LED Indicators Functionality
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestoTimeDelay,US,andPIRsensitivity.Inpreparationfor
theInstallerTest,thetimedelayissetto15seconds,afterthesensorisinstalled,powered-ONandhasstabilized,
theunitwillTime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconrmedby
watchingtheGreen(US)andRed(PIR)indicatorLEDsonthefrontofthesensor,whilemovingaroundtheroom.
1.WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDsdo
notturnON,gotoInstallerAdjustments-SensitivityAdjustmentsSection)
2.Standstillsixtoeightfeetawayfromthesensorforveseconds.LEDsshouldnotturnON.(IfanyLEDturns
ON,noteLEDandgotoInstallerAdjustments–SensitivityAdjustmentsection)
3.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
4.Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
5.TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgofor10min.Time
DelayUserModesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.Toforceinto10min
UserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds,and
thenbacktoitsoriginalposition)WhileinTestMode,theLEDswillflashonceper1/4second.
Sensitivity Adjustments
Ultrasonic Sensitivity (GreenLED)–Usingasmallflatheadscrewdriverturnthegreenpotentiometersothatthearrowpointsup.
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthegreenpotentiometerclockwisein
smallincrements.RepeatStep1.
3.Standstillsixtoeightfeetawayfromsensorforveseconds.LEDshouldnotturnON.
4.IfGreenLEDturnsonwithoutmotionorisconstantlyondecreasetheUSsensitivitybyturningthegreen
potentiometercounter-clock-wiseinsmalldecrements.RepeatStep3.
PIR Sensitivity
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnon,checkforanyobstructions.
3.Standstillsixtoeightfeetawayfromsensorforveseconds.LEDshouldnotturnon.
4.IfRedLEDturnsonwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2.AdjustUltrasonicSensitivity.
Daylight Adjustments (-R Model Only 0 to 300 foot-candles)
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise).
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.If
thereisenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlight
intheroom,thesensorwillallowthelightstoturnONwhenoccupied.
Full and Half Logic Modes (See DIP Switch legend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancy
activation,shouldtheambientlightlevelexceedthepresetfoot-candlelevel.
After activation:
FullLogicMode-shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtotheyellow
controlleadwillturnOFF.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,after
occupancyactivation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturn
thelightsOFFwhileoccupancyisbeingdetected.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Inorderforthisfeaturetofunction,theyellowcontrolleadmust
bewired.
1.WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrent
position,wait3secondsandthenbackintoitsoriginalposition.
2.SetDIPSwitch10toFullorHalfLogicMode.
3.SettheLightleveltoMinimum(fullyCCW).
4.LeavetheroomandletthesensorTime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
incrementsuntilthelightsareON.(Pause5secondsbetweeneachadjustment)
6.OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethecurrent
illumination.
Time Delay Adjustments
PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10
minutes.AslongasAutoisenabled,thesensorwillrespondtoeachpairofFalse-offswithnonormalOFFinbetween,by
alternatelymakingslightadjustmentstoeitherTimeDelay(by2minuteincrements)orsensitivity,sothereshouldbeno
needformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensorTimeDelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2are
alreadydown,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Automatic Mode
InAutomatic-ONMode,thelightsturnONwhenapersonenterstheroom.Ifoptionalmomentarylowvoltage
switchesareusedalongwithAutomatic-ONMode,activatingtheswitch(es)whiletheloadisONturnstheloadOFF.
WhentheloadisturnedOFFmanually,aslongasthesensorcontinuestodetectoccupancytheloadsstayOFF.Afterthe
TimeDelayexpires,thelightsstayOFFandthesensorgoesbacktoAutomatic-ONMode.Forwiringinformationforthe
optionalmomentarylowvoltageswitch(es),pleaseseethewiringsectionoftheinstallationinstructions.
Manual Mode (-R Model Only)
InManual-ONMode,theoptionalmomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivated
thesensorwillmaintainthelightsONuntilmotionceasesandtheTimeDelayexpires.Whiletheroomisoccupiedthe
BASrelayremainsactive.AftertheTimeDelayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)
mustbeusedtoturntheload(s)ONunlessthereismotiondetectedwithinthe10secondre-triggerperiod.
Lighting Sweep Option
Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayupon“powerup”topreventfalseactivationin
buildingswithcomputercontrolsystems.
1. MoveDIPSwitch9up.Ifnotselected(DipSwitch9down),uponinitial“powerup”orrestorationofpowerthe
sensorwillforcethelightsONnomatterthestateofoccupancy.
HVAC/Tracking Mode (-R model only)
Ifselected,TrackingModeallowstheloadconnectiontotheFormCrelaytofollowthestateofthesensor’sblue
lead.HVACModeallowstheloadconnectedtotheFormCrelaytoremainONwhenthelightsareturnedOFFmanually.
ApplicationsmayincludekeepingtheroomatadesiredtemperaturewhilegivingapresentationandthelightsareOFF.
Zero Time Delay Mode
InZeroTimeDelayMode,theoutputisactuatedforonesecondtosignalanotherdevicethatthespacebeing
monitoredisoccupied.Applicationsmayincludetheuseofalightingcontrolsystemtomanagethedelayofthelighting
deactivation.Pleaseseethewiringdiagramsectionforwiringdetails.
WheninZeroTimeDelayModeandTrackingModetheloadconnectedtotheFormCrelayshallfollowthestateofthe
sensor’sbluelead(zeroTimeDelayfortheformCrelay).
WheninZeroTimeDelayModeandHVACMode,theloadconnectedtotheFormCrelayremainsONforthestandard
TimeDelay.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1.MoveDIPSwitch8up.
WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s).
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
During Installer/Test Mode While in User Mode
LED Flashing Speed
LEDswillflashonceper¼second LEDswillflashoncepersecond
Duration
10minutes 10to30minutes
Checkout and Adjustment
(-R model only)
SweepOverride
LEDs
(-R model only)
(-R model only)
(-R model only)
Full/Half Logic HVAC/Tracking
Zero Time Delay
Pot 1 - Blue (0-300 FC)
Ultrasonic
(-R model only)
Pot 2 - Green
123456 78910
11 12
ON
Daylight Sensor Adjustment
Ultrasonic Sensitivity Adjustment
PIR Detector
DIP Switch Settings
Installer Adjustments
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
WallSwitchOFF TurnWallSwitchON.
Iflowvoltageswitchoptionisused,lightsmay
havebeenturned-offmanually.
Presslow-voltageswitch.
DaylightFeatureEnabled
IfalllightsarerequiredtoturnONadjustDIPSwitch10and/
ordaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
Lights
Will Not
Turn ON
manually
DaylightFeatureEnabled
IfalllightsarerequiredadjustDIPswitch10and/ordaylight
potentiometer.
Powerinterruption Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up).
UltrasonicSensitivitysetHigh
LowersensitivitybyturninggreenpotentiometerCCWin
smalldecrements.
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalledminimum4-6feetawayfrom
anyairventandoutofpathofheavyairflow.
Sensorinstalledclosetoindirectlighting. Sensorsshouldbemountedawayfromindirectlighting.
Self-adjust
Itmaybepossiblefortheunittohaveself-adjustedthetime
delaytoa30minutedelay.IfthelightsdonotturnOFFafter
30minutesfollownextstep.
30MinuteDelay Maximumtimedelayis30Minutes.CheckDIPSwitchesto
verifyDIPSwitchsettings.IflightsdonotturnOFFattheset
timedelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up.
Bypass Checkwiringtomakesuresensororswitchpackarenot
bypassed.
Lights Will Not
Turn OFF
manually
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up).
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Troubleshooting
Warranties and Limitation of Liability