Johnson Controls VRF System Engineering Manual

Category
Split-system air conditioners
Type
Engineering Manual
ENGINEERING MANUAL
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
Engineering Manual
TC-16002
Technical Catalog for Outdoor Unit
< Indoor Units >
●2-WayCassetteType
(H,Y,C)IC2018B21S
(H,Y,C)IC2024B21S
TC-16002-rev.1
i
IMPORTANT NOTICE AND SAFETY SUMMARY
1. Introduction
2. Important Safety Instructions
Thismanualshouldbeconsideredasapermanentpartoftheairconditioningequipmentandshould
remainwiththeairconditioningequipment.
(Transportation/InstallationWork)>(RefrigerantPipingWork)>(ElectricalWiringWork)>(Ref.ChargeWork)>(Test
Run)>(User)
ThisEngineeringManualconcentratesonheatpumpairconditioningunits.Readthismanualcarefully
beforeperforminginstallationsoroperations.
Signal Words
Indicatesahazardoussituationthat,ifnotavoided,couldresultindeathor
seriousinjury.
Indicatesahazardoussituationthat,ifnotavoided,couldresultinminoror
moderateinjury.
Indicatesinformationconsideredimportant,butnothazard-related
(forexample,messagesrelatingtopropertydamage).
General Precautions
Toreducetheriskofseriousinjuryordeath,readtheseinstructions
thoroughlyandfollowallwarningsorcautionsincludedinallmanualsthat
accompaniedtheproductandareattachedtotheunit.Referbacktothese
instructionsasneeded.
ThissystemshouldbeinstalledbypersonnelcertiedbyJohnsonControls,Inc.Personnelmustbe
qualiedaccordingtolocal,stateandnationalbuildingandsafetycodesandregulations.Incorrect
installationcouldcauseleaks,electricshock,reorexplosion.InareaswhereSeismic‘’Performance
requirementsarespecied,theappropriatemeasuresshouldbetakenduringinstallationtoguard
againstpossibledamageorinjurythatmightoccurinanearthquakeiftheunitisnotinstalled
correctly,injuriesmayoccurduetoafallingunit.
UseappropriatePersonalProtectiveEquipment(PPE),suchasglovesandprotectivegogglesand,
whereappropriate,haveagasmasknearby.Alsouseelectricalprotectionequipmentandtools
suitedforelectricaloperationpurposes.Keepaquenchingclothandareextinguishernearbyduring
brazing.Usecareinhandling,rigging,andsettingofbulkyequipment.
Whentransporting,becarefulwhenpickingup,movingandmountingtheseunits.Althoughthe
unitmaybepackedusingplasticstraps,donotusethemfortransportingtheunitfromonelocation
toanother.Donotstandonorputanymaterialontheunit.Getapartnertohelp,andbendwith
yourkneeswhenliftingtoreducestrainonyourback.Sharpedgesorthinaluminumnsontheair
conditionercancutngers,sowearprotectivegloves.
Donottouchoradjustanysafetydevicesinsidetheindoororoutdoorunits.Allsafetyfeatures,
disengagement,andinterlocksmustbeinplaceandfunctioningcorrectlybeforetheequipmentis
putintooperation.Ifthesedevicesareimproperlyadjustedortamperedwithinanyway,aserious
accidentcanoccur.Neverbypassorjump-outanysafetydeviceorswitch.
JohnsonControlswillnotassumeanyliabilityforinjuriesordamagecausedbynotfollowingsteps
outlinedordescribedinthismanual.UnauthorizedmodicationstoJohnsonControlsproductsare
prohibitedasthey…
Maycreatehazardswhichcouldresultindeath,seriousinjuryorequipmentdamage.
Willvoidproductwarranties.
Mayinvalidateproductregulatorycertications.
MayviolateOSHAstandards.
ii
TC-16002-rev.1
Takethefollowingprecautionstoreducetheriskofpropertydamage.
Becarefulthatmoisture,dust,orvariantrefrigerantcompoundsnotentertherefrigerantcycleduring
installationwork.Foreignmattercoulddamageinternalcomponentsorcauseblockages.
Ifairltersarerequiredonthisunit,donotoperatetheunitwithouttheairltersetinplace.Iftheair
lterisnotinstalled,dustmayaccumulateandbreakdownmayresult.
Donotinstallthisunitinanyplacewheresilicongasescancoalesce.Ifthesilicongasmolecules
attachthemselvestothesurfaceoftheheatexchanger,thennedsurfaceswillrepelwater.Asa
result,anyamountofdrainagemoisturecondensatecanoverowfromthedraincondensatepanand
couldruninsideoftheelectricalbox,possiblycausingelectricalfailures.
Wheninstallingtheunitinahospitalorotherfacilitywhereelectromagneticwavesaregenerated
fromnearbymedicaland/orelectronicdevices,bepreparedfornoiseandelectronicinterference
ElectromagneticInterference(EMI).Donotinstallwherethewavescandirectlyradiateintothe
electricalbox,controllercable,orcontroller.Inverters,appliances,high-frequencymedicalequipment,
andradiocommunicationsequipmentmaycausetheunittomalfunction.Theoperationoftheunit
mayalsoadverselyaffectthesesamedevices.Installtheunitatleast10ft.(approximately3m)away
fromsuchdevices.
Whenawirelesscontrollerisused,locateatadistanceofatleast3.3ft.(approximately1m)between
theindoorunitandelectriclighting.Ifnot,thereceiverpartoftheunitmayhavedifcultyreceiving
operationcommands.
Donotinstalltheunitinanylocationwhereanimalsandplantscancomeintodirectcontactwiththe
outletairstream.Exposurecouldadverselyaffecttheanimalsandplants.
Donotinstalltheunitwithanydownwardslopetothesideofthedrainboss.Ifyoudo,youmayhave
drainwaterowingbackwhichmaycauseleaks.
Besurethedrainhosedischargeswaterproperly.Ifconnectedincorrectly,itmaycauseleaks.
Donotinstalltheunitinanyplacewhereoilcanseepontotheunits,suchastableorseatingareasin
restaurants,andsoforth.Fortheselocationsorsocialvenues,usespecializedunitswithoil-resistant
featuresbuiltintothem.Inaddition,useaspecializedceilingfandesignedforrestaurantuse.These
specializedoil-resistantunitscanbeorderedforsuchapplications.However,inplaceswherelarge
quantitiesofoilcansplashontotheunit,suchasafactory,eventhespecializedunitscannotbeused.
Theseproductsshouldnotbeinstalledinsuchlocations.
Ifthewiredcontrollerisinstalledinalocationwhereelectromagneticradiationisgenerated,make
surethatthewiredcontrollerisshieldedandcablesaresleevedinsideconduittubing.
Ifthereisasourceofelectricalinterferencenearthepowersource,installnoisesuppression
equipment(lter).
Duringthetestrun,checktheunit’soperationtemperature.Iftheunitisusedinanenvironment
wherethetemperatureexceedstheoperationboundary,itmaycauseseveredamage.Checkthe
operationaltemperatureboundaryinthemanual.Ifthereisnospeciedtemperature,usetheunit
withintheoperationaltemperatureboundaryof35to104°F(0to40°C).
ReadinstallationandappropriateusermanualsforconnectionwithPCorperipheraldevices.Ifa
warningwindowappearsonthePC,theproductstops,doesnotworkproperlyorworksintermittently,
immediatelystopusingtheequipment.
TC-16002-rev.1
iii
Installation Precautions
Toreducetheriskofseriousinjuryordeath,thefollowinginstallation
precautionsmustbefollowed.
Wheninstallingtheunitinto…
Awall:Makesurethewallisstrongenoughtoholdtheunit’sweight.Itmaybenecessaryto
constructastrongwoodormetalframetoprovideaddedsupport.
Aroom:Properlyinsulateanyrefrigeranttubingruninsidearoomtoprevent“sweating”thatcan
causedrippingandwaterdamagetowallandoors.
Damporunevenareas:Usearaisedconcretepadorconcreteblockstoprovideasolid,level
foundationfortheunittopreventwaterdamageandabnormalvibration.
Anareawithhighwinds:Securelyanchortheoutdoorunitdownwithboltsandametalframe.
Provideasuitableairbafe.
Asnowyarea(onlyforHeatPumpModel):Installtheoutdoorunitonaraisedplatformthatis
higherthandriftingsnow.Providesnowvents.
Iftheremotesensorsarenotusedwiththiscontroller,thendonotinstallthiscontroller…
inaroomwherethereisnothermostat.
wheretheunitisexposedtodirectsunshineordirectlight.
wheretheunitwillbeincloseproximitytoaheatsource.
wherehot/coldairfromtheoutdoors,oradraftfromelsewhere(suchasairvents,diffusersor
grilles)canaffectaircirculation.
inareaswithpooraircirculationandventilation.
Donotinstalltheunitinthefollowingplaces.Doingsocanresultinanexplosion,re,deformation,
corrosion,orproductfailure.
Explosiveorammableatmosphere.
Wherere,oil,steam,orpowdercandirectlyentertheunit,suchasincloseproximityordirectly
aboveakitchenstove.
Whereoil(includingmachineryoil)maybepresent.
Wherecorrosivegasessuchaschlorine,bromine,orsuldecanaccumulate,suchasnearahot
tuborhotspring.
Wheredense,salt-ladenairowisheavy,suchasincoastalregions.
Wheretheairqualityisofhighacidity.
Whereharmfulgasescanbegeneratedfromdecomposition.
Donotpositionthedrainpipefortheindoorunitnearanysanitarysewerswherecorrosivegases
maybepresent.Ifyoudo,toxicgasescanseepintobreathableairspacesandcancauserespiratory
injuries.Ifthedrainpipeisinstalledincorrectly,waterleakageanddamagetotheceiling,oor,
furniture,orotherpossessionsmayresult.Ifcondensatepipingbecomesclogged,moisturecanback
upandcandripfromtheindoorunit.Donotinstalltheindoorunitwheresuchdrippingcancause
moisturedamageorunevenlocations:Usearaisedconcretepadorconcreteblockstoprovidea
solid,levelfoundationfortheunittopreventwaterdamageandabnormalvibration.
Beforeperforminganybrazingwork,besurethattherearenoammablematerialsoropenames
nearby.
Performatestruntoensurenormaloperation.Safetyguards,shields,barriers,covers,andprotective
devicesmustbeinplacewhilethecompressor/unitisoperating.Duringthetestrun,keepngersand
clothingawayfromanymovingparts.
Cleanupthesitewhennished,rememberingtocheckthatnometalscrapsorbitsofwiringhave
beenleftinsidetheunitbeinginstalled.
Duringtransportation,donotallowthebackrestoftheforkliftmakecontactwiththeunit,otherwise,
itmaycausedamagetotheheatexchangerandalsomaycauseinjurywhenstoppedorstarted
suddenly.
Removegasinsidetheclosingpipewhenthebrazingworkisperformed.Ifthebrazingllermetalis
meltedwithremaininggasinside,thepipeswillbeblownoffanditmaycauseinjury.
Besuretousenitrogengasforanairtighttest.Ifothergasessuchasoxygengas,acetylenegasor
uorocarbongasareaccidentallyused,itmaycauseexplosionorgasintoxication.
Afterinstallationworkforthesystemhasbeencompleted,explainthe“SafetyPrecautions,”theproperuse
andmaintenanceoftheunittothecustomeraccordingtotheinformationinallmanualsthatcamewiththe
system.AllmanualsandwarrantyinformationmustbegiventotheuserorleftneartheIndoorUnit.
iv
TC-16002-rev.1
Refrigerant Precautions
Toreducetheriskofseriousinjuryordeath,thefollowingrefrigerant
precautionsmustbefollowed.
Asoriginallymanufactured,thisunitcontainsrefrigerantinstalledbyJohnsonControls.Johnson
Controlsusesonlyrefrigerantsthathavebeenapprovedforuseintheunit’sintendedhomecountry
ormarket.JohnsonControlsdistributorssimilarlyareonlyauthorizedtoproviderefrigerantsthat
havebeenapprovedforuseinthecountriesormarketstheyserve.Therefrigerantusedinthisunit
isidentiedontheunit’sfaceplateand/orintheassociatedmanuals.Anyadditionsofrefrigerantinto
thisunitmustcomplywiththecountry’srequirementswithregardtorefrigerantuseandshouldbe
obtainedfromJohnsonControlsdistributors.Useofanynon-approvedrefrigerantsubstituteswillvoid
thewarrantyandwillincreasethepotentialriskofinjuryordeath.
Ifinstalledinasmallroom,takemeasurestopreventtherefrigerantfromexceedingthemaximum
allowableconcentrationintheeventthatrefrigerantgasesshouldescape.Refrigerantgasescan
causeasphyxiation(0.026lbs/ft
3
(0.42kg/m
3
)basedonISO5149forR410A).Consultwithyour
distributorforcountermeasures(ventilationsystemandsoon).Ifrefrigerantgashasleakedduringthe
installationwork,ventilatetheroomimmediately.
Checkthedesignpressureforthisproductis601psi(4.15MPa).Thepressureoftherefrigerant
R410Ais1.4timeshigherthanthatoftherefrigerantR22.Therefore,therefrigerantpipingfor
R410AshallbethickerthanthatforR22.Makesuretousethespeciedrefrigerantpiping.Ifnot,the
refrigerantpipingmayraptureduetoanexcessiverefrigerantpressure.Besides,payattentionto
thepipingthicknesswhenusingcopperrefrigerantpiping.Thethicknessofcopperrefrigerantpiping
differsdependingonitsmaterial.
TherefrigerantR410Aisadopted.Therefrigerantoiltendstobeaffectedbyforeignmatterssuch
asmoisture,oxidelm,(orfat).Performtheinstallationworkwithcaretopreventmoisture,dust,or
differentrefrigerantfromenteringtherefrigerantcycle.Foreignmattercanbeintroducedintothecycle
fromsuchpartsasexpansionvalveandtheoperationmaybeunavailable.
Toavoidthepossibilityofdifferentrefrigerantorrefrigerantoilbeingintroducedintothecycle,the
sizesofthechargingconnectionshavebeenchangedfromR407CtypeandR22type.Itisnecessary
topreparetheappropriatetoolsbeforeperforminginstallationwork.
UserefrigerantpipesandjointswhichareapprovedforusewithR410A.
Acompressor/unitcomprisesapressurizedsystem.Neverloosenthreadedjointswhilethesystemis
underpressureandneveropenpressurizedsystemparts.
Beforeinstallationiscomplete,makesurethattherefrigerantleaktesthasbeenperformed.If
refrigerantgasesescapeintotheair,turnOFFthemainswitch,extinguishanyopenamesand
contactyourservicecontractor.Refrigerant(Fluorocarbon)forthisunitisodorless.Iftherefrigerant
shouldleakandcomeintocontactwithopenames,toxicgascouldbegenerated.Also,becausethe
uorocarbonsareheavierthanair,theysettletotheoor,whichcouldcauseasphyxiation.
Wheninstallingtheunit,andconnectingrefrigerantpiping,keepallpipingrunsasshortas
possible,andmakesuretosecurelyconnecttherefrigerantpipingbeforethecompressorstarts
operating.Iftherefrigerantpipingisnotconnectedandthecompressoractivateswiththestop
valveopened,therefrigerantcyclewillbecomesubjectedtoextremelyhighpressure,whichcan
causeanexplosionorre.
Tightenthearenutwithatorquewrenchinthespeciedmanner.Donotapplyexcessiveforcetothe
arenutwhentightening.Ifyoudo,thearenutcancrackandrefrigerantleakagemayoccur.
Whenmaintaining,relocating,anddisposingoftheunit,dismantletherefrigerantpipingafterthe
compressorstops.
Whenpipesareremovedoutfromunderthepipingcover,aftertheinsulationworkiscompleted,
coverthegapbetweenthepipingcoverandpipesbyapacking(eld-supplied).Ifthegapisnot
covered,theunitmaybedamagedifsnow,rainwaterorsmallanimalsentertheunit.
Donotapplyanexcessiveforcetothespindlevalveattheendofopening.Otherwise,thespindle
valveiesoutduetorefrigerantpressure.Atthetestrun,fullyopenthegasandliquidvalves,
otherwise,thesedeviceswillbedamaged.(Itisclosedbeforeshipment.)
Ifthearrangementforoutdoorunitsisincorrect,itmaycauseowbackoftherefrigerantandresultin
failureoftheoutdoorunit.
Therefrigerantsystemmaybedamagediftheslopeofthepipingconnectionkitexceeds+15
o
.
TC-16002-rev.1
v
Electrical Precautions
Takethefollowingprecautionstoreducetheriskofelectricshock,reor
explosionresultinginseriousinjuryordeath.
Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagram
andtheseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancause
seriousinjuryordeath.
Performallelectricalworkinstrictaccordancewiththisinstallationandmaintenancemanualandall
therelevantregulatorystandards.
Beforeservicing,openandtagalldisconnectswitches.Neverassumeelectricalpoweris
disconnected.Checkwithmeterandequipment.
Onlyuseelectricalprotectionequipmentandtoolssuitedforthisinstallation.
Insulateawiredcontrolleragainstmoistureandtemperatureextremes.
Usespeciedcablesbetweenunits.
Thenewairconditionermaynotfunctionnormallyinthefollowinginstances:
Ifelectricalpowerforthenewairconditionerissuppliedfromthesametransformerasthedevice*
referredtobelow.
Ifthepowersourcecablesforthisdevice*andthenewairconditionerunitarelocatedinclose
proximitytoeachother.
Device*:(Example):Alift,containercrane,rectierforelectricrailway,inverterpowerdevice,
arcfurnace,electricfurnace,large-sizedinductionmotorandlarge-sizedswitch.
Regardingthecasesmentionedabove,surgevoltagemaybeinductedintothepowersupply
cablesforthepackagedairconditionerduetoarapidchangeinpowerconsumptionofthedevice
andanactivationofaswitch.
Checkeldregulationsandstandardsbeforeperformingelectricalworkinordertoprotectthe
powersupplyforthenewairconditionerunit.
CommunicationcablingshallbeaminimumofAWG18(0.82mm
2
),2-Conductor,StrandedCopper.
ShieldedcablemustbeconsideredforapplicationsandroutinginareasofhighEMIandother
sourcesofpotentiallyexcessiveelectricalnoisetoreducethepotentialforcommunicationerrors.
Whenshieldedcablingisapplied,properbondingandterminationofthecableshieldisrequired
asperJohnsonControlsguidelines.Plenumandriserratingsforcommunicationcablesmustbe
consideredperapplicationandlocalcoderequirements.
Thepolarityoftheinputterminalsisimportant,sobesuretomatchthepolaritywhenusingcontacts
thathavepolarity.
Useanexclusivepowersupplyfortheairconditionerattheunit’sratedvoltage.
Highlydangerouselectricalvoltagesmaybeusedinthissystem.Carefullyrefertothewiringdiagram
andtheseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancause
seriousinjuryordeath.
Beforeinstallingthecontrollerorremotedevices,ensurethattheindoorandoutdoorunitoperation
hasbeenstopped.Further,besuretowaitatleastveminutesbeforeturningoffthemainpower
switchtotheindoororoutdoorunits.Otherwise,waterleakageorelectricalbreakdownmayresult.
DonotopentheservicecoveroraccesspaneltotheindoororoutdoorunitswithoutturningOFFthe
mainpowersupply.Beforeconnectingorservicingthecontrollerorcablestoindoororoutdoorunits,
openandtagalldisconnectswitches.Neverassumeelectricalpowerisdisconnected.Checkwitha
meterandequipment.
ThisequipmentcanbeinstalledwithaGroundFaultCircuitBreaker(GFCI),whichisarecognized
measureforaddedprotectiontoaproperlygroundedunit.Installappropriatesizedbreakers/fuses
/overcurrentprotectionswitches,andwiringinaccordancewithlocal,stateandNECcodesand
requirements.Theequipmentinstallerisresponsibleforunderstandingandabidingbyapplicable
codesandrequirements.
vi
TC-16002-rev.1
- CONTENTS -
1. GeneralInformation(Features).................................................................................................................. 1-1
2. 2-WayCassetteType................................................................................................................................. 2-1
2.1 UnitNomenclature............................................................................................................................. 2-1
2.2 Line-up.............................................................................................................................................. 2-1
2.3 GeneralData..................................................................................................................................... 2-2
2.4 DimensionalData.............................................................................................................................. 2-3
2.5 Structure............................................................................................................................................ 2-4
2.6 ComponentData............................................................................................................................... 2-5
2.7 OperationSpace............................................................................................................................... 2-6
2.8 SensibleHeatFactor(SHF).............................................................................................................. 2-6
2.9 ElectricalData................................................................................................................................... 2-7
2.10 SoundData....................................................................................................................................... 2-8
2.11 ControlSystem.................................................................................................................................. 2-9
2.11.1 RefrigerantSystem.................................................................................................................. 2-9
2.11.2 StandardOperationSequence................................................................................................ 2-10
2.11.3 SafetyandControlDeviceSetting........................................................................................... 2-14
2.11.4 WiringDiagram........................................................................................................................ 2-15
3. OptionalParts............................................................................................................................................ 3-1
3.1 LineUp.............................................................................................................................................. 3-1
3.2 MotionSensorKit:SOR-NED........................................................................................................... 3-2
3.3 AntibacterialLongLifeAirFilter:F-90MD-K1.................................................................................... 3-6
3.4 FilterBox:B-90HD............................................................................................................................ 3-7
3.5 DuctAdapter:PD-150D..................................................................................................................... 3-8
3.6 Infrared(IR)ReceiverKit:C2IRK01.................................................................................................. 3-9
3.7 3PConnectorCable:PCC-1A........................................................................................................... 3-16
3.8 RemoteSensor:THM-R2A................................................................................................................ 3-16
3.9 Relayand3PinConnectorKit:PSC-5RA......................................................................................... 3-17
4. SelectionData............................................................................................................................................ 4-1
4.1 SelectionGuide................................................................................................................................. 4-1
4.2 CapacityTable................................................................................................................................... 4-1
4.2.1 CoolingCapacity...................................................................................................................... 4-1
4.2.2 HeatingCapacity..................................................................................................................... 4-2
IMPORTANTNOTICEANDSAFETYSUMMARY......................................................................................... i
1. Introduction................................................................................................................................................ i
2. ImportantSafetyInstructions..................................................................................................................... i
FEATURES
TC-16002-rev.1
1-1
1. General Information (Features)
VRF Air Conditioners
Johnson Controls proudly introduces new Variable Refrigerant Flow (VRF) air conditioners, a highly-efcient
and reliable air-conditioning system. Recently, increased numbers of buildings are requiring "Intelligent"
facilities that include communication networks, ofce automation, and a comfortable environment. In
particular, a comfortable environment is becoming more of a year-around requirement in ofce buildings.
The VRF multi-split system air conditioner meets these requirements. The proven combination of the scroll
compressor and inverter provides the best air conditioning for small and medium ofce buildings.
VRF System
Johnson Controls has developed the VRF system with its customers in mind.
This system, which is unique in the world, allows the interconnection of indoor units for all our VRF air
conditioners.
This system provides the consumer with greater exibility for installation, which means that the air-
conditioning systems will integrate better within complex facility structures.
Wide Range Line-up
Indoor Unit Type
Capacity (MBH)
6 8 12 15 18 24 30 36
2-Way Cassette (H,Y,C)IC2_B21S
: Available
Table 1.1 Indoor Unit Type List
2-Way Cassette Type Models
(H,Y,C)IC2018B21S and (H,Y,C)IC2024B21S
FEATURES
1-2
TC-16002-rev.1
Improved Heat Exchanger
Optimized for excellent efficiency.
Energy-Efficient Fan Motor
Turbo Fan
Improved Airflow Path with Smooth
Air Inlet
NEW
NEW
NEW
NEW
New Design and High Performance Decorative Panel
The decorative panel has a new, simple, but stylish design applicable to the air inlet at grille. It can be
used as a shutter at the time of OFF operation.
Two louvers have individual adjustment capability with a newly equipped individual louver setting function.
Air Inlet Flat Grille
Horizontal
Air Outlet Angle
Downward
Air Outlet Angle
Up
Swing
Simple and Stylish Design Fully Closed
2-way Individual Louver
Improvement of Energy-Saving
(1) Adopting High Efcient New Turbo Fan and DC Fan Motor
(2) Improvement of Heat Exchanger and Reduction of Airow Loss
(3) Improvement of Energy-Saving Operation by Adopting Motion Sensor
* Adopting Motion Sensor Function
- The motion sensor function can adjust the setting temperature according to human activity and it
controls the airow volume and the airow direction.
- The motion sensor function allows optimized energy-efcient control.
FEATURES
TC-16002-rev.1
1-3
Automatic COOL/HEAT Operation
By improving differential temperature for automatic COOL/HEAT operation, it is possible to perform rened
and sensitive operation and a more comfortable air conditioned environment is realized.
SET TEMP.
Room Air TEMP.
(Indoor Unit Air Intake Temp.)
Thermo-ON: The outdoor unit and some indoor units are running.
Thermo-OFF: The outdoor unit and some indoor units stay on, but don’t run.
Heating Mode
Cooling Mode
Thermo-ON
Thermo-OFF
SET TEMP. +3
o
F (2
o
C)
SET TEMP. -3
o
F (-2
o
C)
Control Flow of AUTO Mode
Easy Maintenance (Adopting New Antibacterial Agent of Drain Pan)
The silver ions antibacterial agent is newly adopted in the drain pan, and
it inhibits generation of mold or bacterium which is the cause of slime.
The antibacterial agent (cased) is xed in the drain pan.
(Exchangeable, term of validity is 10,000 hours of the cooling operation
(Approx. ve years).)
Easy Installation
(1) Easier Height Adjustment
The unit height can be adjusted from four corner
pockets, with the decorative panel attached to the unit.
Height adjustment from the corner pockets is suitable
for ne adjustment.
To keep the unit level, avoid signicant height
adjustment.
Unit Body
Decorative Panel
Corner Pocket
The indoor unit height from
the false ceiling surface can
be adjusted from the corner
pocket with a wrench.
Wrench
(2) Improvement of Drain Pump
High-lift DC drain pump makes it possible to raise the drain pipe straight up, up to 33-7/16 inch
(850mm) from the false ceiling surface.
inch (mm)
Max. Lift Height (H) 33-7/16 (850)
Max. Length (a+b+c) 43-5/16 (1100)
Ceiling
Hose Band (Accessory)
a
(Max. 11-13/16 (300))
Max. H
b
Drain Hose
(Accessory)
39-3/8 to 59-1/16
(1000 to 1500)
Support Part
1/25 to 1/100
Down-Slope
Shorter
if possible.
inch (mm)
c
2-WAY CASSETTE
TC-16002-rev.1
2-1
2. 2-Way Cassette Type
2.1 Unit Nomenclature
Model Descriptions
Example
H I C2 018 B 2 1 S
Nomenclature Description
H = Hitachi Brand
Y = York Brand
C = Coleman Brand
H
Indoor Unit I
Indoor Unit Type
C2 = 2-Way Cassette Type
C2
Capacity (MBH) 018
Refrigerant Type
B = R410A
B
Power Supply
2 = 208/230Volts - 1Phase - 60Hz
2
1 = 1st Generation 1
S = Standard Type S
2.2 Line-up
Type
Capacity
Model
RT MBH
Indoor Unit 2-Way Cassette
1.5 18 (H,Y,C)IC2018B21S
2.0 24 (H,Y,C)IC2024B21S
2-WAY CASSETTE
2-2
TC-16002-rev.1
2.3 General Data
Indoor Unit Type 2-Way Cassette Type
Model (H,Y,C)IC2018B21S (H,Y,C)IC2024B21S
Indoor Unit Power Supply AC 1 Phase, 208/230V, 60Hz
Nominal Cooling Capacity *1 Btu/h 18,000 24,000
(kW) (5.3) (7.0)
Nominal Heating Capacity *1 Btu/h 20,000 27,000
(kW) (5.9) (7.9)
Sound Pressure Level *2
(Overall A Scale) dB 42-39-36-33 46-43-39-34
(Hi2-Hi-Me-Lo)
Outer Dimensions
Height in. (mm) 11-3/4 (298) 11-3/4 (298)
Width in. (mm) 33-7/8 (860) 33-7/8 (860)
Depth in. (mm) 24-13/16 (630) 24-13/16 (630)
Net Weight lbs. (kg) 55.1 (25) 55.1 (25)
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Airflow Rate cfm 653-582-512-441 777-688-582-459
(Hi2/Hi/Me/Lo)
(
m
3
/min.
)
(18.5-16.5-14.5-12.5) (22-19.5-16.5-13)
Motor Nominal Output W 57 57
Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52)
Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88)
Condensate Drain VP25 VP25
OD in. (mm) 1-1/4 (32) 1-1/4 (32)
ID in. (mm) 1 (25) 1 (25)
Adaptable Panel Model P-AP90DNA (without Motion Sensor)
Color Neutral White
Outer Dimensions
Height in. (mm) 1-3/16 (30)
Width in. (mm) 43-5/16 (1,100)
Depth in. (mm) 27-15/16 (710)
Net Weight lbs. (kg) 16.5 (7.5)
NOTES:
*1: Nominal capacity is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB)
67°F WB (19.4°C WB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
43°F WB (6.1°C WB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0 ft. (0m)
*2: Sound pressure level is based on the following conditions.
4.9 ft. (1.5m) beneath the unit.
The above data was measured in an anechoic chamber so that reected sound should be taken into consideration in the eld.
2-WAY CASSETTE
TC-16002-rev.1
2-3
2.4 Dimensional Data
Models: (H,Y,C)IC2018B21S and (H,Y,C)IC2024B21S with Decorative Panel P-AP90DNA
Unit: inch (mm)
Min. 94-1/2 (2400)
2-WAY CASSETTE
2-4
TC-16002-rev.1
2.5 Structure
Unit: inch (mm)
No. Part Name Remarks
1 Fan
2 Fan Motor DC
3 Heat Exchanger
4 Distributor
5 Strainer
6 Electronic Expansion Valve
7 Electrical Control Box
8 Refrigerant Gas Pipe Connection with
f
5/8 (15.88) Flare Nut
9 Refrigerant Liquid Pipe Connection with
f
3/8 (9.52) Flare Nut
10 Condensate Pipe Connection VP25 (OD
f
1-1/4 (32))
11 Drain-up Mechanism
12 Float Switch
13 Condensate Pan
14 Rubber Plug for Drain
15 Decorative Panel (P-AP90DNA) Optional
16 Air Inlet Grille
17 Air Filter
18 Air Outlet
19 Air Inlet
20 Cover for Corner Pocket (Use with P-AP90DNA)
2-WAY CASSETTE
TC-16002-rev.1
2-5
2.6 Component Data
Indoor Heat Exchanger and Fan
Model (H,Y,C)IC2018B21S (H,Y,C)IC2024B21S
Heat Exchanger Type Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter
in. (mm)
1/4 (7) 1/4 (7)
Rows 2 2
Number of Tube/Coil 24 24
Fin Material Aluminum
Pitch in. (mm) 1/16 (1.6) 1/16 (1.6)
Maximum Operating Pressure psi (MPa) 601 (4.15) 601 (4.15)
Total Face Area
ft
2
m
2
)
1.2 (0.36) 1.2 (0.36)
Number of Coil/Unit 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit 1 1
Outer Diameter
in. (mm)
14-3/16 (360) 14-3/16 (360)
Nominal Airflow cfm 653-582-512-441 777-688-582-459
(Hi2-Hi-Me-Lo)
(
m
3
/min.
)
(18.5-16.5-14.5-12.5) (22-19.5-16.5-13)
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method DC Motor
Nominal Output W 57 57
Quantity 1 1
Insulation Class E E
2-WAY CASSETTE
2-6
TC-16002-rev.1
2.7 Operation Space
2.8 Sensible Heat Factor (SHF)
Model SHF *
(H,Y,C)IC2018B21S 0.771
(H,Y,C)IC2024B21S 0.772
NOTE:
* SHF is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80
o
F DB (26.7
o
C DB)
67
o
F WB (19.4
o
C WB)
Outdoor Air Inlet Temperature: 95
o
F DB (35.0
o
C DB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0 ft. (0m)
Unit: inch (mm)
Unit: inch (mm)
Piping
Connection
Side
Min.
19-11/16
(500)
Min.
3-15/16
(100)
Single Unit Installation
Min.
19-11/16
(500)
Min.
19-11/16
(500)
Service
Access
Panel
Service
Access
Panel
Service
Access
Panel
Min.
118-1/8
(3000)
Multiple Unit Installation
Min.
3-15/16
(100)
Min.
3-15/16
(100)
Min.
19-11/16
(500)
Min.
19-11/16
(500)
Min.
19-11/16
(500)
Min.
19-11/16
(500)
Piping
Connection
Side
Min. 19-11/16 (500)
Min. 3-15/16 (100)
Min. 59-1/16 (1500)
Min. 59-1/16 (1500)
Min. 39-3/8 (1000)
(Piping Connection Side)
Min.
94-1/2
(2400)
Distance from Wall Side
Minimum Service Space
Models: (H,Y,C)IC2018B21S and (H,Y,C)IC2024B21S with Decorative Panel P-AP90DNA
2-WAY CASSETTE
TC-16002-rev.1
2-7
2.9 Electrical Data
Model
Unit Main Power Applicable Voltage Power Supply
Indoor
Fan Motor
Unit
VOL PH HZ Maximum Minimum MCA MFA OPT FLA
(H,Y,C)IC2018B21S
208/230 1 60 253 188
0.8 15 0.057 0.6
(H,Y,C)IC2024B21S 1.2 15 0.057 0.9
VOL: Rated Unit Power Supply Voltage (V)
PH: Phase
HZ: Frequency (Hz)
MCA: Minimum Circuit Ampacity (A)
MFA: Maximum Fuse Ampacity (A)
OPT: Rated Motor Output (kW)
FLA: Full Load Ampacity (A)
NOTE:
Power supply voltage should be satised with the following.
Supply Voltage: Rated Voltage within ±10%
Starting Voltage: Rated Voltage within -15%
Operating Voltage: Rated Voltage within ±10%
2-WAY CASSETTE
2-8
TC-16002-rev.1
2.10 Sound Data
NOTE:
Operation sound is equivalent to an anechoic chamber (free space).
Noise level will be increased by the surrounding noise and echoes.
Model: (H,Y,C) IC2018B21S
Model: (H,Y,C) IC2024B21S
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50

Johnson Controls VRF System Engineering Manual

Category
Split-system air conditioners
Type
Engineering Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI