  • Hello! I am an AI chatbot trained to assist you with the Samsung AC018TN4FCC/SU Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Air conditioner
Installation manual
AC***TN4FC*
Thank you for purchasing this Samsung air conditioner.
Before operating this unit, please read this manual carefully and retain it for future
reference.
DB68-08576A-00
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 1 2019-11-05 오후 12:52:12
2
English
Contents
Safety Information 3
Installation Procedure 5
Step 1 Checking and preparing accessories 5
Step 2 Choosing the installation location 5
Step 3 Optional: Insulating the body of the indoor unit 8
Step 4 Installing the indoor unit 8
Step 5 Purging inert gas from the indoor unit 10
Step 6 Cutting and flaring the pipes 10
Step 7 Connecting the assembly pipes to the refrigerant pipes 11
Step 8 Performing the gas leak test 12
Step 9 Insulating the refrigerant pipes 12
Step 10 Installing the drain hose and drain pipe 13
Step 11 Performing the drainage test 15
Step 12 Optional: For the installation of the circular panel 16
Step 13 Connecting the power and communication cables 16
Step 14 Optional: Extending the power cable 18
Step 15 Setting the indoor unit addresses and the installation options 19
Instruction for packing and unpacking the unit 33
Appendix 34
Troubleshooting 34
Packing and unpacking guide 35
Product specification 38
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 2 2019-11-05 오후 12:52:12
3
English
Safety Information
WARNING
• Hazardsorunsafepracticesthatmayresultinsevere
personalinjuryordeath.
CAUTION
• Hazardsorunsafepracticesthatmayresultinminor
personalinjuryorpropertydamage.
• Carefullyfollowtheprecautionslistedbelowbecausethey
areessentialtoguaranteethesafetyoftheequipment.
WARNING
• Alwaysdisconnecttheairconditionerfromthepower
supplybeforeservicingitoraccessingitsinternal
components.
• Verifythatinstallationandtestingoperationsare
performedbyqualifiedpersonnel.
• Verifythattheairconditionerisnotinstalledinan
easilyaccessiblearea.
General information
WARNING
• Carefullyreadthecontentofthismanualbeforeinstalling
theairconditionerandstorethemanualinasafeplacein
ordertobeabletouseitasreferenceafterinstallation.
• Formaximumsafety,installersshouldalwayscarefullyread
thefollowingwarnings.
• Storetheoperationandinstallationmanualinasafe
locationandremembertohanditovertothenewownerif
theairconditionerissoldortransferred.
• Thismanualexplainshowtoinstallanindoorunitwitha
splitsystemwithtwoSAMSUNGunits.Theuseofother
typesofunitswithdifferentcontrolsystemsmaydamage
theunitsandinvalidatethewarranty.Themanufacturer
shallnotberesponsiblefordamagesarisingfromtheuseof
noncompliantunits.
• Themanufacturershallnotberesponsiblefordamage
originatingfromunauthorizedchangesortheimproper
connectionofelectricandrequirementssetforthinthe
“Operatinglimits”table,includedinthemanual,shall
immediatelyinvalidatethewarranty.
• Theairconditionershouldbeusedonlyfortheapplications
forwhichithasbeendesigned:theindoorunitisnot
suitabletobeinstalledinareasusedforlaundry.
• Donotusetheunitsifdamaged.Ifproblemsoccur,switch
theunitoffanddisconnectitfromthepowersupply.
• Inordertopreventelectricshocks,firesorinjuries,always
stoptheunit,disabletheprotectionswitchandcontact
SAMSUNG’stechnicalsupportiftheunitproducessmoke,if
thepowercableishotordamagedoriftheunitisverynoisy.
• Alwaysremembertoinspecttheunit,electricconnections,
refrigeranttubesandprotectionsregularly.These
operationsshouldbeperformedbyqualifiedpersonnelonly.
• Theunitcontainsmovingparts,whichshouldalwaysbe
keptoutofthereachofchildren.
• Donotattempttorepair,move,alterorreinstalltheunit.If
performedbyunauthorizedpersonnel,theseoperationsmay
causeelectricshocksorfires.
•
Donotplacecontainerswithliquidsorotherobjectsontheunit.
• Allthematerialsusedforthemanufactureandpackagingof
theairconditionerarerecyclable.
• Thepackingmaterialandexhaustbatteriesoftheremote
controller(optional)mustbedisposedofinaccordancewith
currentlaws.
• Theairconditionercontainsarefrigerantthathastobe
disposedofasspecialwaste.Attheendofitslifecycle,the
airconditionermustbedisposedofinauthorisedcentres
orreturnedtotheretailersothatitcanbedisposedof
correctlyandsafely.
• Donotusemeanstoacceleratethedefrostoperationor
toclean,otherthanthoserecommendedbySamsung.
• Donotpierceorburn.
• Beawarethatrefrigerantsmaynotcontainanodour.
Installing the unit
WARNING
IMPORTANT: When installing the unit, always remember
to connect first the refrigerant tubes, then the electrical
lines.
• Alwaysdisassembletheelectriclinesbeforethe
refrigeranttubes.
• Uponreceipt,inspecttheproducttoverifythat
ithasnotbeendamagedduringtransport.Ifthe
productappearsdamaged,DONOTINSTALLitand
immediatelyreportthedamagetothecarrieror
retailer(iftheinstallerortheauthorizedtechnicianhas
collectedthematerialfromtheretailer.)
• Aftercompletingtheinstallation,alwayscarryouta
functionaltestandprovidetheinstructionsonhowto
operatetheairconditionertotheuser.
Safety Information
Safety Information
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 3 2019-11-05 오후 12:52:12
4
Safety Information
English
Safety Information
• Donotusetheairconditionerinenvironmentswith
hazardoussubstancesorclosetoequipmentthat
releasefreeflamestoavoidtheoccurrenceoffires,
explosionsorinjuries.
• Donotinstalltheproductinaplacewhere
thermohygrostatisneeded(suchasserverroom,
machineryroom,computerroom,etc.)Thoseplacesdo
notprovideguaranteedoperationconditionoftheproduct
thereforeperformancecanbepoorintheseplaces.
• Donotinstalltheproductinashiporavehicle(such
asacampervan).Salt,vibrationorotherenvironmental
factormaycausetheproductmalfunction,electric
shockorfire.
•
Ourunitsshouldbeinstalledincompliancewiththe
spacesshownintheinstallationmanual,toensure
accessibilityfrombothsidesandallowrepairsor
maintenanceoperationstobecarriedout.Theunit’s
componentsshouldbeaccessibleandeasytodisassemble
withoutendangeringpeopleandobjects.
Forthisreason,whenprovisionsoftheinstallationmanual
arenotcompliedwith,thecostrequiredtoaccessand
repairtheunits(inSAFETYCONDITIONS,assetoutin
prevailingregulations)withharnesses,ladders,scaffolding
oranyotherelevationsystemwillNOTbeconsideredpart
ofthewarrantyandwillbechargedtotheendcustomer.
Do not install the air conditioner in following places.
• Placewherethereismineraloilorarsenicacid.Resin
partsflameandtheaccessoriesmaydroporwater
mayleak.Thecapacityoftheheatexchangermay
reduceortheairconditionermaybeoutoforder.
• Theplacewherecorrosivegassuchassulphuricacid
gasgeneratesfromtheventpipeorairoutlet.
• Thecopperpipeorconnectionpipemaycorrodeand
refrigerantmayleak.
• Theplacewherethereisamachinethatgenerates
electromagneticwaves.Theairconditionermaynot
operatenormallyduetocontrolsystem.
• Theplacewherethereisadangerofexisting
combustiblegas,carbonfibreorflammabledust.
• Theplacewherethinnerorgasolineishandled.Gas
mayleakanditmaycausefire.
Power supply line, fuse or circuit
breaker
WARNING
•
Alwaysmakesurethatthepowersupplyiscompliantwith
currentsafetystandards.Alwaysinstalltheairconditioner
incompliancewithcurrentlocalsafetystandards.
• Alwaysverifythatasuitablegroundingconnectionis
available.
• Verifythatthevoltageandfrequencyofthepower
supplycomplywiththespecificationsandthatthe
installedpowerissufficienttoensuretheoperationof
anyotherdomesticapplianceconnectedtothesame
electriclines.
• Alwaysverifythatthecut-offandprotectionswitches
aresuitablydimensioned.
• Verifythattheairconditionerisconnectedtothepower
supplyinaccordancewiththeinstructionsprovidedin
thewiringdiagramincludedinthemanual.
• Alwaysverifythatelectricconnections(cableentry,
sectionofleads,protections…)arecompliantwith
theelectricspecificationsandwiththeinstructions
providedinthewiringscheme.Alwaysverifythatall
connectionscomplywiththestandardsapplicableto
theinstallationofairconditioners.
• Devicesdisconnectedfromthepowersupplyshould
becompletelydisconnectedintheconditionof
overvoltagecategory.
• Besurenottoperformpowercablemodification,
extensionwiring,andmultiplewireconnection.
Itmaycauseelectricshockorfireduetopoor
connection,poorinsulation,orcurrentlimit
override.
Whenextensionwiringisrequiredduetopower
linedamage,referto"Step13Optional:Extending
thepowercable"intheinstallationmanual.
CAUTION
Make sure that you earth the cables.
• Donotconnecttheearthwiretothegaspipe,water
pipe,lightingrodortelephonewire.Ifearthingisnot
complete,electricshockorfiremayoccur.
Install the circuit breaker.
• Ifthecircuitbreakerisnotinstalled,electricshockor
firemayoccur.
Make sure that the condensed water dripping from the
drain hose runs out properly and safely.
Install the power cable and communication cable of
the indoor and outdoor unit at least 1m away from the
electric appliance.
Install the indoor unit away from lighting apparatus
using the ballast.
• Ifyouusethewirelessremotecontrol,receptionerror
mayoccurduetotheballastofthelightingapparatus.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 4 2019-11-05 오후 12:52:12
5
Installation Procedure
English
Installation Procedure
Installation Procedure
Step 1 Checking and preparing
accessories
Thefollowingaccessoriesaresuppliedwiththeindoor
unit.Thetypeandquantitymaydiffer,dependingonthe
specifications.
Insulation pipe Cable-tie
Drain hose Installation manual
Clamp User manual
Installation template Dimension gauge
Step 2 Choosing the installation
location
Installation location requirements
• Theremustbenoobstaclesneartheairinletand
outlet.
• Installtheindoorunitonaceilingthatcansupportits
weight.
• Maintainsufficientclearancearoundtheindoorunit.
• Beforeinstallingtheindoorunit,besuretocheck
whetherthechosenlocationiswell-drained.
• Theindoorunitmustbeinstalledsuchthatitisbeyond
publicaccessandisnottouchablebyusers.
• Rigidwallwithoutvibration.
• Whereitisnotexposedtodirectsunshine.
• Wheretheairfiltercanberemovedandcleanedeasily.
• Theplacewhereanimalsmayurinateontheproduct
Ammoniamaybegenerated.
• Theplacewhereisclosetoheatsources.
• Donotusetheindoorunitforpreservationoffood
items,plants,equipment,andartworks.Thismay
causedeteriorationoftheirquality.
• Donotinstalltheindoorunitifithasanydrainage
problem.
CAUTION
• Asarule,theunitcannotbeinstalledataheightof
lessthat2.5m.
• Ifyouinstallthecassetteorducttypeindooruniton
theceilingwithhumidityover80%,youmustapply
extra10mmofpolyethylenefoamorotherinsulation
withsimilarmaterialonthebodyoftheindoorunit.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 5 2019-11-05 오후 12:52:13
6
Installation Procedure
Installation Procedure
English
Indoor unit dimensions
(Unit:mm)
Category Square panel Circular panel
Front
1000
358
Ceiling opening dimension
960 (950 - 960)
Ceiling opening dimension
960 (950 - 960)
116
1050
883
Large+,
Large
385
166
66
357
404
128
181
190
317
Drain hose
connector
Refrigerant
pipe
Wire insert
hole
100
153
162
289
138
94
Small
385
166
66
357
404
128
181
190
233
Drain hose
connector
Refrigerant
pipe
Wire insert
hole
100
153
162
205
138
94
Common
646
646
942
787
80
ø100
H1
H1Large+,Large:180,Small:150
H2Large+,Large:152,Small:122
H2
Square panel Circular panel
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 6 2019-11-05 오후 12:52:14
7
Installation Procedure
English
Spacing requirements
A : 1500 mm or more
A
A
A
A
'C'
Indoor unit
2500 mm or more
Obstruction
20 mm
1500 mm or
more
10 mm
(Unit:mm)
Model
AC018TN4FCC
AC018TN4FCH
AC024TN4FCC
AC024TN4FCH
AC036TN4FCC
AC036TN4FCH
AC048TN4FCC
AC048TN4FCH
C 261 345 345 345
Model
AC018TN4FCC
AC018TN4FCH
AC024TN4FCC
AC024TN4FCH
AC036TN4FCC
AC036TN4FCH
AC048TN4FCC
AC048TN4FCH
Chassis Small LRG LRG+ LRG+
Net dimension
(W x H x D)
mm 947x281x947 947x365x947 947x365x947 947x365x947
Net weight kg 20.0 23.3 25.3 25.8
Liquid pipe connection mm 6.35 6.35 9.52 9.52
Gas pipe connection mm 12.7 15.88 15.88 19.05
Drain hose connection mm Outerdiameter:Ø32,Innerdiameter:Ø26.5
• Thecircularpanelisbydefaultavailableinexposed
installation.
• Makeinspectionholesontheceilingforeasier
installationandmaintenance,asshowninthe
followingtable.(Thesizeofaninspectionholemustbe
atleast450mmx450mm.)
• Asuspendedceilingstructurecansubstituteforthe
inspectionholes.
Category
Inspection hole
Recessed installation
Exposed
installation
Integrated suspended
Square panel
1ea
-
Circular panel
2ea
•
Fortherecessedinstallationofthecircularpanel
Refrigerant
pipe
Connection part of the
drain hose
Indoor unit
display
Inspection hole
1050
(Unit: mm)
883
ø1010 to 1020
Ceiling opening
diameter
ø1010 to 1020
Inspection hole
NOTE
Theclearancebetweenthepanelandtheinspectionhole
is15to20mmonaside.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 7 2019-11-05 오후 12:52:14
8
Installation Procedure
Installation Procedure
English
CAUTION
• Complywiththelengthandheightlimitsdescribedinthe
figureabove.
• Theindoorunitmustbeinstalledaccordingtothe
specifieddistancesinordertopermitaccessibility
fromeachside,toguaranteecorrectoperation,
maintenance,andrepairoftheunit.
Thecomponentsoftheindoorunitmustbereachableand
removableundersafeconditionsforpeopleandtheunit.
• Donotholdthedischargewhilecarryingtheindoor
unittoavoidthepossibilityofbreakage.
• Youmustholdthehangerplateonthecornerand
carrytheindoorunit.
Step 3 Optional: Insulating the body of
the indoor unit
Ifyouinstallacassettetypeindoorunitontheceiling
whentemperatureisover27°Candhumidityisover
80%,youmustapplyanextra10mmthickpolyethylene
insulationorasimilartypeofinsulationtothebodyofthe
indoorunit.
Cutawaythepartwherepipesarepulledoutforthe
insulatingwork.
A
Insulatetheendofthepipeandsomecurvedareaby
usingseparateinsulator.
NOTE
• A:Referencefortheoutercircumferenceoftheunit
(Wheninsulatingthebodyoftheindoorunit,useAas
thereferenceforitsoutercircumference.)
(Unit:mm)
Indoor unit type and models Dimensions
360cassettetype<S>
(947*947*281)
AC018TN4FCC
AC018TN4FCH
2610*130
360cassettetype<L>
(947*947*365)
AC024TN4FCC
AC024TN4FCH
2610*215
360cassettetype<L+>
(947*947*365)
AC036TN4FCC
AC036TN4FCH
AC048TN4FCC
AC048TN4FCH
2610*215
Step 4 Installing the indoor unit
Whendecidingonthelocationoftheairconditionerthe
followingrestrictionsmustbetakenintoaccount.
1 Determinethepositionsofthepipeandthedrainhose
holeasshowninthepatternsheet,anddrillthehole
withaninnerdiameterof14mm.
NOTE
• Sincethediagramismadeofpaper,itmayshrink
orstretchslightlyduetotemperatureorhumidity.
Forthisreason,beforedrillingtheholes,besure
tomaintainthecorrectdimensionsbetweenthe
markings.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 8 2019-11-05 오후 12:52:15
9
Installation Procedure
English
2 Performthefollowingstepstoinstallinspectionholes
inaccordancewiththepaneltype.
a Fortherecessedinstallationofthesquarepanel.
• Installaninspectionholetothedirectionof
connectionpartsoftherefrigerantpipeandthe
drainhose.(1point)
Indoor unit
display
Refrigerant pipe
Inspection hole
b Forrecessedinstallationofthecircularpanel
• Installinspectionholestobothdirectionsofthe
connectionpartoftherefrigerantpipeandthe
drainhoseandoftheindoorunitdisplay.
(2points)
Inspection hole
Indoor unit display
Refrigerant pipe
Inspection hole
3 Insertboltanchors,useexistingceilingsupportsor
constructasuitablesupportasshowninfigure.
4 Installthesuspensionbolts,dependingontheceiling
type.
Ceiling support
CAUTION
• Makesurethattheceilingisstrongenoughtosupport
theweightoftheindoorunit.Beforehangingtheunit,
testthestrengthofeachattachedsuspensionbolt.
• Ifthelengthofthesuspensionboltismorethan1.5m,
youarerequiredtopreventvibration.
5 Screweightpairsofnutsandwasherstothe
suspensionbolts,makingspaceforhangingtheindoor
unit.
CAUTION
• Youmustinstallallofthesuspensionrods.
• Itisimportanttoleavesufficientspaceinthefalse
ceilingtoallowaccessformaintenanceorrepairsto
thedrainagepipeconnection,therefrigerantpipe
connection,ortoremovetheunitifnecessary.
6 Hangtheindoorunittothesuspensionboltsbetween
twonuts.Cutapadstopperandplaceitonthe
suspensionboltstoholdthewashers.Removethe
stopperandscrewthenutstofixtheunit.
Pad stopper
Bracket
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 9 2019-11-05 오후 12:52:15
10
Installation Procedure
Installation Procedure
English
7 Adjusttheunittotheappropriateposition,takinginto
accounttheinstallationareaforthefrontpanel.
• Placethepatternsheetontheindoorunit.
• Adjustthespacebetweentheceilingandthe
indoorunitbyusingadimensiongauge.
• Fixtheindoorunitsecurelyafteradjustingthelevel
oftheunitbyusingaleveller.
• Removethepatternsheet,connecttheother
cables.andinstallthefrontpanel.
For the recessed installation
of the square panel: 11.5 mm
For the recessed installation
of the circular panel: 41.5 mm
Indoor unit
Ceiling
Gauge of
dimensions
Step 5 Purging inert gas from the
indoor unit
Theindoorunitcomeswithnitrogengas(inertgas)
chargedatthefactory.Therefore,allinertgasmustbe
purgedbeforeconnectingtheassemblypiping.
Unscrew the pinch pipe at the end of each refrigerant
pipe.
Liquid
side
Gas side
Insulator
NOTE
• Topreventdirtorforeignobjectsfromgettingintothe
pipesduringinstallation,donotremovethepinchpipe
completelyuntilyouarereadytoconnectthepiping.
Step 6 Cutting and flaring the pipes
1 Makesurethatyouhavetherequiredtoolsavailable:
pipecutter,reamer,flaringtool,andpipeholder.
2 Ifyouwishtoshortenthepipes,cutthemwithapipe
cutter,ensuringthatthecutedgeremainsata90°
angletothesideofthepipe.Refertotheillustrations
belowforexamplesofedgescutcorrectlyand
incorrectly.
Pipe cutter
Pipe Oblique Rough Burr
3 Topreventanygasfromleakingout,removeallburrs
atthecutedgeofthepipe,usingareamer.
4 Slideaflarenutontothepipeandmodifytheflare.
Pipe Flare Flare
D
D
A
R 0.4 to 0.8 mm
L
90° ±2°
45° ±2°
Outer Diameter (D) Depth (A) Flare dimension (L)
Ø6.35mm 1.3mm 8.7to9.1mm
Ø9.52mm 1.8mm 12.8to13.2mm
Ø12.70mm 2.0mm 16.2to16.6mm
Ø15.88mm 2.2mm 19.3to19.7mm
Ø19.05mm 2.2mm 23.6to24.0mm
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 10 2019-11-05 오후 12:52:16
11
Installation Procedure
English
5 Checkthattheflaringiscorrect,referringtothe
illustrationsbelowforexamplesofincorrectflaring.
Correct
Inclined
Damaged
Surface
Cracked
Uneven
Thickness
Step 7 Connecting the assembly pipes
to the refrigerant pipes
There are two refrigerant pipes of different diameters :
• Asmalleronefortheliquidrefrigerant.
• Alargeroneforthegasrefrigerant.Theinsideof
copperpipemustbecleanandhasnodust.
1 Removethepinchpipeonthepipesandconnectthe
assemblypipestoeachpipe,tighteningthenuts,first
manuallyandthenwithatorquewrench,aspanner
applyingthefollowingtorque.
2
3
3
1
Torque
wrench
Flare nut
Spanner
Union
Outer Diameter (mm) Torque (N•m)
Ø6.35 14to18
Ø9.52 34to42
Ø12.70 49to61
Ø15.88 68to82
Ø19.05 100to120
(1N•m=10kgf•cm)
NOTE
• Ifthepipesmustbeshortened,seeStep 6 Cutting
and flaring the pipesonpage10.
2 Besuretouseaninsulatorthickenoughtocoverthe
refrigeranttubetoprotectthecondensatewateron
theoutsideofthepipefallingontothefloorandto
improvetheefficiencyoftheunit.
3 Cutoffanyexcessfoaminsulation.
4 Makesurethattherearenocracksorwavesonthe
bentarea.
5 Itwouldbenecessarytodoubletheinsulation
thickness(10mmormore)topreventcondensation
evenontheinsulatorwheniftheinstalledareais
warmandhumid.
CAUTION
• Connecttheindoorandoutdoorunitsusingpipeswith
flaredconnections(notsupplied).Forthelines,use
insulated,unwelded,degreasedanddeoxidizedcopper
pipe(CuDHPtypetoISO1337orUNIEN12735-1),
suitableforoperatingpressuresofatleast4.2MPa
andforaburstpressureofatleast20.7MPa.Copper
pipeforhydro-sanitaryapplicationsiscompletely
unsuitable.
• Forsizingandlimits(heightdifference,linelength,
max.bends,refrigerantcharge,etc.)seetheoutdoor
unitinstallationmanual.
• Allrefrigerantconnectionmustbeaccessible,inorder
topermiteitherunitmaintenanceorremovingit
completely.
• Ifthepipesrequirebrazing,makesurethatoxygen
freenitrogen(OFN)isflowingthroughthesystem.
• Nitrogenblowingpressurerangeis0.02to0.05MPa.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 11 2019-11-05 오후 12:52:16
12
Installation Procedure
Installation Procedure
English
Step 8 Performing the gas leak test
Toidentifypotentialgasleaksontheindoorunit,inspect
theconnectionareaofeachrefrigerantpipeusingaleak
detectorforR-410A.
Beforerecreatingthevacuumandrecirculatingthe
refrigerantgas,pressurizethewholesystemwith
nitrogen(usingacylinderwithapressurereducer)at
apressureabove4MPainordertoimmediatelydetect
leaksontherefrigerantfittings.
Madevacuumfor15minutesandpressurizingsystemwithnitrogen.
Liquid
side
Gas side
Insulator
Step 9 Insulating the refrigerant pipes
Onceyouhavecheckedthattherearenoleaksinthe
system,youcaninsulatethepipingandhose.
1 Toavoidcondensationproblems,placeAcrylonitrileButadien
Rubberseparatelyaroundeachrefrigerantpipe.
No gap
NBR
NOTE
• Alwaysmaketheseamofpipesfaceupwards.
2 Windinsulatingtapearoundthepipesanddrainhose
avoidingcompressingtheinsulationtoomuch.
Indoor unit
Insulation cover pipe
Insulation pipe
Be sure to overlap the insulation.
CAUTION
• Besuretowrapinsulationtightlywithoutanygaps.
3 Finishwrappinginsulatingtapearoundtherestofthe
pipesleadingtotheoutdoorunit.
4 Thepipesandelectricalcablesconnectingtheindoor
unitwiththeoutdoorunitmustbefixedtothewall
withsuitableducts.
CAUTION
• Makesurethatallrefrigerantconnectionmustbe
accessibleforeasymaintenanceanddetachment.
• Installtheinsulationnottogetwiderandusethe
adhesivesontheconnectionpartofittoprevent
moisturefromentering.
• Windtherefrigerantpipewithinsulationtapeifitis
exposedtooutsidesunlight.
• Installtherefrigerantpiperespectingthatthe
insulationdoesnotgetthinneronthebentpartor
hangerofpipe.
• Addtheadditionalinsulationiftheinsulationplate
getsthinner.
Refrigerant pipe insulation
a x 3
Hanger
Additional insulation
a
5 Selecttheinsulationoftherefrigerantpipe.
• Insulatethegassideandliquidsidepipe,notingthe
insulationthicknessthatmustdifferaccordingto
thepipesize.
• Standard:Lessthananindoortemperatureof30°C,
withhumidityat85%.Ifinstallinginahighhumidity
environment,useonegradethickerinsulatorby
referringtothetablebelow.Ifinstallinginan
unfavourableenvironment,usethickerone.
• Theheat-resistancetemperatureoftheinsulator
mustbemorethan120°C.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 12 2019-11-05 오후 12:52:17
13
Installation Procedure
English
Pipe
Pipe size
(mm)
Insulation type (heating/cooling)
Remarks
Standard
(Less than 30°C, 85%)
High humidity
(Over 30°C, 85%)
EPDM, NBR (mm)
Liquidpipe
Ø6.35toØ9.52 9t 9t
Theinternal
temperatureis
higherthan120°C.
Ø12.7toØ19.05 13t 13t
Gaspipe
Ø6.35 13t 19t
Ø9.52
19t 25t
Ø12.70
Ø15.88
Ø19.05
• Wheninstallinginsulationintheplacesand
conditionsbelow,usethesameinsulationthatis
usedforhighhumidityconditions.
<Geological condition>
Highhumiditylocationssuchasshorelines,hot
springs,lakeorriversides,andridges(whenpartof
thebuildingiscoveredbyearthandsand)
<Operation purpose condition>
Restaurantceiling,sauna,swimmingpooletc.
<Building construction condition>
Ceilingsfrequentlyexposedtomoistureandcooling
arenotcovered.Forexample,pipesinstalledata
corridorofadormitoryandstudioornearanexitthat
opensandclosesfrequently.
Places(wherethepipesareinstalled)thatarehighly
humidduetoalackofventilation.
Step 10 Installing the drain hose and
drain pipe
1 Pushthesupplieddrainhoseasfaraspossibleover
thedrainsocket.
2 Tightenthemetalclampasshowninthepicture.
3 Wrapthesuppliedlargesealingpadoverthemetal
clampanddrainhosetoinsulateandfixitwithclamps.
4 Insulatethecompletedrainpipinginsidethebuilding
(fieldsupply).
Ifthedrainhosecannotbesufficientlysetonaslope,
fitthehosewithdrainraisingpiping(fieldsupply).
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 13 2019-11-05 오후 12:52:17
14
Installation Procedure
Installation Procedure
English
5 Pushthedrainhoseuptoinsulationwhenconnecting
thedrainhosetodrainsocket.
Metal clamp
Drain socket
Drain hose
Large seailng pad
Be sure to bond the drain
hose and the main pipe.
Drain pipe
Drain hose
PVC Tube Joint
+ VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
• Installairventilationtodraincondensationsmoothly.
Air ventilation
Ceiling
• Ifitisnecessarytoincreasetheheightofthedrain
pipe,installthedrainpipestraightwithin300mm
fromthedrainhoseport.Ifitisraisedhigherthan550
mm,theremaybewaterleaks.
Band joint
300 mm
or less
20 mm or more
Drain hose
Ceiling
550 mm or less
•
• Donotgivethehoseanupwardgradientbeyond
theconnectionport.Thiswillcausewatertoflow
backwardswhentheunitisstopped,resultinginwater
leaks.
Under gradient
Ceiling
• Donotapplyforcetothepipingontheunitsidewhen
connectingthedrainhose.Thehoseshouldnotbe
allowedtohangloosefromitsconnectiontotheunit.
Fastenthehosetoawall,frameorothersupportas
closetotheunitaspossible.
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
• Installhorizontally.
Indoor unit
Be horizontal
Flexible hose
• Max.allowableaxisgap.
Indoor unit
Max. 20 mm
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 14 2019-11-05 오후 12:52:18
15
Installation Procedure
English
• Max.allowablebendingangle.
Indoor unit
Max. 30˚
NOTE
• Ifaconcentrateddrainpipeisinstalled,refertothe
figurebelow.
Centralized horizontal drain pipe
(more than 1/100 slope)
Main drain pipe
Full thread bolt hanger
1000 to 1500 mm
300 to
550 mm
200 mm
or more
Individual air
vent
Main air vent
(must be installed)
Step 11 Performing the drainage test
1 Doaleaktestattheconnectionpartoftheflexible
hoseandthedrianpipe:
a Connectageneralhosetotheconnectionpartof
theflexiblehoseoftheindoorunit,andpourin
somewater.
Hose
Flexible hose
Water leakage
check part
b Afterpouringsomewater,reassembletherubber
capontheconnectionpartofaflexiblehoseof
theindoorunitandfirmlytightenitwithabandto
preventleakage.
c Checktheleaktestatthepartwheretheadhesive
fortheflexiblehoseandthedrianpipeisused.
CAUTION
• Theleaktestmustbeperformedforatleast24hours.
2 Checkthecondensedwaterdrainage:
a Pourabout2litersofwaterintotheindoorunit
drainpanasshowninthepicture.
b Whentheelectriccableconnectioniscompleted
• Turnontheindoorunitandoutdoorunit.
• OperateintheCoolmode.
CAUTION
• OnlyintheCoolmode,youcancheckthecorrect
operationofthedrainpump.
Whentheelectriccableconnectionhasnotbeencompleted
• Removethecontrolboxcoveroftheindoorunit.
• Connectthepowersupply(230V,60Hz)totheLand
Nterminals.
• Reassemblethecontrolboxcoverandturnonthe
indoorunit.
CAUTION
•
Whenthefloatswitchisnotdetectedduetoinsufficient
wateronthedrainpan,thedrainpumpwillnotwork.
• IfthepowersupplyisdirectlyconnectedtotheL
andNterminals,communicationerrormessage
mightappear.
• Aftercompletingthedrainagecheck,turntheunit
offanddisconnectthepowersupply.
• Reassemblethecontrolboxcover.
c Checkwhetherthedrainpumpworkscorrectly.
d Checkwhetherthedrainageisperforming
correctlyattheendofthedrainpipe.
e Checkforleakageatthedrainpipeanddrainpipe
connectionpart.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 15 2019-11-05 오후 12:52:18
16
Installation Procedure
Installation Procedure
English
f
Whenleakageoccurs,checkwhethertheindoorunit
islevelandcheckthedrainhoseconnectionpart,
drainpipeconnectionpartanddrainpumpconnection.
g Whenthedrainagecheckiscompletedand
thecondensedwaterremainsonthedrainpan,
removethewater.
Step 12 Optional: For the installation
of the circular panel
Making a circular opening on the ceiling
Useapapercompassprintedontheindoorunitpackage.
(attachedinsidetotheupperpart)
1
Useaboltorapintofixpivotpointofthepapercompasson
centeroftheceiling.(inthemiddleoflocationforinstallation)
2 Putapencilattheoppositesideofthep ivotpoint
fixedinplace.
3 Rotatethepapercompassonitspivotpointtodrawa
lineontheceiling.
4 Rotatethepapercompassdiametricallytodrawa
circleontheceiling.
For the painting of the panel
• Makesuretoonlyapplypaintsandvarnishesforresins
(ABS,HIPS)orpaintthinners.
• Ifyouapplylacquersforgeneraluseonthepanel,it
mayleadtodiscolorationorerosiononthesurfaceof
thepanel.
Step 13 Connecting the power and
communication cables
CAUTION
• Alwaysremembertoconnecttherefrigerantpipes
beforeperformingtheelectricconnections.
Whendisconnectingthesystem,alwaysdisconnect
theelectriccablesbeforedisconnectingthe
refrigerantpipes.
CAUTION
•
Alwaysremembertoconnecttheairconditionertothe
groundingsystembeforeperformingtheelectricconnections.
Useacrimpringterminalattheendofeachwire.
Theindoorunitispoweredthroughtheoutdoorunitby
meansofaH07RN-Fconnectioncable(oramorepower
model),withinsulationinsyntheticrubberandajacket
inpolychloroprene(neoprene),inaccordancewiththe
requirementsspecifiedinthestandardEN60335-2-40.
1 Removethescrewontheelectricalcomponentbox
andremovethecoverplate.
2 Routetheconnectioncordthroughthesideofthe
indoorunitandconnectthecabletotheterminals
refertothefigurebelow.
3 Routetheotherendofthecabletotheoutdoorunit
throughtheceiling&theholeonthewall.
4 Reassembletheelectricalcomponentboxcover,
carefullytighteningthescrew.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 16 2019-11-05 오후 12:52:18
17
Installation Procedure
English
Wiring terminals) 1 phase
1(L) 2(N) L N
F1 F2
F1 F2
L N
Indoor power
Main power cable
Communication
cable
Indoor unit
Outdoor unit
Wiring terminals) 3 phase
1(L) 2(N) L1(R) L2(S) L3(T) N
F1 F2
F1 F2
L N
Indoor power
Main power cable
Communication
cable
Indoor unit
Outdoor unit
NOTE
• Insertthepowerandthecommunicationcablestothe
cableinserthole,thenarrangeandconnectthecables,
asshowninthefigure:
Cable
insert hole
Power cable
Communication cable
Indoor power supply
Power supply Max/Min(V) Indoor power cable
230V,60Hz ±10% 0.75mm²↑,3wires
Communication cable
0.75mm²↑,2wires
AC power: M4 screw
Communication: M3.5 screw
11
13
7. 5
9.0
(Unit: mm)
18
13.8
Tightening torque (kgf • cm)
M3.5 8.0to12.0
M4 12.0to18.0
• 1N·m=10kgf·cm
•
Powersupplycordsofpartsofappliancesforoutdooruse
shallnotbelighterthanpolychloroprenesheathedflexible
cord.(CodedesignationIEC:60245IEC57/CENELEC:
H05RN-ForIEC:60245IEC66/CENELEC:H07RN-F)
• Sinceithastheexternalpowersupply,refertothe
outdoorunitinstallationmanualforMAINPOWER.
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 17 2019-11-05 오후 12:52:19
18
Installation Procedure
Installation Procedure
English
CAUTION
• Wheninstallingtheindoorunitinacomputer
roomornetworkroom,usethedoubleshielded
communicationcable(tapealuminum/polyester
braid+copper)ofFROHH2Rtype.
Step 14 Optional: Extending the power
cable
1 Preparethefollowingtools.
Tools Spec Shape
Crimpingpliers MH-14
Connectionsleeve
(mm)
20xØ6.5
(HxOD)
Insulationtape
Width19
mm
Contractiontube
(mm)
70xØ8.0
(LxOD)
2 Asshowninthefigure,peelofftheshieldsfromthe
rubberandwireofthepowercable.
• Peeloff20mmofcableshieldsfromthepre-
installedtube.
CAUTION
• Forinformationaboutthepowercable
specificationsforindoorandoutdoorunits,referto
theinstallationmanual.
• Afterpeelingoffcablewiresfromthepre-installed
tube,insertacontractiontube.
• Ifcablewiresareconnectedwithoutusing
connectingsleeves,theircontactareabecomes
reduced,orcorrosiondevelopsontheouter
surfacesofthewires(copperwires)overalong
time.Thismaycauseanincreaseofresistance
(reductionofpassingcurrent)andconsequently
mayresultinafire.
20 20 20
60
120
180
Power cable
202020
60
120
180
Pre-installed tube
for the power cable
(Unit: mm)
3 Insertbothsidesofcorewireofthepowercableinto
theconnectionsleeve.
• Method 1:Pushthecorewireintothesleevefrom
bothsides.
• Method 2:Twistthewirecorestogetherandpushit
intothesleeve.
Connection sleeve Connection sleeve
Method 1 Method 2
4 Usingacrimpingtool,compressthetwopointsand
flipitoverandcompressanothertwopointsinthe
samelocation.
• Thecompressiondimensionshouldbe8.0.
Compression
dimension
• Aftercompressingit,pullbothsidesofthewireto
makesureitisfirmlypressed.
Compress it 4 times
5 mm
Method 1
Compress it 4 times
5 mm
Method 2
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 18 2019-11-05 오후 12:52:20
19
Installation Procedure
English
5 Wrapitwiththeinsulationtapetwiceormoreand
positionyourcontractiontubeinthemiddleofthe
insulationtape.
40 mm
Insulation tape
Method 1
35 mm
Insulation tape
Method 2
6 Applyheattothecontractiontubetocontractit.
Contraction tube
Contraction tube
Method 1
Method 2
7 Aftertubecontractionworkiscompleted,wrapitwith
theinsulationtapetofinish.
Threeormorelayersofinsulationarerequired.
Insulation tape
Insulation tape
Method 1
Method 2
CAUTION
• Makesurethattheconnectionpartsarenotexposed
tooutside.
• Besuretouseinsulationtapeandacontractiontube
madeofapprovedreinforcedinsulatingmaterialsthat
havethesamelevelofwithstandvoltagewiththepower
cable.(Complywiththelocalregulationsonextensions.)
WARNING
• Incaseofextendingtheelectricwire,pleaseDONOT
usearound-shapedPressingsocket.
Incompletewireconnectionscancauseelectric
shockorafire.
Step 15 Setting the indoor unit
addresses and the installation options
Youcannotsetbothoftheindoorunitaddressesand
theinstallationoptionsinabatch:setbothofthem
respectively.
Common steps for setting the addresses and
options
AR-KH00E/AR-KH03E remote control (for 360 cassette
only)
Temperature
button
Timerbutton
Wheel
Modebutton
Setting the
option values
Entering the
mode for setting
the options
NOTE
• Theremotecontroldisplaymayvarydependingonthe
model.
1 Enterthemodeforsettingtheoptions:
a Removethebatteriesfromtheremotecontrol.
b Whileholdingdownthe
(Temp)and
(Timer)buttonssimultaneously,insertthe
batteriesintotheremotecontrol.
c Makesurethatyouareenteredtothemodefor
settingtheoptions:
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 19 2019-11-05 오후 12:52:21
20
Installation Procedure
Installation Procedure
English
2 Settheoptionvalues.
CAUTION
• Thetotalnumberofavailableoptionsare24:SEG1to
SEG24.
• BecauseSEG1,SEG7,SEG13,andSEG19arethepage
optionsusedbythepreviousremotecontrolmodels,
themodestosetvaluesfortheseoptionsareskipped
automatically.
• Seta2-digitvalueforeachoptionpairinthefollowing
order:SEG2andSEG3
SEG4andSEG5SEG6and
SEG8
SEG9andSEG10SEG11andSEG12SEG14
andSEG15
SEG16andSEG17SEG18andSEG20
SEG21andSEG22
SEG23andSEG24
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 X X X X X
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 X X X X X
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 X X X X X
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3 X X X X X
On (SEG1 to SEG12) Off (SEG13 to SEG24)
Takethestepspresentedinthefollowingtable:
Steps Remote control display
1 SettheSEG2andSEG3values:
a SettheSEG2valuebyrotatingtheWheel
counterclockwiseuntilthevalueyouwanttoset
appearsontheremotecontroldisplay.
SEG2
b SettheSEG3valuebyrotatingtheWheelclockwise
untilthevalueyouwanttosetappearsontheremote
controldisplay.
SEG3
WhenyourotatetheWheel,valuesappearinthefollowingorder:
2 Pressthe (Mode)button.CoolandOnappearontheremotecontroldisplay.
3 SettheSEG4andSEG5values:
a SettheSEG4valuebyrotatingtheWheel
counterclockwiseuntilthevalueyouwanttoset
appearsontheremotecontroldisplay.
SEG4
CAC_360 사우디향_냉방전용,냉난방_IM_EN_DB68-08576A-00.indb 20 2019-11-05 오후 12:52:21
/