ITT S-DRIVE IM213 User manual

Type
User manual
U
L
®
C
US
ITT
Goulds Pumps
S-Drive™ Constant Pressure
Aquavar SPD™
Variable Speed Pump Control
Installation, Operation &
Maintenance
Models Covered:
S-Drive™
Aquavar SPD™
(5 – 30 HP)
Goulds Pumps is a brand of ITT Corporation.
www.goulds.com
Engineered for life
Commercial Water
IM213
2
INDEX
Index
Important Safety Instructions ........................................................................................................ 3
System Components ....................................................................................................................... 4
System Design ................................................................................................................................ 5
Piping .............................................................................................................................................. 7
Mounting the Controller ................................................................................................................ 8
Power Supply and Wiring .............................................................................................................. 9
Starting the System (Input/Output Connections, Switch Settings, Motor Rotation) ................. 14
Input and Output Functions (Control Terminals) ......................................................................... 19
Troubleshooting ............................................................................................................................ 20
Controller Dimensions .................................................................................................................. 25
Appendix (Input Wire Sizing Chart) ............................................................................................. 26
Goulds Pumps Limited Warranty ................................................................................................. 28
Note:
•UseCopperwireonly.
•Suitableforuseinapollutiondegree2micro-environment.
•Motoroverloadprotectionprovidedat110%offullloadcurrent.
•Inordertomaintaintheenvironmentalratingintegrityoftheenclosure,allopeningsmustbe
closedbyequipmentrated3,3R,3S,4,4X,6or6P.
•MaximumAmbienttemperaturerange-22ºFto122ºF.
•MaximumHumidity:95%at104ºFnon-condensing.
3
! Safety Instructions
DANGER
WARNING
CAUTION
Section 1
Important: Read all safety information prior to installation of the
Controller.
Note
ThisisaSAFETY ALERT SYMBOL.Whenyouseethissymbolonthecontroller,pumporinthis
manual,lookforoneofthefollowingsignalwordsandbealerttothepotentialforpersonal
injuryorpropertydamage.Obeyallmessagesthatfollowthissymboltoavoidinjuryordeath.
Indicatesanimminentlyhazardoussituationwhich,ifnotavoided,willresultindeath
orseriousinjury.
Indicatesapotentiallyhazardoussituationwhich,ifnotavoided,couldresultindeath
orseriousinjury.
Indicatesapotentiallyhazardoussituationwhich,ifnotavoided,mayresultinminoror
moderateinjury.
Usedwithoutasafetyalertsymbolindicatesapotentiallyhazardoussituationwhich,if
notavoided,couldresultinpropertydamage.
NOTE Indicatesspecialinstructionswhichareveryimportantandmustbefollowed.
Note
Alloperatinginstructionsmustberead,understood,andfollowedbytheoperatingpersonnel.
GouldsPumpsacceptsnoliabilityfordamagesoroperatingdisorderswhicharetheresultof
non-compliancewiththeoperatinginstructions.
1. Thismanualisintendedtoassistintheinstallation,operationandrepairofthesystemandmustbekeptwith
thesystem.
2. InstallationandmaintenanceMUSTbeperformedbyproperlytrainedandqualiedpersonnel.
3. Reviewallinstructionsandwarningspriortoperforminganyworkonthesystem.
4. AnysafetydecalsMUSTbeleftonthecontrollerand/orpumpsystem.
5. ThesystemMUSTbedisconnectedfromthemainpowersupplybeforeattemptinganyoperation
ormaintenanceontheelectricalormechanicalpartofthesystem.Failuretodisconnectelectrical
powerbeforeattemptinganyoperationormaintenancecanresultinelectricalshock,burnsor
death.
6. Wheninoperation,themotorandpumpcouldstartunexpectedlyandcauseseriousinjury.
Hazardous
voltage
DANGER
Hazardous
Pressure
CAUTION
CAUTION
4
System Components
Section 2
PleasereviewtheS-Drivecomponentsandinsurethatyouhaveallthepartsandarefamiliarwiththeir
names.BesuretoinspectallcomponentsGouldsPumpssuppliesforshippingdamage.
S-Drive Variable Speed Controller:
1. S-DriveController
2. PressureTransducerwithCable
3. ConduitPlateCaps
Warning
DO NOTpowertheunitorrunthepumpuntilallelectricalandplumbingconnec-
tions,especiallythepressuresensorconnection,arecompleted.Thepumpshould
notberundry.Allelectricalworkmustbeperformedbyaqualiedtechnician.Al-
waysfollowtheNationalElectricalCode(NEC),ortheCanadianElectricalCode(CEC)
aswellasalllocal,stateandprovincialcodes.Codequestionsshouldbedirectedto
yourlocalelectricalinspectororcodeenforcementagency.Failuretofollowelectrical
codesandOSHAsafetystandardsmayresultinpersonalinjuryorequipmentdamage.Failureto
followmanufacturer'sinstallationinstructionsmayresultinelectricalshock,rehazard,
personalinjury,death,damagetoequipment,unsatisfactoryperformanceandmayvoid
manufacturer'swarranty.
WARNING
Hazardous
voltage
Hazardous
Pressure
CAUTION
SPD Y XXXX F
F=WITHOUTPUTFILTER
BLANK=NOOUTPUTFILTER
4DIGITSFORHP
5HP =0050
7.5HP=0075
10HP =0100
15HP =0150
20HP =0200
25HP =0250
30HP =0300
1DIGITFORINPUTVOLTAGE
230VOLT=2
460VOLT=4
575VOLT=5
SERIES
Controller Product Code Information
5
System Design
Section 3
Note
SystemsMUSTbedesignedbyqualiedtechniciansonlyandmeetallapplicablestateandlocal
coderequirements.
ThefollowingdiagramsshowatypicalsystemusingtheS-DriveConstantPressureController.Diagram#1
showsatypicalsetupforasubmersiblesystem.
3
FLOW
4
6
5
1
2
8
9
7
1 S-DRIVE CONTROLLER
2 FUSIBLE DISCONNECT
3 PRESSURE GAUGE
4 AIR DIAPHRAGM TANK
5 PRESSURE TRANSDUCER
6 3 PHASE OUTPUT (ALWAYS)
7 DISCHARGE CHECK VALVE
8 GATE VALVE (HIGHLY RECOMMENDED)
9 SUBMERSIBLE PUMP END
10 SUBMERSIBLE MOTOR (3 PHASE)
11 PRESSURE RELIEF VALVE
NOTE: FOR SINGLE PHASE INPUT, CONNECT L1 AND L3, THEN SET MOTOR
OVERLOAD SWITCHES TO 50% OF CONTROLLER RATING OR LOWER.
L1
L2
L3
GND
T1
T2
T3
GND
10
11
6
Section 3 (continued)
Diagram#2showsaset-upformunicipalwaterconnection.
System Design
FLOW
AIR
4
8
6
3 PHASE OUTPUT
TO MOTOR
5
1
2
SUCTION
3
8
9
7
1 SPD CONTROLLER 6 AIR DIAPHRAGM TANK
2 FUSIBLE DISCONNECT 7 3 PHASE MOTOR
3 CENTRIFUGAL PUMP 8 GATE VALVE (BALL VALVE)
4 CHECK VALVE 9 PRESSURE GAUGE
5 PRESSURE TRANSDUCER (CABLE ASSEMBLY) 10 PRESSURE RELIEF VALVE
NOTES: For single phase input power, use L1 and L3 terminals and adjust motor overload switches to
50% of controller rating or lower.
9
T1
T2
T3
L1
L2
L3
SUPPLY POWER
GND
GND
10
7
Piping
Section 4
General
Note
Allplumbingworkmustbeperformedbyaqualiedtechnician.Alwaysfollowalllocal,stateand
provincialcodes.
Aproperinstallationrequiresapressurereliefvalve,a¼"femaleN.P.T.threadedttingforthepressuresensor,
andproperlysizedpipe.Pipingshouldbenosmallerthanthepumpdischargeand/orsuctionconnections.
Pipingshouldbekeptasshortaspossible.Avoidtheuseofunnecessaryttingstominimizefrictionlosses.
Somepumpandmotorcombinationssuppliedwiththissystemcancreatedangerouspressure.
Selectpipeandttingsaccordinglyperyourpipesuppliers’recommendation.Consultlocalcodes
forpipingrequirementsinyourarea.
Alljointsmustbeairtight.UseTeontapeoranothertypeofpipesealanttosealthreadedconnections.Please
becarefulwhenusingthreadsealantasanyexcessthatgetsinsidethepipemayplugthepressuresensor.
Galvanizedttingsorpipeshouldneverbeconnecteddirectlytothestainlesssteeldischargeheadorcasingas
galvaniccorrosionmayoccur.Barbtypeconnectorsshouldalwaysbedoubleclamped.
Pressure Tank, Pressure Relief Valve and Discharge Piping
Useonly“pre-charged”tanksonthissystem.Donotusegalvanizedtanks.Selectanareathatisalwaysabove
34ºF(1.1ºC)inwhichtoinstallthetank,pressuresensorandpressurereliefvalve.Ifthisisanareawherea
waterleakorpressurereliefvalveblow-offmaydamageproperty,connectadrainlinetothepressurerelief
valve.Run the drain line from the pressure relief valve to a suitable drain or to an area where water
will not damage property.
Pressure Tank, System Pressure
Sizing–Abladdertank(notincluded)isusedtocushionthepressuresystemduringstart-upandshut-down.It
shouldbesizedtoatleast20%ofthetotalcapacityofyourpump.Example:Ifyourpumpissizedfor100GPM
thensizeyourtankforatleast20gal.totalvolume,notdrawdown.Pre-chargeyourbladdertankto10-15PSI
belowyoursystempressure.Thecontrollerispre-setfor50PSIatthefactory.Thereforea35-40PSIpre-charge
inyourtankwouldberequired.Usethehighertankpre-chargesettingifthesystemdriftsover5PSIata
constantowrate.NOTE:Pre-chargeyourtankbeforellingwithwater!
Caution
MaximumworkingpressureofHydroProbladdertankis125psi.
Installing the Pressure Sensor
Thepressuresensorrequiresa¼"FNPTttingforinstallation.Installthepressuresensorwiththeelectrical
connectorpointinguptoavoidcloggingthepressureportwithdebris.Installthepressuresensorinastraight
runofpipeawayfromelbowsorturbulence.Foroptimumpressurecontrolinstallthepressuresensorinthe
samestraightrunofpipeasthepressuretank.Ensurethepressuresensoriswithin10ftofthepressuretank.
Installingthepressuresensorfarawayfromthepressuretankmayresultinpressureoscillations.Do not
install the pressure sensor in a location where freezing can occur.Afrozenpipecancausedamagetothe
pressuresensor.
Hazardous
Pressure
CAUTION
Hazardous
Pressure
CAUTION
8
Piping
Section 4 (continued)
Thepressuresensorcableisprewiredtothecontroller.Thecablecanbeshortenedforacleanerinstallation.
Longercablelengthsareavailable,consultfactory.Maximumrecommendedpressuresensorcablelengthis
300ft.Avoidleavingacoilofpressuresensorcableasthiscaninduceunwantedtransientvoltagesandnoise
intothesystem.Donotrunthepressuresensorcablealongsidetheinputoroutputwiring.Maintainadistance
ofatleast8”betweenthepressuresensorcableandinputoroutputwiring.
Ensurethepressuresensorcableisconnectedasfollows:Browntoterminal7(24VDCSUPPLY),Whiteto
terminal6(TRANSDUCERINPUT),Draintochassis.ConnectingtheDrainwiretothechassiselectrically
connectsthesensorcasetothechassisofthecontroller.Insomecasesthisdrainwiremustbedisconnected
fromthecontrollerchassis.Incaseswherethethereisgroundedmetalpipingwhichiscontinuousbetween
thetransducerandthemotororthetransducerisinstalledingroundedmetalpiping,agroundloopcanresult
sothedrainwiremustbedisconnectedfromthechassis.Incaseswheretherearesectionsofnonmetallic
pipingbetweenthetransducerandmotororthetransducerisinstalledinungroundedpipingthisdrainwire
shouldbeconnectedtothecontrollerchassis.
Mounting the Controller
Section 5
General
Mountthecontrollerinawellventilated,shadedareausing4screws.Thecontrollermustbemounted
vertically.Besuretoleave8inchesoffreeairspaceoneverysideoftheunit.Thecontrollermustbeinan
areawithanambientbetween-22ºFand122ºF.Ifinstallationisabove3300feetabovesealevel,ambient
temperaturesarederated1%per330feetabove3300feet.Thealtitudelimitforthiscontrolleris6500ft.
Donotinstallabove6500ft.
9
WARNING
Hazardous
voltage
Mounting the Controller
Section 5 (continued)
Note
Donotblocktheheatsink(ns)andfansanddonotsetanythingontheunits.
Warning
Thecontrolleraccesscovershouldalwaysbesecurelyfastenedtothecontrolboxdue
tothedangerousvoltage/shockhazardinsidetheunit.Alockcanbeusedtoprevent
unwantedentry.
Power Supply and Wiring
Section 6
Power Supply
Note
InstallationandmaintenanceMUSTbeperformedbyproperlytrainedandqualiedpersonnel.
AlwaysfollowtheNationalElectricalCode(NEC)orCanadianElectricCode(CEC),aswellasall
state,localandprovincialcodeswhenwiringthesystem.
Thetypeoftransformerandtheconnectioncongurationfeedingadriveplaysanimportantroleinitsperformance
andsafety.Thefollowingisabriefdescriptionofsomeofthemorecommoncongurationsandadiscussionoftheir
virtuesandshortcomings.Alwaysaskwhattypeofpowersystemthesitehasbeforesizingthedrive.
Delta/Wye with grounded Wye neutral
Thiscongurationisoneofifnotthemostcommon.Itprovidesrebalancingofunbalancedvoltagewitha30
degreephaseshift.Dependingontheoutputconnectionsfromthedrivetomotor,thegroundedneutralmay
beapathforcommonmodecurrentcausedbythedriveoutput.
10
WARNING
Hazardous
voltage
Power Supply and Wiring
Section 6 (continued)
Delta/Delta with grounded leg
Anothercommoncongurationprovidingvoltagerebalancingwithnophaseshiftbetweeninputandoutput.
Again,dependingontheoutputconnectionsfromthedrivetomotor,thegroundedneutralmaybeapathfor
commonmodecurrentcausedbythedriveoutput.
Ungrounded secondary
Groundingofthetransformersecondaryisessentialtothesafetyofpersonnelaswellasthesafeoperation
ofthedrive.Leavingthesecondaryoatingcanpermitdangerouslyhighvoltagesbetweenthechassisofthe
driveandtheinternalpowerstructurecomponents.Inmanycasesthisvoltagecouldexceedtheratingofthe
EMClterandinputMOVprotectiondevicesofthedrivecausingacatastrophicfailure.Inallcases,theinput
powertothedriveshouldbereferencedtoground.Ifthetransformercannotbegrounded,thenanisolation
transformermustbeinstalledwiththesecondaryofthetransformergrounded.
Warning
Ifapowersystemwithanungroundedsecondaryisused,thelinetogroundEMClter
componentsandlinetogroundMOVprotectionmustbedisconnectedordamageto
thecontrollercanresult.
ToremovethelinetogroundEMCltercomponents,locatethejumpershownbelow.Thejumperisontheleft
handsideofthecontrolleronthemainboard.Movetothedisconnectedpositionshownbelow.
11
Power Supply and Wiring
Section 6 (continued)
ToremovethelinetogroundMOVprotection,locatethejumpershownbelow.Thejumperislocatedbetween
theinputandoutputterminalblocksonthemainboard.Movetothepositionshown.
ForFrameSize1Controllers: ForFrameSizes2and3Controllers:
Resistance grounding and ground fault protection
ConnectingtheWyesecondaryneutraltogroundthrougharesistorisanacceptablemethodofgrounding.
Underashortcircuitsecondarycondition,anyoftheoutputphasestogroundwillnotexceedthenormal
linetolinevoltage.ThisiswithintheratingoftheMOVinputprotectiondevicesonthedrive.Theresistoris
oftenusedtodetectgroundcurrentbymonitoringtheassociatedvoltagedrop.Sincehighfrequencyground
currentcanowthroughthisresistor,careshouldbetakentoproperlyconnectthedrivemotorleadsusing
therecommendedcablesandmethods.Insomecases,multipledrivesononetransformercanproducea
cumulativegroundcurrentthatcantriggerthegroundfaultinterruptcircuit.
Open Delta (consult factory)
Thistypeofcongurationiscommonon230voltsystems.Fromtimetotimeitmaybeencounteredwhere
onlysinglephasepowerisavailableandthree-phasepowerisrequired.Thetechniqueusestwosinglephase
transformerstoderiveathirdphase.Whenusedtopoweradrivethiscongurationmustbederatedtoabout
70%ofthesinglephaseratingofonetransformer.Thissystemprovidespoorregulationanditispossiblethat
onlythetwolineconnectedphaseswillprovidepower.Inthiscasethedrivemustbederatedto50%ofits
rating.(Ex.A20HP230voltdrivenowbecomesa10HP230voltdrive.)
12
Power Supply and Wiring
Section 6 (continued)
Single Phase Connection
Forsmalldriveswithdioderectierfrontenditispossibletorunathreephaseoutputwithasinglephase
input.Onlypartofthethreephaseinputbridgeisused.Ripplecurrentbecomes120Hzratherthan360.This
placesagreaterdemandontheDCltercomponents(capacitorbankandDCchoke).Theresultisthatthe
drivemustbederatedto50%current.
Thechartbelowshowsthefullloadoutputcurrentratingsofthecontrollerwhensinglephaseor3phase
powerisused.IfsinglephaseinputpowerisusedtheMotorOverloadswitchesmustbesetto50%orlower.
Nominal Controller Full Load
HP Rating Output Current Rating
Supply Frame Model 3 Phase 1 Phase 3 Phase 1 Phase
Voltage Size Number Input Input Input Input
1
SPD20050
5.0 2.0 17.8 8.1
SPD20050F
SPD20075
7.5 3.0 26.4 10.9
2
SPD20075F
SPD20100
10.0 5.0 37.0 17.8
SPD20100F
208/230
SPD20150
15.0 7.5 47.4 26.4
3
SPD20150F
SPD20200
20.0 10.0 60.6 33.0
SPD20200F
SPD20250
25.0 12.0 76.0 40.2
4
SPD20250F
SPD20300
30.0 15.0 94.0 47.4
SPD20300F
SPD40050
5.0 8.9
1
SPD40050F
SPD40075
7.5 13.2
SPD40075F
SPD40100
10.0 18.5
SPD40100F
460
2
SPD40150
15.0 23.7
SPD40150F
SPD40200
20.0 30.3
SPD40200F
SPD40250
25.0 37.5
3
SPD40250F
SPD40300
30.0 47.0
SPD40300F
13
Power Supply and Wiring
Section 6 (continued)
Conduit, Wire and Fuse Sizing
Theuseofmetalconduitwithmetalconduitconnectorsisrecommendedforallelectricalconnections.Usethe
NECorCECtodeterminetherequiredconduitsizefortheapplication.
Refertothechartbelowfortheminimumallowablewiresizeforeachcontroller.Notethatthesewiresizes
arenotadjustedforvoltagedropduetolongcablelengths.Refertothewiresizingchartintheappendixto
determinethemaximumlengthfortheinputcable.Refertothemotormanualformaximumoutputcable
length.Themaximumrecommendedvoltagedroponbothinputandoutputcablecombinedis5%.Standard
wiresizingchartsgivemaximumcablelengthsforonlyinputoroutputcables.Becauseofthisthelengths
giveninthetablemustbeadjustedsothetotalvoltagedropdoesnotexceed5%.Forexample,iftheinput
wiresizingchartintheappendixgivesthemaximumlengthof400'andonly100'isusedthenonly25%ofthe
totalvoltagedrop(1.25%drop)isused.Themaximumoutputcablelengthreadfromthemotor‘swiresizing
chartmustthenbeadjustedto75%ofitsvaluesothatthemaximumvoltagedropof5%isnotexceeded.
UseonlyfastactingclassTfuses.ThewireusedfortheinputpowerconnectionsonmodelsSPD20300and
SPD20300Fmusthaveatemperatureratingof90ºCminimum.Allotherwiremustberated75ºCminimum.
Thechartbelowshowstherecommendedsizesforwireandfusesforeachcontroller.Notethatthewiresizes
werenotadjustedforvoltagedropduetolongcablelengths.
Maximum Ambient Temperature 20ºC 30ºC 40ºC 50ºC
Generator Input Output Input Output Input Output Input Output
Voltage Frame Model Full Load Nominal Fuse Size Cable Cable Cable Cable Cable Cable Cable Cable
Size Number Output Current HP Size (VA) Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG
1
SPD20050
17.8 5.0 30.0 7700 10 14 10 14 10 12 8 12
SPD20050F
SPD20075
26.4 7.5 40.0 11400 8 12 8 10 8 10 6 8
2
SPD20075F
SPD20100
37.0 10.0 50.0 16000 8 10 8 8 6 8 4 8
SPD20100F
SPD20150
47.4 15.0 70.0 20500 4 8 4 8 4 6 3 6
230
3
SPD20150F
SPD20200
60.6 20.0 80.0 26200 4 6 4 6 4 4 2 4
SPD20200F
SPD20250
76.0 25.0 110.0 32800 2 4 2 4 1 3 1/0 2
4
SPD20250F
SPD20300
94.0 30.0 135.0 40600 2* 3 1* 3 1* 2 1/0* 1
SPD20300F
SPD40050
8.9 5.0 15.0 7700 14 14 14 14 14 14 14 14
1
SPD40050F
SPD40075
13.2 7.5 20.0 11400 12 14 12 14 12 14 10 14
SPD40075F
SPD40100
18.5 10.0 30.0 16000 10 14 10 14 10 12 8 12
SPD40100F
460
2
SPD40150
23.7 15.0 40.0 20500 8 12 8 12 8 10 6 10
SPD40150F
SPD40200
30.3 20.0 50.0 26200 8 10 8 10 6 10 4 8
SPD40200F
SPD40250
37.5 25.0 60.0 32400 6 8 6 8 4 8 4 8
3
SPD40250F
SPD40300
47.0 30.0 70.0 40600 4 8 4 8 4 6 3 6
SPD40300F
*90ºCWireRequiredoninputtocontroller.
14
WARNING
Hazardous
voltage
WARNING
Hazardous
voltage
Section 6 (continued)
Input Power and Line Transformer Requirements
Thelineinputvoltageandtransformerpowermustmeetcertainphaseandbalancerequirements.If you or
your installing electrical contractor is in doubt of the requirements, the following provide guidelines
for installation. When in doubt contact the local power utility or the factory.
Beforeconnectingpowertothecontrollermeasurethelinetolineandlinetogroundvoltagefromthepower
source.Thelinetolinevoltagemustbeintherangeof195Vacto265Vac(230V+/–15%)for230Vmodels
and391Vacto529Vac(460V+/–15%)for460Vmodels.Themaximumphasetophaseimbalanceis+/–3%.
Ifthephasetophaseimbalanceisgreaterthan+/–3%thenanisolationtransformermaybenecessary.The
linetogroundvoltagemustbelessthan110%ofthenominal(230Vor460V)linetolinevoltage.Ifthelineto
groundvoltageisnotinthisrangetheEMClterandMOVcomponentsmayneedtoberemoved(seesectionon
“Ungroundedsecondary”transformers)oranisolationtransformerwithagroundedsecondarymaybenecessary.
Ifanisolationtransformerisused,thebestchoiceisONEthreephase,sixwindingtransformer.Adeltaprimary
isbestforthirdharmoniccancellation.Awyesecondaryavoidscirculatingcurrentproblemsandprovidesthe
verydesirableoptionofgroundingthesecondaryneutralforminimumvoltagestressandrippletoground.The
transformershouldhaveaKVAratingatleast1.1timesthemaximumconnectedHP.AKfactorof6issufcient
iftransformerimpedenceisgreaterthan2%.AKFactorof5issufcientiftransformerimpedenceisgreater
than3%.ThetransformermanufacturermayprovidederatingfornonKFactorratedtransformerstooperateat
thedriveproducedKFactorlevels.
Othertransformercongurationsareacceptable.Three single phase transformers can be used if they are
identical for phase to phase symmetry and balance.Awyeconnectedprimaryneutralshouldneverbe
grounded.Greatcareshouldbetakenwithdeltaprimarydeltasecondarycongurations.Anylackofphaseto
phasesymmetrycouldresultincirculatingcurrentsandunacceptabletransformerheating.
Warning
Neverusephaseconverterswithdrivesasnuisancetrippingandpossibledamagemay
occur.Instead,usesinglephaseinputpowerand50%deratefactor.
Warning
“OpenDelta”powersystemsshouldbesizedusingthe50%deratefactor.
Consultfactory.
Section 7
Output Power Connections
Runthemotorleadwirefromthemotororconduitboxthroughmetalconduittothebottomofthe
controller.Usemetalconduitandmetalconduitconnectors.SizetheconduitsaccordingtotheNEC,
CECorlocalcodes.Connectconduitandinsertthewiresthroughthesecondorthirdopeningfromthe
left.Choosetheopeningthattsorislargerthantheconduitused.Iftheopeningislargerthantheconduit,
useconduitbushingstoattachtheconduittothecontroller.
Power Supply and Wiring
Hazardous
voltage
DANGER
Starting the System
15
Hazardous
voltage
DANGER
Hazardous
voltage
DANGER
Hazardous
voltage
DANGER
Hazardous
voltage
DANGER
Starting the System
Section 7 (continued)
Consultmotormanualtodeterminethewiresizefortheapplication.Ensurethegroundconnectiontothemotor
iscontinuous.ConnectwirestotheoutputterminalblocklabeledT1/U,T2/V,T3/W,andGND/.Connectthe
groundwiretotheterminallabeledGND/.ConnecttheotherphaseleadstoT1/U,T2/VandT3/W.
ForCentriProMotors,connectingT1/UtoRed,T2/VtoBlackandT3/WtoYellowwillgivethecorrectrotation.
Danger
Thecontrollerhashighleakagecurrenttoground.Theoutputterminalsmarked
“GND”or“”mustbedirectlyconnectedtothemotorground.Failuretoproperly
groundthecontrollerormotorwillcreateanelectricalshockhazard.
Input Power Connections
MakesuredisconnectswitchesorcircuitbreakersaresecurelyintheOFFpositionbeforemakingthis
connection.Runtheinputpowerwiresfromthefuseddisconnectthroughmetalconduittothebottom
ofthecontroller.Usemetalconduitandmetalconduitconnectors.Sizetheconduitsaccordingtothe
NEC,CECorlocalcodes.Usethewiresizingchartintheappendixtodeterminethesizeoftheinputpowerwires.
Connecttheconduitandinsertthewiresintothefarleftopeningonthecontroller.Connectwirestothe“INPUT”
terminalblock.ConnectthegroundwiretotheterminallabeledGND.Forthreephaseinput,connecttheinput
phasewirestoL1,L2andL3.Forsinglephaseinput,connecttheinputwirestoL1andL3.Ifsinglephaseinputis
usedthemotoroverloadswitchesmustbesetto50%orlower.
Caution
ThewireusedforinputpowerconnectionsonmodelsSPD20300andSPD20300Fmusthavea
temperatureratingof90ºC minimum.
Danger
Thecontrollerhasahighleakagecurrenttoground.Theinputterminalsmarked“GND”
mustbedirectlyconnectedtotheserviceentranceground.Failuretoproperlygroundthe
controllerormotorwillcreateanelectricalshockhazard.
Note
IfsinglephaseinputpowerisusedtheMotorOverloadswitchesmustbesetto50%orloweror
nuisanceinputphaselosserrorscanresult.
Note
DonotuseGFCIprotectionwiththiscontroller.Nuisancetrippingwillresult.
Danger
StatusCodeIndicatorLightisnotavoltageindicator!Alwaysturnoffdisconnect
switchandcircuitbreakerandwait5minutesbeforeservicing.
Danger
Thecontrollerwillremainelectricallychargedfor5minutesafterpoweristurnedoff.
Wait5minutesafterdisconnectingpowerbeforeopeningcontrolleraccesscoveras
thereisasevereshockhazard.
Hazardous
voltage
DANGER
16
Starting the System
Section 7 (continued)
Setting the Motor Overload Switches
TheMotorOverloadSettingSwitchesadjustthelevelofmotoroverloadcurrent
protectionnecessarytoprotectthemotorincaseofanovercurrentcondition.
Bank1switches1,2and3allowadjustmentofthemotoroverloadsetting.
Theseswitchesadjustthemotoroverloadprotectionasapercentageofthefull
loadoutputcurrentratingofthecontroller.Chooseamotoroverloadsettingthat
meetsorislessthanthemotor’sSFArating.Forexample,ifthefullloadoutput
currentratingofthecontrolleris37AandthemotorSFAratingis33A,themotor
overloadsettingshouldbesetto85%(33A/37A=89%,nextlowestsettingis
85%).
Inapplicationswherethepumpandmotorarenotusedtothefullcapacitythe
systemmaynotdrawcurrentclosetothemotor’sSFArating.Inthiscasechoose
amotoroverloadsettingthatisclosetotheactualfullloadrunningcurrent.
Note
Ifsinglephaseinputpowerisusedthemotoroverloadswitchesmustbesetto50%orloweror
nuisanceinputphaselosserrorscanresult.
Thechartbelowshowsthemotoroverloadsettingforeachmodel.
Motor Overload Setting
Supply Frame Model
100% 95% 90% 85% 80% 70% 50% 40%
Voltage Size Number
1
SPD20050
17.8 16.9 16.0 15.1 14.2 12.5 8.9 7.1
SPD20050F
SPD20075
26.4 25.1 23.8 22.4 21.1 18.5 13.2 10.6
2
SPD20075F
SPD20100
37.0 35.2 33.3 31.5 29.6 25.9 18.5 14.8
SPD20100F
208/230
SPD20150
47.4 45.0 42.7 40.3 37.9 33.2 23.7 19.0
3
SPD20150F
SPD20200
60.6 57.6 54.5 51.5 48.5 42.4 30.3 24.2
SPD20200F
SPD20250
76.0 72.2 68.4 64.6 60.8 53.2 38.0 30.4
4
SPD20250F
SPD20300
94.0 89.3 84.6 79.9 75.2 65.8 47.0 37.6
SPD20300F
SPD40050
8.9 8.5 8.0 7.6 7.1 6.2 4.5 3.6
1
SPD40050F
SPD40075
13.2 12.5 11.9 11.2 10.6 9.2 6.6 5.3
SPD40075F
460
SPD40100
18.5 17.6 16.7 15.7 14.8 13.0 9.3 7.4
SPD40100F
2
SPD40150
23.7 22.5 21.3 20.1 19.0 16.6 11.9 9.5
SPD40150F
SPD40200
30.3 28.8 27.3 25.8 24.2 21.2 15.2 12.1
SPD40200F
SPD40250
37.5 35.6 33.8 31.9 30.0 26.3 18.8 15.0
3
SPD40250F
SPD40300
47.0 44.7 42.3 40.0 37.6 32.9 23.5 18.8
SPD40300F
17
Section 7 (continued)
Caution
FailuretoproperlysettheMotorOverloadSettingswitchescanresultinlossofmotoroverload
protectionandwillvoidthemotorwarranty.Nuisancetrippingormotordamagecanoccurifthese
switchesarenotsetproperly.
Setting the Acceleration/Deceleration Switches
Switch4frombank1andswitches1and2frombank2controltheacceleration/decelerationramptimes.The
acceleration/decelerationswitches(ACCEL/DECELRAMPSETTINGS)controlhowfastthecontrollerwillchange
thespeedofthemotor.Therampsettingisthetimeittakesthemotortochangefromminimumspeedto
maximumspeed.Forexample,iftherampsettingissetto1secondandtheminimumspeedissetto30Hz,the
motorwillrampupfrom30Hzto60Hzin1second.Afasterrampsettingshouldbeusedinsystemswherethe
owratecanchangequickly.Thismeansthatthemotorcanreactfastertomaintainthesetpressure.Aslower
rampsettingshouldbeusedinsystemswheretheowratechangesslowlyorwherefastchangesinspeed
cancausewaterhammerorpressuresurges.
Setting the No Water Restart Time Switches
Switches3and4frombank2controlthenowaterrestarttime.Thenowater(drywell)restarttimeswitches
controlthetimebetweenanowater(drywell)errorandtherestartofthesystem.Forexample,ifthenowater
restarttimeswitchesaresetto30minutes,thesystemwillrestart30minutesafteranowater(drywell)error
hasbeendetected.Forthe10minuterestarttime,thecontrollerwillnotrestartif5faultsaredetectedwithin60
minutes.Allothersettingswillcontinuetorestartafterthechosenrestarttime.
Note
Failuretoproperlysetthemotoroverloadswitchescanresultinnuisancenowater(drywell)
faults.
Setting the Minimum Frequency Switch
Switch1frombank3controlstheminimumfrequency.Theminimumfrequencyswitchcontrolstheslowest
speedthatthemotorwillrun.Forsubmersiblepump/motorapplicationstheseswitchesmustalwaysbesetto
30Hzminimumspeed.Forabovegroundapplicationswithhighsuctionpressure,the15Hzsettingcanbeusedto
preventpressureoscillationatlowspeeds.Insomecasesthesuctionpressuremaybehighenoughthatthepump
exceedsthepressuresettingat30Hz.Inthiscasethe15Hzsettingcanbeused.
Caution
Failuretoproperlysettheminimumfrequencyswitchcanresultinmotordamageandwillvoidthe
motorwarranty.Theminimumfrequencymustbesetto30Hzforsubmersibleapplications.
Setting the Carrier Frequency Switch
Switch2frombank3controlsthecarrierfrequency.FormodelnumberswithouttheFsufx,theswitchcanbe
usedtochangetheoutputcarrierfrequencytoavoidaudiblenoiseissuesinabovegroundapplications.For
modelnumberswiththeFsufx,thisswitchisdisabledandthecarrierfrequencyisalwayssetto2kHz.
Starting the System
18
Starting the System
Hazardous
voltage
DANGER
Section 7 (continued)
Setting the Pressure
Whenpowerisappliedthepumpwillstartandthesystempressurewillincreasetothefactorypresetpressure
(50PSIifSP1isenabledanda300PSIsensorisusedor75PSIifSP2isenabledanda300PSIsensorisused).
Afterthepressurehasstabilized,usetheincrease(INC)ordecrease(DEC)pressureadjustpushbuttonstoadjust
thepressuresetting.Push and Holdtheincreaseordecreasepushbuttonuntilthedesiredpressuresettingis
reached.Thenewpressuresettingwillsavewhenthesystemgoesintostandbymode(solidgreenlight/pump
off).Pressuresetpoint1willbeadjustedandstoredwhentheSP2/SP1switchinputisopen.Pressuresetpoint1
ispresetto50PSIwhenusedwitha300PSItransducer.Pressuresetpoint2willbeadjustedandstoredwhen
theSP2/SP1switchinputisclosed.Pressuresetpoint2ispresetto75PSIwhenusedwitha300PSItransducer.
Motor Rotation Direction
Ifthepressure/owseemsloworthesystemisindicatingMotorOverloaderrorcheckthemotorrotation
direction.Turnthebreaker/disconnectswitchtotheoffpositionandwait5minutes.Switchanytwoleadsonthe
controlleroutput(T1/U,T2/VorT3/W).Turnthebreaker/disconnectswitchtotheonposition.Observepressure
andow.Ifthepressureorowstillseemslowcheckplumbing.
ForCentriProMotors,connectingT1/UtoRed,T2/VtoBlackandT3/WtoYellowwillgivethecorrectrotation.
Note
Itispossibleforthepumptomaintainconstantpressurewithalowoworahighsuctionhead
evenifthepumpisrotatingbackwards.Whilethepumpisrunninguseanampprobeononeofthe
outputpowerleadsconnectedtothemotorandcomparethecurrentdrawbetweenthetworotation
directions.Thelowestcurrentreadingindicatesthepumpisrunninginthecorrectdirection.
System Status
Thestatusindicatorlightdisplaysthestatusofthecontroller.Aconstantgreenstatuscodeindicatesthatthe
pumpisinstandbymode(pumpnotrunning).Ablinkinggreenstatuscodeindicatesthatthepumpisrunning.
Aconstantorangelightindicatestheinputvoltageislow.Ablinkingorconstantredlightindicatesaproblem
withthecontrollerorsystem.Refertotheaccesscoversidepanelforalistofstatuscodes.SeeSection9formore
details.
Danger
Thestatuscodeindicatorlightisnotavoltageindicator!Alwaysturnoffdisconnect
switchandcircuitbreakerandwait5minutesbeforeservicing.
19
Input and Output Functions
Section 8
Thecontrolterminalstripsallowforavarietyofinputandoutputfunctions.
Warning:Turnoffallpowertothecontrollerbeforewiringdevicestothe
controlterminals.
Warning:InputsRUN/STOP,HAND/AUTO,SP2/SP1andPRESSUREDROPare
switchinputs.Donotconnectpowertotheseinputsordamagetothecontroller
willresult.Onlyconnectnon-poweredswitchcontactstotheseinputs.
RUN/STOP:Thisinputallowsthepump/motortobeturnedonandoffbyan
externalswitch.Connectthecontactsofanon-poweredexternalswitchto
terminals1(COM)and2(RUN/STOP).Whentheswitchisclosedthecontroller
isinRUNmode(outputtomotorisenabled).Whentheswitchisopenthe
controllerisinSTOPmode(outputtomotorisdisabled).
HAND/AUTO:Thisinputallowsthecontrollertorunthemotoratfullspeed
withouttheuseofapressuretransducer.Thisinputcanbecontrolledbyan
externalnon-poweredswitch.Connectthecontactsofanon-poweredexternal
switchtoterminals3(COM)and4(HAND/AUTO).Whentheswitchisclosedthe
controllerisinHANDmode.WhileinHANDmodetheRUN/STOPinputisusedtostartandstopthemotorandthe
pressuretransducerinputisignored.WhentheswitchisopenthecontrollerisinAUTOmode.WhileinAUTOmode
thecontrollerusesthepressuretransducerfeedbacktocontrolthespeedofthemotor.
INPUT and +24V:Theseterminalsarethetransducerfeedbackandtransducerpowersupply.Connectthewhite
leadfromthetransducercabletoterminal6(INPUT).Connectthebrownleadfromthetransducercabletoterminal7
(+24V).Connectingthedrain(bare)wiretothechassisallowsgroundingofthecaseofthepressuretransducer.The
controllerisconguredwitha300PSI4-20mAoutputpressuretransducer.
ANALOG OUTPUT:Thisoutputisa4-20mAsignalbasedonmotorspeed(4mA=0Hz,20mA=60Hz)andcanbe
connectedtoexternalmonitoringorexternalcontroldevices.Connectterminal10(ANALOGOUTPUT)tothe4-20mA
inputoftheexternaldevice.Connectterminal9(COM)tothenegativesideofthecurrentloopontheexternaldevice.
Theexternaldevicemusthaveaninputresistance(impedance)intherangeof45Ωto250Ω.Themaximumoutput
voltageis24V.
SP2/SP1:Thisinputallowsthesystemtooperateatoneof2pressuresettings.Thisinputcanbecontrolledbyan
externalnon-poweredswitch.Connectthecontactsofanon-poweredexternalswitchtoterminals5(COM)and11
(SP2/SP1).Whentheswitchisclosedpressuresetpoint2isenabled(presetto75PSIwhenusedwitha300PSI
transducer).Whentheswitchisopenpressuresetpoint1isenabled(presetto50PSIwhenusedwitha300PSI
transducer).
PRESSURE DROP:Thisinputallowstheusertoselecttheamountofpressuredropinthesystembeforethepump
starts.Thisinputcanbecontrolledbyanexternalnon-poweredswitch.Connectthecontactsofanon-powered
externalswitchtoterminals5or9(COM)and12(PRESSUREDROP).Whentheswitchisclosedthesystempressure
willdrop20PSI(whenusedwitha300PSItransducer)beforerestartingthepump.Whentheswitchisopenthe
systempressurewilldrop5PSI(whenusedwitha300PSItransducer)beforerestartingthepump.
RUN RELAY:Thisoutputindicateswhenthepump/motorisrunning.Thisoutputcanbeusedtocontrolpowertoa
light,analarmorotherexternaldevice.Whenthepump/motorisoffterminal13(RELAY1–NO)willbeopenand
terminal14(RELAY1–NC)willbeconnectedtoterminal15(RELAY1–COM).Whenthepump/motorisonterminal
13(RELAY1–NO)willbeconnectedtoterminal15(RELAY1–COM)andterminal14(RELAY1–NC)willbeopen.
Therelayratingis250Vac,5ampsmaximum.
FAULT RELAY:Thisoutputindicateswhenthesystemisfaulted.Thisoutputcanbeusedtocontrolpowertoalight,
analarmorotherexternaldevice.Whenthesystemisnotfaultedterminal16(RELAY2–NO)willbeopenand
terminal17(RELAY2–NC)willbeconnectedtoterminal18(RELAY2–COM).Whenthesystemisfaultedterminal
16(RELAY2–NO)willbeconnectedtoterminal18(RELAY2–COM)andterminal17(RELAY2–NC)willbeopen.
Therelayratingis250Vac,5ampsmaximum.
20
Hazardous
voltage
DANGER
Troubleshooting
Section 9
General
TheS-DriveandAquavarSPDdriveareself-diagnosingcontrollers.Ifaproblemoccurs,observetheStatusCode
IndicatorLightonthefrontoftheunit.NoStatusCodeIndicatorLightmeanseithernoorlowinputvoltage(less
than140Vac).
Danger
StatusCodeIndicatorLightisnotavoltageindicator!Alwaysturnoffdisconnectswitch
andcircuitbreakerandwait5minutesbeforeservicing.Highvoltagemaystillremainon
controller.
Refertothestatuscodelabelonthesideofthecontrolleraccesscovertodiagnosesystemerrors.
See the following diagram.
Usethefollowingtabletohelptroubleshootproblems.
No Light
Controller Status Description
Low/NoInputVoltage Checktheinputvoltagetothecontroller.Measuretheinputvoltage
betweenphasesusinganACVoltmeter.Thisvoltageshouldbe
greaterthan140Vacforthestatusindicatorlighttoturnon.
Green Light Codes
Flashes Controller Status Description
Constant Standby ConstantGreenLightindicatesthepumpisoff.Thesystemisin
Standbymodewhenthereisnoowinthesystemandthepressure
settinghasbeenreachedortheRUN/STOPinputissettoSTOP(open
switch).
Blinking PumpRunning FlashingGreenLightindicatesthepumpisrunning.
Red Flashes Fault Code Restart Action
Constant ReplaceController Controllerwillnotrestart.Powermust
beresettoclearthefault.
2Blinks NoWater/LossofPrime Controllerwillrestartautomatically
accordingtotheNoWaterRestartTime
switches(switches3&4ofbank2).
3Blinks SensorFault Controllerwillrestartautomaticallywhen
thesensorsignaliswithinthevalid
operatingrange.
4Blinks PumporMotorBound Controllerwillrestartautomatically5
times.After5faultsthepowermustbe
resettoclearthefault.
5Blinks ShortCircuit/GroundFault Controllerwillnotrestart.Powermustbe
resettoclearthefault.
6Blinks InputPhaseLoss Controllerwillrestartautomatically5times.
After5faultsthepowermustberesetto
clearthefault.
7Blinks Temperature Controllerwillrestartautomaticallywhen
temperatureiswithintheoperatingrange
ofthecontroller.
8BLINKS OverVoltage Controllerwillrestartautomaticallywhen
theinputvoltageiswithintheoperating
rangeofthecontroller.
9Blinks MotorOverload Controllerwillrestartautomatically.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

ITT S-DRIVE IM213 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI