DANLERS BMPIRSP Installation guide

Type
Installation guide

This manual is also suitable for

DANLERS BMPIRSP is a batten mount passive infrared occupancy switch with a PIR sensor to detect movement of a warm body and a photocell to monitor ambient light levels. It can switch loads of up to 1500W of fluorescent or mains halogen lamps, 750W of electronic or wire wound transformers, and 500W of CFL, 2D lamps, LED drivers, and LED lamps and fittings. It has a range of 1.5m diameter and a maximum height of 5m. The time delay can be set between 10 seconds and 40 minutes, and the ambient light threshold can be set between approximately 100 and 3000 lux.

DANLERS BMPIRSP is a batten mount passive infrared occupancy switch with a PIR sensor to detect movement of a warm body and a photocell to monitor ambient light levels. It can switch loads of up to 1500W of fluorescent or mains halogen lamps, 750W of electronic or wire wound transformers, and 500W of CFL, 2D lamps, LED drivers, and LED lamps and fittings. It has a range of 1.5m diameter and a maximum height of 5m. The time delay can be set between 10 seconds and 40 minutes, and the ambient light threshold can be set between approximately 100 and 3000 lux.

Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected] Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue.
ThisproductconformstoBSEN60669-2-1.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.overcurrentprotection,1kVovervoltage.Pleaseensure
thatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
Batten Mount PIR occupancy switches
BMPIR5M BMPIR10M BMPIRSP BMPIRRH
DANLERSBattenmountpassiveinfra-redoccupancyswitches(PIR)
canbemountedontotheendoflightingbattensviathe20mmknock
out.Theswitchincludestheconnection20mmthreadand1mofwire
tails to connect to the lighting ballast.
The PIRs incorporate a passive infra-red quad sensor to detect
movementofawarmbodywithinthedetectionzoneandincludea
photocelltomonitortheambientlightlevel.
Ondetectingmovement,iftheambientlightisdarkenough,thePIR
will switch the load on. The ambient threshold can be set by the user
to between approximately 100 and 3000 lux (on the working plane)
viatheLUXadjuster.
BMPIR5Mhasa5mdiameterrange,5mmaxheight,seediag.B.
BMPIR10Mhasa10mdiameterrange,5mmaxheight,seediag.B.
BMPIRSPhasa1.5mdiameterrange,5mmaxheight,seediag.B.
BMPIRRHhasa2.5mdiameterrange,2.5mmaxheight,seediag.B.
A ‘real time’ photocell status indicator glows green when the photocell
isactiveandglowsredwhenthephotocellisinactive.
Ifnomoremovementisdetectedwithinacertaintime,thenthePIRwill
switchofftheload.ThetimecanbesetviatheinternalTIMEadjuster
to between 10seconds and 40 minutes (diagram D).
Loading
ThesePIRsshouldonlybeconnectedtoa230V50Hzacsupply.
Theycanswitchthefollowingtypeofloads:
• 10amps(2500W)resistiveloadsandtungsten
• 6amps(1500W)uorescent(switchstart)/mainshalogenlamps
 (recommendedwithintegralsafetyfuse)
• 3amps(750W)electronicorwirewoundtransformers.
• 2amps(500W)CFL,2Dlamps,LEDDriversandLEDlamps
 andttings.
NormallyOPENcontacts.
13/03/15 INS713BMPIR5M/10M/SP/RH
Wiring diagram
The PIR does not detect
• PersonistoofarfromthePIRswitch,seedetectiondiagram.
• Personismovingunusuallyslowly(perhapswhentesting).
ThePIRfalsetriggers
• Detectorisplacedtooclosetoheatormovingairsources.
Trouble shooting
L
load
optional manual
wall switch for
overriding off
N
230 VAC
SL
N
L
load
optional manual
wall switch for
overriding off
N
230 VACSL
NSL
N
Single BMPIRxxA few BMPIRxx wired in parallel
BMPIR5M/10M/SP/RH
3000
40m
20m
10m
5m
2.5m
80s
40s
20s
10s
100
up to 5m
For optimum
coverage
recommended
mounting
height: 2.4
to 5m
up to 10m
BMPIR5M BMPIR10M
100° 112°
For optimum
coverage
recommended
mounting
height: 2.4
to 5m
up to 1.5m
For optimum
coverage
recommended
mounting
height: 2.4
to 5m
BMPIRSP
20°
For optimum
coverage
recommended
mounting
height: 2.4
BMPIRRH
100°
Installation procedure
1. Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
Makesurethepowerisisolatedfromthecircuit.
2. Removethe20mmknockoutfromtheendofthelightingbatten.
3. MakingreferencetodiagramA:Removethe20mmthreadfromthe
PIR and insert it through the 20mm knockout hole with the thread
facingoutwards
4. FeedthetrailingwiresthroughthethreadandwiththePIRfacing
downwards tighten the 20mm thread.
5. The trailing wires should be connected to the ballast as:
Brown-Livesupply.Blue-Neutralsupply.White-SwitchedLinetoballast.
6. Oncethewiringhasbeencompletedandveried,switchonthesupply
and test the operation.
Set-up
7. Whenpoweredup,(after1minutestabilisationtime)turnluxpot
fullyclockwiseandtimepotfullyanticlockwise.
8. Pressthebuttonforapproximately0.5s.TheLEDwillgogreenindi-
catingtheLUXcellisactive.(Orpressandholdbuttonforapprox.4
seconds – LED goes RED indicating Lux cell INACTIVE). Repeating
thesestepswilltogglethefunctionality.
9. Ifluxcellactive,vacateareauntilPIRswitchswitchestheloadoff
(shouldbeafter10seconds).
10.WiththeLUXasdesiredondesktopfromdaylightONLY(noarticial
light),windtheluxpotanticlockwisewhilstwavingyourhandinfront
ofthePIRcell.WhenthePIRswitchestheloadON,stopturningthe
pot.TheLuxinhibitlevelisnowset.
11. Turn the PIR time to the desired timeout.
To light
fitting
ballast
C: Lux
adjustment
D: Time
adjustment Dual colour LED
RED - PIR active, Photocell inactive
GREEN - PIR and Photocell override ON (passive LUX)
Lux Cell
Mode
PIR Lens
Time
delay
setting
Lux setting
Lux cell
PIR head - key components
Precondition Power-up Condition
LuxCellInactive
RelayOFF
LuxCellInactive
RelaycomesONfor1Min.After1min.readyfordetection.
LuxCellActive
RelayON
LuxCellActive
RelaystaysONfor1Min.After1min.readyfordetection.
LuxCellActive
RelayOFF
LuxCellActive
RelaycomesONfor1Min.After1min.readyfordetection.
LuxCellInactive
RelayON
LuxCellInactive
RelaystaysONfor1Min.After1min.readyfordetection.
A: Installation diagram,
viewed from below
B: Detection range
3000
40m
20m
10m
5m
2.5m
80s
40s
20s
10s
100
  • Page 1 1
  • Page 2 2

DANLERS BMPIRSP Installation guide

Type
Installation guide
This manual is also suitable for

DANLERS BMPIRSP is a batten mount passive infrared occupancy switch with a PIR sensor to detect movement of a warm body and a photocell to monitor ambient light levels. It can switch loads of up to 1500W of fluorescent or mains halogen lamps, 750W of electronic or wire wound transformers, and 500W of CFL, 2D lamps, LED drivers, and LED lamps and fittings. It has a range of 1.5m diameter and a maximum height of 5m. The time delay can be set between 10 seconds and 40 minutes, and the ambient light threshold can be set between approximately 100 and 3000 lux.