Danfoss ECL Comfort 310, A377 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 310, A377 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort310,applicationA377
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................13
2.3Mounting...........................................................17
2.4Placingthetemperaturesensors................................21
2.5Electricalconnections.............................................23
2.6InsertingtheECLApplicationKey..............................31
2.7Checklist............................................................37
2.8Navigation,ECLApplicationKeyA377.........................38
3.0Dailyuse.........................................................53
3.1Howtonavigate...................................................53
3.2Understandingthecontrollerdisplay..........................54
3.3Ageneraloverview:Whatdothesymbolsmean?...........57
3.4Monitoringtemperaturesandsystem
components........................................................58
3.5Influenceoverview................................................59
3.6Manualcontrol.....................................................60
3.7Schedule............................................................61
4.0Settingsoverview............................................62
5.0Settings...........................................................64
5.1IntroductiontoSettings..........................................64
5.2Flowtemperature..................................................65
5.3Roomlimit..........................................................69
5.4Returnlimit.........................................................71
5.5Flow/powerlimit.................................................78
5.6Optimization........................................................82
5.7Controlparameters................................................89
5.8Application.........................................................93
5.9Heatcut-out......................................................103
5.10Tanktemperature................................................106
5.11Alarm..............................................................111
5.12Alarmoverview..................................................115
5.13Anti-bacteria......................................................116
6.0Commoncontrollersettings............................118
6.1Introductionto‘Commoncontrollersettings..............118
6.2Time&Date.......................................................119
6.3Holiday............................................................120
6.4Inputoverview...................................................122
6.5Log.................................................................123
6.6Outputoverride..................................................124
6.7Keyfunctions.....................................................125
6.8System.............................................................127
7.0Miscellaneous................................................134
7.1ECA30/31setupprocedures.................................134
7.2Overridefunction................................................142
7.3Severalcontrollersinthesamesystem......................145
7.4Frequentlyaskedquestions....................................148
7.5Definitions........................................................151
7.6Type(ID6001),overview.......................................154
7.7ParameterIDoverview..........................................155
©Danfoss|2017.10VI.GU.F6.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA377
(ordercodeno.087H3817).
TheECLApplicationKeyA377contains3subtypes,allapplicablein
ECLComfort310:
A377.1:2xheatingand1xDHW
A377.2:2xheatingand1xadvancedDHW
A377.3:2xheatingand1xadvancedDHWwithDHW
circulationtemperaturemonitoring
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310for
advancedsolutions,forexampleM-bus,ModbusandEthernet
(Internet)communication.
TheapplicationKeyA377complieswithECLComfort310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedandthebuilt-inroomtemperaturesensorcanbe
utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://heating.danfoss.com/download/tools/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartforECLComfort310:
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort310,modulesand
accessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
VI.GU.F6.02
©Danfoss|2017.10|3
OperatingGuideECLComfort310,applicationA377
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
4|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.GU.F6.02
©Danfoss|2017.10|5
OperatingGuideECLComfort310,applicationA377
2.0Installation
2.1Beforeyoustart
Theapplications(subtypes)intheA377applicationkeyarevery
flexibleandalmostidentical.
However,someapplicationshaveextrafunctionswhichare
describedseparately.
Thesearethebasicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1).
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Bymeansofaweekschedule(upto3Comfortperiods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesforthedesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperature(RemotecontrolunitECA30/
31)doesnotequalthedesiredroomtemperature,thedesiredflow
temperaturecanbeadjusted.
Thecirculationpump(P2)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedflow/power.
Thedesiredflowtemperatureofheatingcircuit1can,viaS7,be
controlledbymeansofanexternalvoltageintherange0-10volt.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
Analarmcanbeactivatediftheactualflowtemperaturediffers
fromthedesiredflowtemperature.
TheroomtemperaturesignalcanbeachievedfromtheRemote
ControlUnitECA30/31,ifconnected.
A377.2:
WhenbothDHWheating/chargingandheatingcircuit1are
active,thecirculationpumpintheheatingcircuitcancontinue
operating.Theheatingcircuittemperatureistypicallyincreased.
Thisisparallelmode.Iftheincreaseoftheflowtemperature
cannotbeaccepted,thecirculationpumpinheatingcircuitcanbe
stopped.ThisisDHWprioritymode.
TypicalA377.1application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
Returntemperaturesensor,circuit2
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
(S7)
(Externaltemperaturecontrol,notillustrated)
S8
DHWtanktemperaturesensor,lower
S9
DHWflowtemperaturesensor,circuit3
S10
Returntemperaturesensor,circuit3
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit3
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
P1
DHWheatingpump(notillustrated)
P2
Circulationpump,heating,circuit1
P3
DHWcirculationpump
P4
DHWchargingpump
P5
Circulationpump,heating,circuit2
A1
Alarm
A/B
Internal/externalconnectionsforDHWcirculation
6|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
Heatingcircuit,ingeneral:
Exerciseofcirculationpumpandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
Heating(circuit2):
Thiscircuitworksaftersameprinciplesascircuit1.
TheflowtemperaturesensorS4isthemostimportantsensor.
ThemotorizedcontrolvalveM3controlsthecircuit.
Thereturntemperature(S2)enableslimitationasdescribed
previously.
Heatingcircuit2canbeconnectedafterheatingcircuit1.Ifso,the
desiredflowtemperatureatS3canbeinfluencedbythedesired
flowtemperatureatS4.
A377.1examplea:
A377.1,exampled
VI.GU.F6.02
©Danfoss|2017.10|7
OperatingGuideECLComfort310,applicationA377
DHW(circuit3):
TheDHWheatingcircuitisconnecteddirectlytotheheating
source.ThetemperaturesensorS10measuresthereturn
temperature.Ifthereturntemperaturelimitisexceeded,the
desiredtemperatureatS9canbecorrected.
Bymeansofaweekschedule(upto3Comfortperiods/day),the
DHWcircuitcanbeinComfortor‘Saving’mode(twodifferent
temperaturevaluesfordesiredDHWtemperature).
Chargingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthe
charging-starttemperature,theDHWheatingpumpP1isswitched
ON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain
theheating/chargingtemperatureatS9.
TheDHWchargingpumpisswitchedONwhentheS9temperature
isacceptable,whichmeansitmustbewithin3Kfromdesired
heating/chargingtemperature.SeealsoapplicationA377.1,ex.d.
IfS9isplacedontheheat-exchanger'ssecondaryside,itmustbe
placedintheheat-exchanger.
TheDHWchargingtemperatureisdeterminedbythedesiredDHW
temperatureatS6plusthesetchargingdifference.Thecharging
temperatureistypically5–10degreeshigherthanthedesired
DHWtemperature.
A377.1,A377.3:
S10canhaveoneoftwofunctions:
1.Actasreturntemperaturelimiter
2.MonitortheDHWheatingtemperatureinordertoavoid
dischargingandenablereturntemperaturelimitation.
Function1:Thereturntemperature,whentheDHWheating/
chargingisactive,canbelimitedtoasetvalue.
Function2:TheDHWchargingpumpisswitchedONwhentheS10
temperatureishigherthantheDHWtemperature.After4minutes,
thereturntemperaturelimitation(setvalue)isactivated.
A377.2:
TheDHWheating/chargingcircuitisconnectedafterheating
circuit1.TheDHWheatingcircuitcannotbeconnecteddirectlyto
theheatingsource.ThetemperaturedemandatS9istransferredas
desiredtemperatureatS3.
TheDHWheatingcircuithasapreheatingcircuit,wheretheDHW
heatingtemperatureatS9isadaptedtothedesiredDHWcharging
temperatureatS10.IftheDHWchargingtemperatureatS10
cannotbereached,theECLcontrollergraduallyincreasesthe
desiredDHWheatingtemperatureatS9inordertoobtaintheDHW
chargingtemperature.TheECLcontrollerrememberstheadapted
S9temperature.Amaximumtemperaturevaluecanbeset.
Adelayedstart
ofchargingpumpcanbearranged.Also,itcan
bearranged,thatthestartofthechargingpumpdependsonthe
chargingtemperature.Inthiscase,S10mustbeplacedinthe
heat-exchanger.
A377.1,exampled
Charging-starttemperature:
DesiredDHWtemperature+Startdifference.
Example:
50°C+(-3K)=47°C
TheS10temperaturesensorcanalternativelybeusedasamonitoring
temperaturesensortoenableDHWcharging.Ifusedasamonitoring
temperaturesensor,theS10temperaturesensormustbeplacedin
thesupplypipe.
8|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
Chargingstop,DHWtankwith1temperaturesensor:
WhenthemeasuredDHWtemperatureS6getshigherthan
thecharging-stoptemperature,theDHWchargingpumpP2is
switchedOFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors:
WhenthemeasuredDHWtemperatureS6gets2Khigherthan
thecharging-starttemperatureANDthelowertanktemperature
S8getshigherthanthecharging-stoptemperature,theDHW
chargingpumpP2isswitchedOFF.Apost-runtimecanbeset.
DHWcirculation:
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBstopstheDHWchargingpump
aftertheDHWtankchargingprocedure.Thetemperatureatthe
chargingtemperaturesensorismaintainedaccordingtothevalue
ofthedesiredDHWtemperatureinordertocompensateforthe
heatlossintheDHWcirculationpipe.
Flow/powerlimitation
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworpowertoasetmaximumvalue.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheDHWcirculationpumpP3hasaweekscheduleforupto3
ON-periodsperday.
TypicalA377.2application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
Returntemperaturesensor,circuit2
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
(S7)
(Externaltemperaturecontrol,notillustrated)
S8
DHWtanktemperaturesensor,lower
S9
DHWheatingtemperaturesensor,circuit3
S10
DHWchargingtemperaturesensor,circuit3
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit3
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
P1
DHWheatingpump
P2
Circulationpump,heating,circuit1
P3
DHWcirculationpump
P4
DHWchargingpump
P5
Circulationpump,heating,circuit2
A1
Alarm
A/B
Internal/externalconnectionsforDHWcirculation
Charging-stoptemperature:
DesiredDHWtemperature+Stopdifference.
Example,S6only:
50°C+(3K)=53°C
Example,S6andS8:
50°C+(-8K)=42°C
VI.GU.F6.02
©Danfoss|2017.10|9
OperatingGuideECLComfort310,applicationA377
A377.2examplea:
A377.2exampleb:
10|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
A377.3,ex.a
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
Returntemperaturesensor,circuit2
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
(S7)
(Externaltemperaturecontrol,notillustrated)
S8
DHWcirculationtemperaturesensor
S9
DHWheating/chargingtemperaturesensor
S10
DHWreturntemperaturesensor,circuit3
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit3
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
P1
DHWheatingpump
P2
Circulationpump,heating,circuit1
P3
DHWcirculationpump
P4
DHWchargingpump
P5
Circulationpump,heating,circuit2
A1
Alarm
A/B
Internal/externalconnectionsforDHWcirculation
VI.GU.F6.02
©Danfoss|2017.10|11
OperatingGuideECLComfort310,applicationA377
A377,ingeneral
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertomeasuretheroomtemperatureand
controltheECLcontrollerremotely.
WhentheDHWcircuitisactivefortheheating/charging
procedure,heatingcircuits1and2canbeclosedinordertogive
higherprioritytotheDHWheating/charging.
HolidayprogramsarepresentforHeatingandDHWcircuits.
Besides,aholidayprogramispresentfortheentirecontroller.
Oneormoreconnectedfloworenergymeters(basedonM-bus
signal)canlimitthefloworpowertoasetmaximum(DHWcircuit)
andinrelationtotheoutdoortemperature(heatingcircuits).
InputS7canbeusedtocontrolthedesiredflowtemperatureof
heatingcircuit1.Theappliedvoltageintherange0-10voltis
convertedintheECLcontrollertothedesiredflowtemperature.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.TheECLcontrollersintheECL485system
canworkinmaster-slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beused
tooverridethescheduletoafixed'Comfort','Saving','Frost
protection'or'Constanttemperature'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdatacanfurthermorebetransferredtotheModbus
communication.
Alarm:
AlarmA1(=relay6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
WhentheA377hasbeenuploaded,theECLComfortcontroller
startsinManualmode.Thiscanbeusedforcheckingthecontrolled
componentsforcorrectfunctionality.
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
12|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
VI.GU.F6.02
©Danfoss|2017.10|13
OperatingGuideECLComfort310,applicationA377
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication
examples.Someoftheapplicationexamplesneedchangeof
dedicatedsettings.
Seethedocumentationforapplicationsandsubtypes,delivered
withtheapplicationkey.
A377.1,ex.a
A377.1,ex.d
A377.3,ex.a
A377.3,ex.b
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(3):
InternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
OFF
DHWcircuit(3):
ExternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
ON
A377.1,ex.b
A377.1,ex.c
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2.
Issue:
Navigation:
IDno.:
Recommended
setting:
Heatingcircuit(1):
Heatdemand
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2.
Circuit2mustbeabletosendtheheatdemandtocircuit1.
Issue:
Navigation:
IDno.:
Recommended
setting:
Heatingcircuit(2):
Heatdemand
MENU\Settings\Application:'SenddesiredT'
12500
ON
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(3):
InternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
OFF
DHWcircuit(3):
ExternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
ON
14|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
Adviceforsettings:
A377.2,ex.a
Circuit1mustbeabletoreceivetheDHW-heatingdemandfrom
circuit3.
Issue:
Navigation:
IDno.:
Recommended
setting:
Heatingcircuit(1):
Heatdemand
MENU\Settings\Application:'Demandoffset'
11017
3K*
*ThisvalueisaddedtotheDHW-heatingdemandfromcircuit3.
Circuit3mustbeabletosendtheDHW-heatingdemandto
circuit1.
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(3):
Heatdemand
MENU\Settings\Application:'SenddesiredT'
13500
ON
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(3):
InternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
OFF
DHWcircuit(3):
ExternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
ON
VI.GU.F6.02
©Danfoss|2017.10|15
OperatingGuideECLComfort310,applicationA377
Adviceforsettings:
A377.2,ex.b
A377.2,ex.c
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2
andtheDHW-heatingdemandfromcircuit3.
Issue:
Navigation:
IDno.:
Recommended
setting:
Heatingcircuit(1):
Heatdemand
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatingdemandvaluecircuit2and3.
Circuit2mustbeabletosendtheheatdemandtocircuit1.
Issue:
Navigation:
IDno.:
Recommended
setting:
Heatingcircuit(2):
Heatdemand
MENU\Settings\Application:'SenddesiredT'
12500
ON
Circuit3mustbeabletosendtheDHW-heatingdemandto
circuit1.
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(3):
Heatdemand
MENU\Settings\Application:'SenddesiredT'
13500
ON
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(3):
InternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
OFF
DHWcircuit(3):
ExternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
13054
ON
16|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
VI.GU.F6.02
©Danfoss|2017.10|17
OperatingGuideECLComfort310,applicationA377
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
18|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
VI.GU.F6.02
©Danfoss|2017.10|19
OperatingGuideECLComfort310,applicationA377
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
20|©Danfoss|2017.10
VI.GU.F6.02
OperatingGuideECLComfort310,applicationA377
/