DIP Switch Settings Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled
IfalllightsarerequiredadjustDIPSwitch10
and/ordaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up)
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalledminimum4-6feetaway
fromanyairventandoutofpathofheavyairow.
Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting.
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up
Bypass
Checkwiringtomakesuresensoror
switchpackarenotbypassed
Lights Will Not
Turn OFF
manually
Override
MakesuresensorisnotinOverrideMode
(DIPSwitch8up)
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Installer Adjustments
SweepOverride
LEDs
(-R model only)
(-R model only)
Full/Half Logic HVAC/Tracking
Zero Time Delay
Pot 1 - Blue (0-300 FC)
Ultrasonic
(-R model only)
Pot 2 - Green
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandPIRsensitivity.InpreparationfortheInstallerTest,
thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,theunitwilltime-out15seconds
afterthelastmotiondetected.CoverageandsensitivitycanbeconrmedbywatchingthePassiveInfrared(PIR)indicatorLEDson
thefrontofthesensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDsdonotturn
ON,gotoInstallerAdjustments–SensitivityAdjustmentsSection)
2. Standstillsixtoeightfeetawayfromthesensorforveseconds.LEDsshouldnotturnON.(IfanyLEDturnsON,noteLED
andgotoInstallerAdjustments–SensitivityAdjustmentsection)
3. Walkoutsidetheroomandwait15secondsforthelightstoturnOF F.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
4. Re-entertheroomandmanuallyturnthelightsON.(IflightsdonotturnONgotoTroubleshootingSection)
5. TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgofor10min.TimeDelayUser
Modesetting.
Note: ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To
forceinto10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrent
position,wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillashonceper1/4second.
12345678910
11 12
ON
Daylight Sensor Adjustment
PIR Detector
Sensitivity Adjustments
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheRedLEDdoesnotturnON,checkforanyobstructions.
3. Standstillsixtoeightfeetawayfromsensorforveseconds.LEDshouldnotturnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
Daylight Adjustments (-R Model Only 0 to 300 foot-candles)
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise).
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis
enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOF F.Ifthereisnotenoughlightintheroom,the
sensorwillallowthelightstoturnONwhenoccupied.
Full and Half Logic Modes(SeeDIPSwitchlegend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancyactivation,should
theambientlightlevelexceedthepresetfoot-candlelevel.
After activation:
FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtotheyellowcontrol
leadwillturnO F F.ThelightswillremainOF F,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,afteroccupancy
activation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturnthelightsOFFwhile
occupancyisbeingdetected.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoarticiallightisneeded.Inorderforthisfeauretofunction,
theyellowcontrolleadmustbewired.
1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait
3secondsandthenbackintoitsoriginalposition.
2. SetDIPSwitch10toFullorHalfLogicMode.
3. Setthelightleveltominimum(fullyCCW).
4. Leavetheroomandletthesensortime-outsolightsareO F F.EnterthespaceandlightsshouldremainOF F.
5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrementsuntil
thelightsareON.(Pause5secondsbetweeneachadjustment)
6. OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethecurrentillumination.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.Aslong
asAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,byalternatelymakingslight
adjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedformanualadjustment.Ifmanual
adjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2arealreadydown,
toggleDIPSwitch10outofitscurrentposition,wait3secondsandthenbacktoitsoriginalposition)
Manual Mode
InManualONMode,theoptionalmomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivatedthesensor
willmaintainthelightsONuntilmotionceasesandthetimedelayexpires.WhiletheroomisoccupiedtheBASrelayremainsactive.
Afterthetimedelayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)mustbeusedtoturntheload(s)ONunless
thereismotiondetectedwithinthe10secondre-triggerperiod.
Lighting Sweep Option
Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayupon“power-up”topreventfalseactivationinbuildingswith
computercontrolsystems.
1. MoveDIPSwitch9up.Ifnotselected(DipSwitch9down),uponinitial“power-up”orrestorationofpowerthesensorwillforce
thelightsONnomatterthestateofoccupancy.
HVAC/Tracking Mode (-R model only)
Ifselected,TrackingModeallowstheloadconnectiontotheFormCrelaytofollowthestateofthesensor’sbluelead.HVAC
ModeallowstheloadconnectedtotheFormCrelaytoremainONwhenthelightsareturnedOFFmanually.Applicationsmayinclude
keepingtheroomatadesiredtemperaturewhilegivingapresentationandthelightsareOF F.
Zero Time Delay Mode
InZeroTimeDelayMode,theoutputisactuatedforonesecondtosignalanotherdevicethatthespacebeingmonitoredis
occupied.Applicationsmayincludetheuseofalightingcontrolsystemtomanagethedelayofthelightingdeactivation.Pleaseseethe
wiringdiagramsectionforwiringdetails.
WheninZeroTimeDelayModeandTrackingModetheloadconnectedtotheFormCrelayshallfollowthestateofthesensor’s
bluelead(zeroTimeDelayfortheformCrelay).
WheninZeroTimeDelayModeandHVACMode,theloadconnectedtotheFormCrelayremainsONforthestandardtimedelay.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1. MoveDIPSwitch8up.
WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s).
LED Indicators Functionality
During Installer/Test Mode While in User Mode
LED Flashing Speed
LEDswillashonceper¼second LEDswillashoncepersecond
Duration
10minutes 10to30minutes
Checkout and Adjustment