Vemer Fiuto User manual

Type
User manual

Vemer Fiuto is a flush-mounting detector for monitoring air quality by measuring CO2 equivalent (CO2eq), designed to be installed in closed environments such as shops, offices, public places, etc. The output relay is activated when the equivalent CO2 concentration exceeds the intervention value set with the knob, and can be used, for example, to activate ventilation units for air exchange. The device performs actions of 1B type and is intended to operate in environments with pollution degree 2 and overvoltage category III (EN 60730-1). CO2 equivalent (CO2eq) is a measurement of all the gases that contribute to the greenhouse effect, taking into account their specific Global Warming Potential (GWP). By measuring CO2eq, Vemer Fiuto can provide a more accurate assessment of air quality than by measuring CO2 alone.

Vemer Fiuto is a flush-mounting detector for monitoring air quality by measuring CO2 equivalent (CO2eq), designed to be installed in closed environments such as shops, offices, public places, etc. The output relay is activated when the equivalent CO2 concentration exceeds the intervention value set with the knob, and can be used, for example, to activate ventilation units for air exchange. The device performs actions of 1B type and is intended to operate in environments with pollution degree 2 and overvoltage category III (EN 60730-1). CO2 equivalent (CO2eq) is a measurement of all the gases that contribute to the greenhouse effect, taking into account their specific Global Warming Potential (GWP). By measuring CO2eq, Vemer Fiuto can provide a more accurate assessment of air quality than by measuring CO2 alone.

3
4
1
2
Vemer S.p.A.
I - 32032 Feltre (BL) • Via Camp Lonc, 16
e-mail: info@vemer.it - web site: www.vemer.it
MKIS01075-010 Mod. FIUTO
Flush-mounting detector for monitoring air quality by measuring
CO2 equivalent (CO2eq), designed to be installed in closed environments
such as shops, offices, public places, etc.
The output relay is activated when the equivalent CO2 concentration exceeds
the intervention value set with the knob, and can be used, for example,
to activate ventilation units for air exchange. The device performs actions
of 1B type and is intended to operate in environments with pollution degree 2
and overvoltage category III (EN 60730-1).
Code Model Descritpion
VE788100 Fiuto Flush-mounting air quality detector
SAFETY WARNINGS
During product installation and operation it is necessary to observe
the following instructions:
1) The device must be installed by a qualified person, in strict compliance
with the connection diagrams.
2) Do not power or connect the device if any part of it is damaged.
3) After installation, inaccessibility to the connection terminals without
appropriate tools must be guaranteed.
4) The device must be installed and activated in compliance with current electric
systems standards.
5) Before accessing the connection terminals, verify that the leads are not live.
6) In the electrical system of the building where the instrument must be installed,
a protection device from the overcurrents must be present.
TECHNICAL SPECIFICATIONS
Power supply: 230Vac (-15% ÷ +10%) 50/60Hz
Absorption: 4VA (0.5W)
Installation on 3 modules box (503 type)
Terminals:
– 3 terminals for 1.5 mm2 cables for output relay
– 2 terminals for 1.5 mm2 cables for power supply
Output: bistable relay 5(3)A / 250 Vac
Minimum time between a switching and the next one: 1 minute
Regulation type: on/off with fixed differential of 50 ppm
Regulation range: 400 ppm÷ 2000 ppm
2-position selector switch: always off, automatic
Operating temperature: 0 ÷ +50°C
Storage temperature: -10°C ÷ + 60°C
Operating humidity: 20 ÷ 90% non condensing
Protection degree: IP40
Insulation: reinforced among accessible parts (frontal) and all other terminals
Mechanical locks on the knob to limit the adjustment range
The adapters inside the box allow the monitoring of the following cover plates:
For information about the possibility to adapt the device with different
cover plates from those listed, contact the Technical Service.
* through mount that you can buy on request (code VE767500)
All the above trademarks are the property of their respective owners
ABB Chiara series
ABB Mylos series
Ave S44 series
Bticino Axolute series
Bticino Axolute Air*
Bticino Light series
Bticino Light tech series
Bticino Living series
Bticino Livinglight series
Bticino Livinglight Air series
Bticino Matix series
Gewiss Chorus series
Vimar Eikon series
Vimar Eikon Evo series
Vimar Idea series
Vimar Plana series
Vimar Arké series
User Manual
FLUSH-MOUNTING AIR QUALITY DETECTOR
Read all instructions carefully
OPERATION
PACKAGE CONTENTS
WIRING DIAGRAMS
ADJUSTABLE COVER PLATES
5
When we talk about air quality, we usually mean the concentration
of carbon dioxide present.
However, it is established that there are, in addition to carbon dioxide (CO2),
also other gases responsible for the decay of air quality and, consequently,
of the greenhouse effect: methane (CH4), protoxide nitrogen (N2O),
hydrofluorocarbons (HFC), perfluorocarbons (PFC) and sulfur hexafluoride (SF6)
Each of these gases contributes to the greenhouse effect with a different
weight (called GWP or Global Warming Potential).
The measurement of all these gases that also takes account
of their specific GWP is called CO2 equivalent (CO2eq).
WHAT IS CO2 EQUIVALENT
Cover, knob and plastic elements are available in white and anthracite grey colours
Detector
Covers VI plastic
elements
BM plastic
elements
A mount B mount
• Use the selector placed on the front to turn on or off the device:
- position 0: device off, no regulation
- position |: device switched on, active regulation.
Use the knob to set the intervention value.
It’s possible to set values between 400 ppm and 2000 ppm.
When the CO2 concentration present in the room exceeds the set value,
the red led lights up and the relay switches between contacts 1-2.
Note: in order to preserve the life of the system, the minimum time
between a relay switching and the next one is 1 minute. However, the led
status updating is immediate. Therefore, after using the regulation knob, it
is possible to find a momentary discrepancy between what is indicated by
the led and the actual status of the relay.
This condition lasts for up to 1 minute.
Setpoint modification
The device signals the probe error condition with the LED flashing.
In this case the regulation is inhibited and the relay contact remains
between terminals 2 and 3. Contact Vemer Technical Support.
Probe error signal
AIR mount
COM
NO NC
NL
230Va
123 45
Install the device at a height of about 1.5-2 m from the floor, avoiding positions
with excess or total lack of ventilation. Also make sure that the detector is
installed away from direct radiation, at a distance of at least 30 centimeters
from doors, windows and heat sources. Pay attention that the flow of air that
hits the detector is not obstructed by curtains or wardrobes placed nearby.
Avoid installing the detector in a humid area or with temperatures outside
the operating range. Also avoid positioning the detector near sinks, hobs
or near extractor hoods or vents and, more generally, areas where dirt
and dust could obstruct the slots, preventing correct operation
The device is sold already mounted with anthracite colour.
To transform it in the white version, remove the knob and the cover, acting
on the hooks placed on the upper and lower side of the device and mount
the cover and the white knob included in the package.
Make the connections by respecting
the diagrams described in this manual.
Fix the device inside the 3 modules box
in compliance with the assembly diagrams
described on the back of this instruction sheet.
The accessories for the installation
included in the package allow the mounting
of the plates described in the diagram
“adjustable cover plates”.
INSTALLATION
Reduction of the adjustment range
It is possible to mechanically limit the adjustment range if the device
is installed, for example, in public places or in hotel rooms.
To limit the adjustment range, proceed as follows:
- position the knob in an intermediate value to the desired range
(for example, if the desired adjustment range is 1000-1600 ppm,
bring the knob indicator to the 1300 ppm position)
- remove the knob.
- under the knob there are two rings marked from the words “min”
and “MAX”, respectively for the lower limit and above.
- turn the “min” ring nut clockwise
and position it at the minimum
value of the desired adjustment
range (refer to the ppm values
shown on the cover).
- turn the “MAX” ring nut
anticlockwise and position
it corresponding to the
maximum value of the
desired adjustment range
(refer to the ppm values shown on the cover).
- reposition the knob, making sure that the indicator of the setpoint on
the knob is in the same position as when the knob has been removed.
To remove the setpoint limitation, turn the two ring nuts until the limitation
blocks are in an external position in the range 400 ppm ÷ 2000 ppm.
6
7
REFERENCE STANDARDS
Compliance with Community Directives
2014/35/UE (LVD) and 2014/30/UE (EMCD)
is declared with reference to the following harmonized standards: • EN 60730-2-15
03-2021
Fiuto does not require any particular maintenance.
However, it is necessary to ensure the cleanliness of the slots placed
on the front to ensure proper air flow. Do not use chemicals, polishes
or bleach for cleaning. Simply dust with a damp cloth.
CARE AND MAINTENANCE
After powering up, the device performs the starting phase, which is
necessary to warm up the detector. In this phase, which lasts a total of about
20 seconds, the red led flashes and in the initial 2 seconds the relay switches
twice. In this phase the device does not perform any adjustment and the relay
remains between terminals 2 and 3.
After the starting phase, the device performs the detector self-calibration.
This phase has a variable duration, from about 30 minutes in the best case
(which occurs if the room is well ventilated, with a CO2eq concentration of
about 400 ppm) up to 8 hours in the worst case. During the self-calibration
phase, the adjustment is still active, even if the CO2eq measurement carried
out by the detector can take place with lower accuracy.
Note: the starting and self-calibration phase are performed every time
the device is powered.
Start up
8
AIR
*
B
BM
B
A
AXO AIR
B
VI*
Bticino Matix series
Bticino Living, Light, Light Tech, Livinglight, Axolute series
Vimar Eikon, Eikon Evo, Plana series
Ave S44 series – ABB Mylos series
Remove the cogs Remove the cogs
Bticino Livinglight AIR series
* Note: If the box extension is not present (adapter
which increases the depth of the in-built box)
we recommend using the frame for installation
Livinglight AIR. AXO AIR mount not included in the package.
Bticino Axolute AIR series
* Note: only for installing the Vimar Idea series
cover plate, use the side plastic elements VI.
ABB Chiara series
Vimar Arké series, Idea
Gewiss Chorus series
MOUNTING
  • Page 1 1
  • Page 2 2

Vemer Fiuto User manual

Type
User manual

Vemer Fiuto is a flush-mounting detector for monitoring air quality by measuring CO2 equivalent (CO2eq), designed to be installed in closed environments such as shops, offices, public places, etc. The output relay is activated when the equivalent CO2 concentration exceeds the intervention value set with the knob, and can be used, for example, to activate ventilation units for air exchange. The device performs actions of 1B type and is intended to operate in environments with pollution degree 2 and overvoltage category III (EN 60730-1). CO2 equivalent (CO2eq) is a measurement of all the gases that contribute to the greenhouse effect, taking into account their specific Global Warming Potential (GWP). By measuring CO2eq, Vemer Fiuto can provide a more accurate assessment of air quality than by measuring CO2 alone.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI