Danfoss CF-RS Standard Room Thermostat Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss CF-RS Standard Room Thermostat Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
088U0210
Instruction CF-RS Standard Room Thermostat
Anleitung CF-RS Raumthermostat (standard)
Vejledning CF-RS Standardrumtermostat
Instruction CF-RS Thermostat standard
2
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Instruction . . . . . . . . . . . . . . . . . . . . . . . 3
Anleitung . . . . . . . . . . . . . . . . . . . . . . . 14
Vejledning . . . . . . . . . . . . . . . . . . . . . . . 24
Instruction . . . . . . . . . . . . . . . . . . . . . . 34
3VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
1. Functional Overview . . . . . . . . . . . . . . . . . . 4
2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. Transmission Test . . . . . . . . . . . . . . . . . . . . . 8
4. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5. Uninstallation . . . . . . . . . . . . . . . . . . . . . . . . 10
6. Specications . . . . . . . . . . . . . . . . . . . . . . . . 11
7. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 12
8. Figures and illustrations . . . . . . . . . . . . . . . 44
Index
4
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Front - g. 1
Turning knob & push button
Red LED (behind the cover)
LED modes
• Permanent light ON
• No light OFF
• Slow ashing Flashes
• Fast ashing Flickers
Back - g. 2
Back plate
Turning knob release
Back plate lock/unlock (turn 90°)
Screw hole for wall mounting
Battery placement
Screw and wall plug
Note: To activate batteries please remove enclosed
strips from batteries
1. Functional Overview
5VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Turning Knob - g. 3
Turning knob release
Room temperature limitation - g. 4
Minimum limitation (blue) (from 10°C)
Maximum limitation (red) (up to 30°C)
6
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Note:
To activate batteries in the Room Thermostat
please remove enclosed strips from the batteries
The assignment of the Room Thermostats to the
Master Controller should be within 1½m distance
Activate Install mode on
Master Controller - g. 1
Use the menu selection button to select the
Install mode. Install LED ashes
Activate Install mode by pressing OK . Install
LED goes ON
Activate Install mode on
Room Thermostat
Press the push button . LED and icker
during communication
Select output on Master Controller
All available output LEDs on Master Controller
light up, and the rst of them ashes
Press output selection button , select desired
output (ashes) and accept with OK
All output LEDs go OFF. Selected output
stays ON shortly
2. Installation
7VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Room Thermostat installation status
Satisfactory - LED goes OFF
Not satisfactory - LED ashes 5 times
Note: A Room Thermostat can be assigned to sev-
eral outputs if needed
8
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Initiate transmission test on Room
Thermostat - g. 1
• Press the push button
• LED goes ON
Link test is satisfactory
• LED goes OFF
Link test is unsatisfactory
• LED ashes 5 times
No Link connection to Room
Thermostat
Try to relocate Room Thermostat in the room
Or install Repeater Unit (CF-RU) and locate be-
tween Master Controller and Room Thermostat
Note: Master Controller output LED(s) connect-
ed to the room thermostat, ash(es) during Link test
3. Transmission Test
9VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Placing the Room Thermostat - g. 5
! Wherever possible, the room thermostat should be
installed at a place where the eect of sunlight,
draught, other heaters (eg. TVs), etc. is avoided.
Mounting with screws - g. 2
4. Mounting
10
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Activate Uninstall mode on Master
Controller - g. 1
Use the Menu selection button to choose
the Uninstall menu. Uninstall LED ashes
Activate Uninstall mode by pressing OK .
Uninstall LED goes ON
Deselect output on Master Controller
Select output to be removed by output selec-
tion button
Remove ashing output with OK
5. Uninstallation
11VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Temperature setting
range
5-35°C
Transmission frequency 868.42MHz
Transmission range in
normal buildings (up to)
30m
Transmission power < 1mW
Battery Alkaline 2xAA, 1.5V
Battery lifetime
(up to)
3-4 years
Ambient temperature 0-50°C
IP class 21
6. Specications
12
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
Error Indication Possible Cause
The LED ashes every
5th minute
Low battery
The LED ashes Critical low battery
The LED ashes 5 times Installation/Link Test is
unsatisfactory
7. Troubleshooting
13VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Standard Room Thermostat
16
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Anleitung CF-RS Raumthermostat (standard)
Drehknopf - Abb. 3
Lösevorrichtung des Drehknopfs
Raumtemperaturbegrenzung - Abb. 4
Mindestbegrenzung (blau) (ab 10°C )
Höchstbegrenzung (rot) (bis 30°C)
24
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Vejledning CF-RS Standardrumtermostat
1. Funktionsoversigt. . . . . . . . . . . . . . . . . . . . . 25
2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3. Transmissionstest . . . . . . . . . . . . . . . . . . . . 29
4. Montering . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5. Anstallation . . . . . . . . . . . . . . . . . . . . . . . . . 31
6. Specikationer . . . . . . . . . . . . . . . . . . . . . . . 32
7. Fejlnding . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8. Figurer og illustrationer . . . . . . . . . . . . . . . 44
Indhold
32
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Vejledning CF-RS Standardrumtermostat
Temperatur indstilling-
sområde
5-35°C
Transmissionsfrekvens 868.42MHz
Transmissionsræk-
kevidde i almindelige
bygninger (op til)
30m
Transmissionseekt < 1mW
Batteri Alkaline 2xAA, 1.5V
Batterilevetid (op til) 3-4 år
Omgivelsestemperatur 0-50°C
IP-klasse 21
6. Specikationer
33VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Vejledning CF-RS Standardrumtermostat
Fejlindikation Mulig årsag
Indikatoren blinker
hvert femte minut
Batteriniveau lavt
Indikatoren blinker Batteriniveau kritisk lavt
Indikatoren blinker fem
gange
Installlations-/linktesten
er ikke-tilfredsstillende
7. Fejlnding
34
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Thermostat standard
1. Présentation des fonctions . . . . . . . . . . . . 35
2. Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3. Test de transmission
. . . . . . . . . . . . . . . . . . 39
4. Montage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5. Désinstallation . . . . . . . . . . . . . . . . . . . . . . . . 41
6. Spécications . . . . . . . . . . . . . . . . . . . . . . . . 42
7. Dépannage . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8. Tableaux et illustrations . . . . . . . . . . . . . . . 44
Index
36
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Thermostat standard
Bouton tournant - g. 3
Libérer le bouton tournant
Limite température pièce - g. 4
Limite minimale (bleu) (depuis 10°C)
Limite maximale (rouge) (jusqu’à 30°C)
40
VI.UH.L1.52
Produced by Danfoss Floor Heating Hydronics 08.2008
Instruction CF-RS Thermostat standard
Emplacement du Thermostat
d’ambiance - g. 5
Installer si possible le thermostat dÅfambiance á un
endroit non exposé au soleil, aux courants d’air et á
d’autres sources de chaleur, etc. (par ex. TV).
Montage avec vis - g. 2
4. Montage
/