from the diagrams shown in section
10, you may want to make a sketch of the system about to
be installed. This makes it easier to use the Installer’s
Guide, which will guide you step-by-step from installation to
final adjustments before the end-user takes over.
Note!
The controller is pre-programmed with factory settings that
are shown in the relevant sections of this guide.
However, you might come across some settings that are not
listed in this instruction. These settings could be related either
to recent updates or the use of optional modules (which are
described in the instructions in question).
How to use this guide
This guide is divided into two parts:
Daily Use (turn the guide over)
Yellow sections 1-7
Installation and Maintenance:
Grey sections 10 and onwards
Before you start
Installation
Note:
System diagrams in this instruction are principal drawings
and do not contain all components which are necessary in
heating systems.
10b
Heating system type 3
Indirectly connected heating system and primarily
connected direct storage tank with built-in heating coil.
Heating system type 2a
Indirectly connected heating system and primarily
connected heat exchanger for hot-water charging system
with circulation through the tank.
Line 52-II Closed valve/controlled
circulation temperature
Setting
OFF
Line 84-II Pump P2 in precontrolled circuit
Setting
OFF
Line 52-II Closed valve/controlled
circulation temperature
Setting
ON
Line 84-II Pump P2 in precontrolled circuit
Setting
OFF
Installation
Heating system type 2
Indirectly connected heating system and primarily
connected heat exchanger for hot-water charging system
with circulation through the tank.
Heating system type 1
Indirectly connected heating system with mixing loop and
secondarily connected storage tank with built-in heating
coil.
Line 17-I Temperature reference feedback
Setting
3
Line 52-II Closed valve/controlled
circulation temperature
Setting
ON
Line 83-II Controller use as independent controller,
master or slave controller
Setting
4
Line 84-II Pump P2 in precontrolled circuit
Setting
OFF
Line 140-II Sensor S5 = lower hot-water sensor/
return temperature sensor in circuit II
Setting
OFF
Line 52-II Closed valve/controlled
circulation temperature
Setting
ON
Line 84-II Pump P2 in precontrolled circuit
Setting
OFF
Note:
The systems can only be realized with the ECL Card version
CI08 and controller version 1.08.
Identifying the system type
10a
The ECL Comfort controller is a universal controller that
can be used for various systems. Based on the shown
standard systems, it is possible to configure additional
systems.
In this section you find the most frequently used systems. If
your system is not quite as shown below, find the diagram
which has the best resemblance with your system and
make your own combinations.
Installation
Heating system type 6
Indirectly connected heating system and primarily con-
nected precontrolled heat exchanger for hot-water charging
system with circulation through the tank.
Heating system type 6a
Indirectly connected heating system and primarily
connected precontrolled heat exchanger for hot-water
charging system with circulation through the heat
exchanger.
10d
Line 52-II Closed valve/controlled
circulation temperature
Setting
ON
Line 84-II Pump P2 in precontrolled circuit
Setting
OFF
Line 52-II Closed valve/controlled
circulation temperature
Setting
OFF
Line 84-II Pump P2 in precontrolled circuit
Setting
ON
Note:
System diagrams in this instruction are principal drawings
and do not contain all components which are necessary in
heating systems.
10c
Heating system type 4
Indirectly connected heating system with mixing loop and
secondarily connected hot-water charging system.
Heating system type 5
Indirectly connected heating system and secondarily
connected hot-water charging system with mixing loop.
Note:
The following heating system type can only be applied with
the relais module ECA 80.
Installation
Line 17-I Temperature reference feedback
Setting
3
Line 52-II Closed valve/controlled
circulation temperature
Setting
ON
Line 83-II Controller use as independent controller,
Master or slave controller
Setting
4
Line 84-II Pump P2 in precontrolled circuit
Setting
OFF
Line 140-II Sensor S5 = lower hot-water sensor/
return temperature sensor in circuit II
Setting
OFF
Line 17-I Temperature reference feedback
Setting
3
Line 43-I Parallelbetrieb/Parallelbetrieb mit
reduziertem Heizbetrieb
Setting
OFF
Line 52-II Closed valve/controlled
circulation temperaturer
Setting
ON
Line 83-II Controller use as independent controller,
master or slave controller
Setting
2
Line 84-II Pump P2 in precontrolled circuit
Setting
OFF
Line 140-II Sensor S5 = lower hot-water sensor/
return temperature sensor in circuit II
Setting
OFF
Installation
11b11b
Installation
Mounting the ECL Comfort
controller
11a
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull
off the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Installation
Wire cross section: 0.75 - 1.5 mm
2
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted into each screw
terminal.
Note:
Incorrect connection can damage the TRIAC outputs. Max. load
(terminal 3, 4, 6 and 7) 0.2 A/230 V a.c.!
Option:
Relay module ECA 80 (contacts: max. load 4(2)A/230 V a.c.)
25 (R4) Alarm relay output
28 (R5) Control of the hot-water charging pump in heating
system types 4, 5, 6 and 6a.
12b
Terminal Description Max. load
1 (L) Voltage supply
230 V a.c.
2 (N) Voltage supply
230 V a.c.
3 (M1) Gear motor
- open/circuit I 0.2 A / 230 V a.c.
4 (M1) Gear motor
- close/circuitI
alternative: ABV thermo
actuator 0.2 A / 230 V a.c.
5 230 V a.c. voltage supply
for motor output, circuit I
6 (M2) Gear motor
- open/circuit II 0.2 A / 230 V a.c.
7 (M2) Gear motor
- close/circuit II
alternative: ABV thermo
actuator 0.2 A / 230 V.a.c.
8 230 V a.c. voltage supply
for motor output, circuit II
9 (P1) Circulation pump for heating
circuit I 4(2) A / 230 V a.c.
10 230 V a.c. voltage supply
for pump relay R1
11 (P2) Hot-water charging pump
for hot-water circuit II 4(2) A / 230 V a.c.
12 230 V a.c. voltage supply
for pump relay R2
13 (P3) Circulation pump
for hot-water circuit II 4(2) A / 230 V a.c.
14 230 V a.c. voltage supply
for pump relay R3
Installation
12a
Electrical connections
230 V a.c.
230 V a.c. connections - without safety thermostat
Establish these jumpers:
1 to 5, 5 to 8, 8 to 10, 10 to 12, 12 to 14, and
2 to common N-terminal.
If an ECA 80 module is applied, the jumpers 14 to 26,
26 to 29 must be established additionally.
Establish these jumpers:
1 to 10, 10 to 12, 12 to 14
Safety thermostat:
4, 5 and 10/7, 8 and 10 with ST- (safety thermostat )
and 2 to common N-terminal.
If an ECA 80 module is applied, the jumpers 14 to 26,
26 to 29 must be established additionally.
230 V a.c. connections - with safety thermostat
This circuit diagram is only valid
if Danfoss actuators are used
Optional
Optional
Installation
13b
Terminal Description Max. load
1 (L) Voltage supply 24 V a.c.
2 (N) Voltage supply 24 V a.c.
3 (M1) Gear motor
- open/circuit II 1.0 A / 24 V a.c.
4 (M1) Gear motor
- close/circuit I
alternative: ABV thermo
actuator 1.0 A / 24 V a.c.
5 24 V a.c. voltage supply
for motor output, circuit I
6 (M2) Gear motor
- open/circuit II 1.0 A / 24 V a.c.
7 (M2) Gear motor
- close/circuit II
alternative: ABV thermo
actuator 1.0 A / 24 V a.c.
8 24 V a.c. voltage supply
for motor output/circuit II
9 (P1) Circulation pump
for heating circuit I 4(2) A / 24 V a.c.
10 24 V a.c. voltage supply
for pump relay R1
11 (P2) Hot-water charging pump
for hot-water circuit II 4(2) A / 24 V a.c.
12 24 V a.c. voltage supply
for pump relay R2
13 (P3) Circulation pump
for hot-water circuit II 4(2) A / 24 V a.c.
14 24 V a.c. voltage supply
for pump relay R3
Wire cross section: 0.75 - 1.5 mm
2
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted into each screw
terminal.
Note:
Incorrect connection can damage the TRIAC outputs. Max. load
(terminal 3, 4, 6 and 7) 1 A/24 V a.c.!
Option:
Relay module ECA 80 (Contacts: max. load 4(2)A/230 V a.c.)
25 (R4) Alarm relay output
28 (R5) Control of the hot-water charging pump in heating
system types 4, 5, 6 and 6a.
Installation
13a
Electrical connections
24 V a.c.
Establish these jumpers:
1 to 5, 5 to 8, 8 to 10, 10 to 12, 12 to 14,
2 to common N-terminal.
If an ECA 80 module is applied, the jumpers 14 to 26, and
26 to 29 must be established additionally.
24 V a.c. connections - with safety thermostat
Establish these jumpers:
1 to 10, 10 to 12, 12 to 14
Safety thermostat:
4, 5 and 10/7, 8 and 10 with ST- (safety thermostat),
2 to common N-terminal.
If an ECA 80 module is applied, the jumpers 14 to 26, and
26 to 29 must be established additionally.
24 V a.c. connections - without safety thermostat
This circuit diagram is only valid
if Danfoss actuators are used
Optional
Optional
Installation
14b
Note!
Valid for ESM-11: Do not move the sensor after it has been
fastened in order to avoid damage to the sensor element.
Installation
14a
Connecting and placing
the temperature sensors
Establish the jumper from 16 to common terminal.
Wire cross section for sensor connections:
Min. 0.4 mm
2
Total cable length: Max. 125 m (all sensors incl. system
device bus).
Note:
Cable lengths of more than 125 m may cause noise
sensibillity (EMC).
Connecting the temperature sensors and the bus
Terminal Description Type (recomm.)
15 and 16 System device bus
Connections for room
panel/remote control/ ECA 60
(relay module)*
ECA 61/(ECA 80)
17 and 16 S1 Outdoor temp. sensor ESM-10
18 and 16 S2 Flow temp. sensor ESMU/ESM-11/
circuit I ESMC
19 and 16 S3 Return temp. sensor ESMU/ESM-11/
circuit I ESMC
20 and 16 S4 Flow temp. sensor ESMU/ESM-11/
circuit II ESMC
21 and 16 S5 Return temp. sensor ESMU/ESM-11/
circuit II or ESMC
lower hot-water tank ESMB
temp.sensor circuit II
22 and 16 S6 Upper hot-water tank ESMU/ESMB
temp. sensor
* The system device bus/room panel/remote control is only active
when the outdoor temperature sensor is connected.
It is important that the sensors are mounted in the correct
position in your system.
The temperature sensor mentioned below are sensors
used for the ECL Comfort 200 and 300 series which not all
will be needed for your application.
Outdoor temperature sensor (ESM-10)
The outdoor sensor should be mounted on that side of the
building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors, windows
or air outlets.
Flow temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends that
the ESMU type to be inserted into the exchanger flow
outlet.
Make sure that the surface of the pipe is clean where the
sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return sensor should always be placed in / on a pipe
with return water flow.
Room panel ECA 60 or remote control ECA 61
Do not place it on outside walls or close to radiators,
windows or doors.
Hot-water temperature sensor (ESMU or ESMB)
Place the hot water sensor according to the
manufacturers specification.
Boiler sensor (ESMU, ESM-11 or ESMC)
Place the sensor according to the boiler manufacturer’s
specification.
Flow/air duct temperature sensor
Place the sensor close to the exchanger.
Installation
Understanding the ECL Card
The ECL Card contains factory settings for a standard
heating system. If the actual heating system differs from
the standard system, the controller must be adjusted
accordingly. After the adjustment, the new settings
should be stored on the ECL Card.
For ECL Card copying and daily use including
adjustment of temperatures and time periods, insert the
ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the ECL
Card - the installer’s side - must be facing you.
As a main rule, the ECL Card should always remain in
the controller during service, maintenance and settings.
If the card is removed please note that:
The controller settings are locked after approx. 10
min.
The ECL Card must not be exposed to direct heat or
sunshine
If several controllers are installed in the heating system
you can write a title on the ECL Card with a permanent
ink pen.
15b
Installation
C
C99
Y
0
P
C73
08 108
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
15a
Inserting the ECL Card
How to insert your ECL Card the first time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the ECL Card data.
The controller immediately starts to copy the factory
settings and heating system type from the ECL Card. After
copying, the display will show the heating system type the
controller is set to control. After approx. 10 sec. the display
will change to display line C.
The controller is now ready to be set to control your
heating system.
Software ver-
sion,
ECL Card
Line
Circuit
Time
Outdoor
temperature
Desired
room
temperature
Application type
Software ver-
sion, controller
Note:
The shown displays are examples that may not correspond
with your application type and software versions.
Basic set-up
The grey
side of the
ECL Card
02
01
2220
5
A
3
1
17
Setting the time and date -
Line A
In case of a power failure, which lasts longer than 12 hours,
the time and the date have to be set again.
All other settings are stored as programmed.
Go to line A.
Use the shift button to switch between minutes,
hours, year, month and day
Set the correct time and date
Use the yellow side of the ECL Card to enter the day
plan settings.
See User’s Guide, section 4.
Actual time
Month, day
Year
Basic set-up
0
1
1
ON
2
094
2
3
ON
2
ON
16
Adjusting the ECL Card
settings
Update of the ECL Card after maintenance and service
All new settings can be stored on the ECL Card. For details
about copying, see section 34.
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings on the
grey side of the ECL Card (see the example below).
Use the arrow buttons to move from line to line
of the ECL Card, for example line 2:
Settings to
be adjusted
Value in range
indicator
Use the minus/plus buttons to adjust the
settings.
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the options.
The circuit selector shifts between circuit I
and II. You can adjust all settings and service
parameters individually in both circuits, ie.
circuit II.
Circuit
Line
indicator
The gear motor
opens or closes
the valve as long as the the relevant button is
pressed.
The thermo actuator
opens (NC) or closes (NO)
the valve as long as the button is pressed.
NO - normally open
NC - normally closed
This operation applies to both circuits.
19
Manual control - Line B
Basic set-up
Go to line B.
Shift to manual mode
5
1 2
036
B
3
ON
1
ON
2
ON
Controlled
units
Controller mode
Note!
During manual operation, all control functions are deactivated.
Check the activation direction of the motorized valve either
by looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
Select the unit you want to control. The selected
unit symbol will flash.
Controlled units are switched OFF or
ON when the relevant button is pressed.
1
Basic set-up
5
1 2
036
B
3
ON
1
ON
2
ON
The grey
side of the
ECL Card
The grey
side of the
ECL Card
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Monitoring temperatures
and system units - Line B
18
Go to line B.
Note!
This display also shows actual and reference values of flow
and return temperature during hot-water charging.
The activity of the motorized valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display
will indicate it as “- -”.
If the sensor is short-circuited, the display will indicate it as
- - - “.
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Push the shift button to see:
- the calculated flow temperature
- the return temperature set points
Relationship between temperature and ohmic value
Temperature
Ohm
Controlled units
State indicator
Return temperature
Flow temperature
-50 °C 808 Ohm
-40 °C 846 Ohm
-30 °C 884 Ohm
-20 °C 921 Ohm
-10 °C 961 Ohm
0 °C 1000 Ohm
10 °C 1039 Ohm
20 °C 1078 Ohm
30 °C 1117 Ohm
40 °C 1155 Ohm
50 °C 1194 Ohm
60 °C 1232 Ohm
70 °C 1271 Ohm
80
o
C 1309 Ohm
90
o
C 1347 Ohm
100
o
C 1385 Ohm
110
o
C 1423 Ohm
120 °C 1462 Ohm
130 °C 1501 Ohm
140 °C 1539 Ohm
150 °C 1578 Ohm
1
ON
1
1
1
1 2
04
C
55
3
ON
1
ON
2
ON
Choose circuit II.
Lower tank sensor
(actual temperature), if
ON is chosen in line
140
Upper
tank
sensor
(actual
temperature)
Floor heating systems
This controller is factory set for radiator systems, which are
typically high flow temperature systems.
To control floor heating systems, which are typically low flow
temperature systems, you need to change the heat curve
according to your type of system.
Basic set-up
20b
Parallel displacement
Circuit Setting range Typical setting
I -9... +9 0
Slope
Circuit Setting range Typical setting
I 0.2 ... 3.4 1.0
The grey
side of the
ECL Card
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
1.0
1.4
0.6
0.2
1.8 2.2 3.0 3.4
100
110
2.6
o
C
o
C
Setting the heat curve/
storage temperature
- Line C
20a
Go to line C.
The symbol for the slope of the heat curve will
flash.
Make your adjustments.
1 2
8
C
1
0
3
ON
1
ON
2
ON
Slope
Displacement
Adjust the slope of the heat curve, if required
(see diagram on the right page).
Basic set-up
Slope
Circuit Setting range Factory setting
I 0.2 ... 3.4 1.8
Parallel displacement
Circuit Setting range Factory setting
I -9... +9 0
The grey
side of the
ECL Card
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will flash.
Whether it is reasonable to change the slope or parallel
displacement will depend on the individual heat requirement.
If the requested heating temperature can only be reached in
the long run by a noticable parallel displacement (+) of the
set slope, the slope should be changed.
Small increases or reductions in heating temperature can be
implemented by means of the parallel displacement.
0
1
1
ON
2
094
2
3
ON
2
ON
Flow temperature limits -
Line 2
22
The left end of the setting range flashes.
Adjust the min. limit of your heating system.
Select the max. limit. The right end of the setting
range flashes. The max. limit flashes in the
setting range.
Adjust the max. limit.
Basic set-up
Max. flow
temperature
Min. flow
temper-
ature
Setting range
2 Flow temperature min., max. limits
Circuit Setting range Factory setting
I 10 ... 110 °C min. 40 °C max. 90 °C
The grey
side of the
ECL Card
Go to line 2.
1 2
8
1
1
3
ON
1
ON
2
ON
Heating cut-out - Line 1
21
Set the outdoor temperature limit at which you
want the heating system to stop.
The valve closes and after about 3 min. the
heating pump stops.
The limitations set in line 22 will be ignored.
Go to line 1.
Basic set-up
The heating system switches on again when the outdoor
temperature and the accumulated temperature become lower
than the set temperature.
18 ˚C
Temperature
Actual outdoor
temperature
Accumulated outdoor
temperature
Time
Heating
Heating off
Heating
1 Limit for heating cut-out
Circuit Setting range Factory setting
I 10 ... 30 °C 18 °C
The grey
side of the
ECL Card
ON
OFF
Basic set-up
The room sensor in the reference room
registers the difference between the desired
and the actual room temperature. The flow
temperature reference will be corrected to
eliminate this difference.
B: Reference room control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as
a temperature reference for the rest of the rooms.
(However, should you have a few radiator thermostats
installed, make sure that they are fully open).
Set a positive value for min. influence and a
negative value for max. influence.
Example 1
The actual room temperature is 2
o
C too low.
The influence at max. limitation (right corner of the display) is
set to
-20.
The influence at min. limitation (left corner of the display) is
set to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x 20 x 1.8 x 0.1= 7.2
o
C
Example 2
The actual room temperature is 2
o
C too high.
The influence at max. limitation (right corner of the display) is
set to
-35.
The influence at min. limitation (left corner of the display) is
set to 35.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x (-35) x 1.8 x 0.1= -12.6
o
C.
23b
The grey
side of the
ECL Card
+
_
Influence
Min. limitation
Max. limitation
Below room Above room
temperature temperature
0
o
C
Desired room
temperature
Room temperature
influence - Line 3
23a
Basic set-up
1
2
ON
0-4
0
3
1
ON
3
ON
Note!
This section is only relevant if you have installed a room
sensor or ECA 60/61. There are two basic principles for
control of the room temperature influence:
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a
max. limitation of the room temperature. The controller will
allow for free heat gains, i.e. solar radiation or heat from a
fire place, etc.
The max. influence determines how much the
room temperature should influence the flow
temperature.
Go to line 3.
The bar below the min. value flashes.
Adjust the min. influence.
Select the max. influence.
The bar below the max. value flashes.
Adjust the max. influence.
Min.
influence
Max.
influence
Example
The actual room temperature is 2
o
C too high.
The influence at max. limitation (right corner of the display) is
set to
-40.
The influence at min. limitation (left corner of the display) is
set to 0.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x
-40 x 1.8 x 0.1= -14.4
o
C.
3 Room temperature influence
Circuit Setting range Factory setting
I 0 ... 99/-99 ... 0 min. 0 max. -40
The grey
side of the
ECL Card
+
_
Above room
temperature
Desired room
temperature
Influence
Max. limitation
0
o
C
24b
Basic set-up
If you want to tune the PI-regulation precisely, you can
use the following method:
Set the integration time (line 5) to its max. value (999 sec.).
Decrease the value for the proportional band (Line 4) until
the system starts hunting with a constant amplitude (it might
be necessary to force the system by setting an extreme
value).
Find the critical time period on the temperature recording or
use a stop watch.
This time period will be characteristic for the system, and you
can evaluate the settings from this critical period.
Integration time = 0.85 x critical time period
Proportional band = 2.2 x proportional band value in the
critical time period.
If the regulation seems to be too slow, you can decrease the
proportional band value by 10%.
Note!
Make sure there is a consumption when you set the
parameters.
How to calculate the running time of the motorized valve
The running time of the motorized valve is calculated using the
following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec/mm)
Example: 5.0 mm x 15 sec/mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec/degr.)
Example: 90 degrees x 2 = 180 sec.
VS2 15 3.0 AMV 100 90 250
VS2 15...25, VM2 15...25, AMV(E)
VB2 15...20 5.0 10, 20 15 75
VS2 15...25, VM2 15...25,
VB2 15...20 5.0 AMV(E) 30 3 15
VM2 32, VB2 25 7.0 AMV(E) 20 15 105
VM2 32, VB2 25 7.0 AMV(E) 30 3 21
Valve type Valve Actuator Actuator Running
stroke type speed time
(mm) (sec./mm) (sec.)
The grey
side of the
ECL Card
Time
Temp.
Critical time period
1
1
ON
2
0
4
8
3
ON
2
ON
24a
Setting the PI-regulation -
Line 4-7 (heating)
Go to line 4.
Setting to be adjusted
Line
indicator
Set the proportional band.
A higher value will result in a stable, but slow
regulation of the flow temperature.
Go to line 5.
Set a high integration time constant to obtain a
slow but stable reaction to deviations.
A small integration constant will make the
controller react fast but with less stability.
Go to line 6.
Set the running time of the motorized valve
according to the example on the opposite page.
This is the time it takes the valve to move from
closed to fully open position.
Go to line 7.
Set the neutral zone to a high value if you can
accept a high variation in flow temperature.
When the actual flow temperature is within the
neutral zone, the controller does not activate the
motorized valve.
Basic set-up
4 Proportional band
Circuit Setting range Factory setting
I 1 ... 250 K 80 K
5 Integration time constant
Circuit Setting range Factory setting
I 5 ... 999 sec. 30 sec.
6 Running time of the motorized valve
Circuit Setting range Factory setting
I 5 ... 250 sec. 35 sec.
7 Neutral zone
Circuit Setting range Factory setting
I 0 ... 9 K 3 K
The grey
side of the
ECL Card
Note!
The neutral zone is symmetrical around the flow reference
value.
Basic set-up
One sensor (S6)
Two sensors (S5 + S6)
Note:
If only one sensor (S6) is mounted, it will register the cut-
out temperature as well as the cut-in temperature.
Example - cut-in/cut-out difference:
Line 2 - Line1 = 20 K - 15 K = 5 K
--------------------------------------
---------------------------------------
Temperature
Cut-out difference - Line 1
Cut-in difference - Line 2
P2
Cut-in
Cut-out
Charging
temperature
(desired)
Time
S6
S5
OFF OFFON
--------------------------------
--------------------------------------
--------------------------------
Temperature
Cut-out difference - line 1
Cut-in difference - line 2
Cut-in
Cut-out
Charging
temperature
(desired)
Time
S6
ON ONOFF
P2
25b
The grey
side of the
ECL Card
Basic set-up
Cut-in and cut-out
temperature at hot-water
charging, line 1 and 2
25a
The hot-water charging temperature can be switched on
and off by one or two storage tank sensors. The controller
will automatically register the number of sensors.
Select circuit II.
Go to line 1.
Example:
Charging temperature 60 °C
Cut-out difference 15 K
Calculated temperature at which
the hot-water charging is switched off
(temperature at the lower tank sensor)
(60-15=) 45 °C
Set the difference.
Set the difference.
Example:
Charging temperature 60 °C
Cut-in difference 20 K
Calculated temperature at which the
the hot-water charging is switched on
(temperature at the upper tank sensor)
(60-20=) 40 °C
Go to line 2.
1 Difference, cut-out temperature
- lower sensor
Circuit Setting range Factory setting
II 1 ... 99 K 15 K
Set the difference between the charging temperature and
the cut-out temperature of the hot water charging.
2 Difference, cut-in temperature
- upper sensor
Circuit Setting range Factory setting
II 1 ... 99 K 20 K
Set the difference between the charging temperature and
the cut-in temperature of the hot water charging.
The grey
side of the
ECL Card
Basic set-up
Go to line 6.
Set the running time of the motorized valve.
This is the time it takes the valve to move from
closed to fully open position.
Go to line 7.
Set the neutral zone. As long as the control
deviation is within the neutral zone, the actuator
does not receive an input signal from the
controller.
27b
7 Neutral zone
Circuit Setting range Factory setting
II 0 ... 9 K 3 K
6 Running time of the motorized valve
Circuit Setting range Factory settings
II 5 ... 250 sec. 35 sec.
Note the table in section 24 “How to calculate the running
time of the motorized valve”.
The grey
side of the
ECL Card
1
1
ON
2
0
4
8
3
ON
2
ON
Setting the PI-regulation -
line 4-7
(hot-water charging)
27a
Basic set-up
Go to line 4.
Set the desired proportional band value.
High value - Weak reaction to deviations
Low value - Strong reaction to deviations,
however with a risk of instable
control
Go to line 5.
Set the desired integration time constant.
High value - Slow but stable control
Low value - Fast but with less stable
control.
Select circuit II.
4 Proportional band
Circuit Setting range Factory setting
II 1 ... 250 K 80 K
5 Integration time constant
Circuit Setting range Factory setting
II 5 ... 999 sec. 30 sec.
The grey
side of the
ECL Card
29b
Control & overviews
Adapting the ECL Comfort controller to the heating
system
Check list
Turn the ECL Card so that the grey side faces
you.
Set the time and the date (Line A)
See section 17.
Check all settings referring to the grey side of
the ECL Card
See sections 20 to 25.
Check all settings in
Extended Service
(lines 10
to 199) are made or that the factory settings
comply with your requirements.
If your heating system differs from the diagram shown on
the overleaf of the cover, you should check and alter the
following service parameters, if necessary.
To ensure that you have the correct settings see section 10
for examples of different heating systems.
52-I Priority / parallel operation
52-II Closed valve / control of circulation
temperature
84-II Pump P2 used in primary circuit
Line
29a
Control & overviews
Check list
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral).
See section 12 or 13.
Check that valves and pumps are connected to
the correct terminals.
See section 12 or 13.
Check that all sensors are connected to the
correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you and press
, if necessary.
See section 15.
Select manual operation in the controller mode.
See section 2
in the user’s guide.
Check that valves open and close, and that
pumps start and stop when operated manually.
See section 19.
Having completed the manual operation check,
choose automatic operation.
Check that the temperatures shown in display A
and B match the actual sensors, both for circuit I
(heating) and circuit II (hot water).
See section 1
in the user’s guide.
A Time and date Sections 16 & 17
B System information Sections 18 & 19
C Upper and lower Section 20
storage tank sensor
ECL Card setting
(circuit II)
Control & overviews
30b
ECL Card settings
(circuit I)
30a
A Time and date Sections 16 & 17
B System information Sections 18 & 19
C Heat curve Section 20
Control & overviews
Setting range Factory setting Your settings
1 Difference, cut-out temperature
- lower sensor
1 - 99 K 15 K K
See section 25.
2 Difference, cut-in temperature
- upper sensor
1 - 99 K 20 K K
See section 25.
4 Proportional band
1 - 250 K 80 K K
See section 27.
5 Integration time constant
5 - 999 sec. 30 sec. sec.
See section 27.
6 Running time of the motorized valve
5 - 250 sec. 35 sec. sec.
See section 27.
7 Neutral zone
0 - 9 K 3 K K
See section 27.
Setting range Factory setting Your settings
C Heat curve - slope
0.2 - 3.4 1.8
See section 20.
C Heat curve - parallel displacement
-9 ... +9 0 K K
See section 20
1 Limit for heating cut-out
10 - 30 °C 20 °C °C
See sectiion 21.
2 Flow temperature, min./max. limits
10 - 110 °C Min. 40, Max. 90 °C °C
See section 22.
3 Room temperature influence
0 - 99 / -99 - 0 Min. 0, Max. -40
See section 23.
4 Proportional band
1- 250 K 80 K K
See section 26.
5 Integration time constant
5 - 999 sec. 30 sec. sec.
See section 26.
6 Running time of the motorized valve
5 - 250 sec. 35 sec. sec.
See section 26.
7Neutral zone
0 - 9 K 3 K K
See section 24.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Danfoss ECL Comfort 300 - C47 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI