Samsung AC140TN4PKG/SA Installation guide

Category
Split-system air conditioners
Type
Installation guide
Air conditioner
Installation manual
AC***TN4PKG
Thank you for purchasing this Samsung air conditioner.
Before operating this unit, please read this manual carefully and retain it for future
reference.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 1 2019-08-27 오후 3:49:06
2
English
Contents
Safety Information 3
Safety Information 3
Installation Procedure 5
Step 1 Checking and preparing accessories 5
Step 2 Choosing the installation location 5
Step 3 Optional: Insulating the body of the indoor unit 8
Step 4 Installing the indoor unit 8
Step 5 Purging inert gas from the indoor unit 10
Step 6 Cutting and flaring the pipes 10
Step 7 Connecting the assembly pipes to the refrigerant pipes 11
Step 8 Performing the gas leak test 12
Step 9 Insulating the refrigerant pipes 12
Step 10 Installing the drain hose and drain pipe 13
Step 11 Performing the drainage test 15
Step 12 Optional: For the installation of the circular panel 16
Step 13 Connecting the power and communication cables 17
Step 14 Optional: Extending the power cable 19
Step 15 Setting the indoor unit addresses and the installation options 20
Appendix 37
Troubleshooting 37
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 2 2019-08-27 오후 3:49:06
3
English
Safety Information
WARNING
• Hazardsorunsafepracticesthatmayresultinsevere
personalinjuryordeath.
CAUTION
• Hazardsorunsafepracticesthatmayresultinminor
personalinjuryorpropertydamage.
• Carefullyfollowtheprecautionslistedbelowbecausethey
areessentialtoguaranteethesafetyoftheequipment.
WARNING
• Alwaysdisconnecttheairconditionerfromthepowersupply
beforeservicingitoraccessingitsinternalcomponents.
• Verifythatinstallationandtestingoperationsareperformed
byqualifiedpersonnel.
• Verifythattheairconditionerisnotinstalledinaneasily
accessiblearea.
General information
WARNING
• Carefullyreadthecontentofthismanualbeforeinstalling
theairconditionerandstorethemanualinasafeplacein
ordertobeabletouseitasreferenceafterinstallation.
• Formaximumsafety,installersshouldalwayscarefully
readthefollowingwarnings.
• Storetheoperationandinstallationmanualinasafe
locationandremembertohanditovertothenewownerif
theairconditionerissoldortransferred.
• Thismanualexplainshowtoinstallanindoorunitwitha
splitsystemwithtwoSAMSUNGunits.Theuseofother
typesofunitswithdifferentcontrolsystemsmaydamage
theunitsandinvalidatethewarranty.Themanufacturer
shallnotberesponsiblefordamagesarisingfromtheuse
ofnoncompliantunits.
• Themanufacturershallnotberesponsiblefordamage
originatingfromunauthorizedchangesortheimproper
connectionofelectricandrequirementssetforthinthe
“Operatinglimits”table,includedinthemanual,shall
immediatelyinvalidatethewarranty.
• Theairconditionershouldbeusedonlyfortheapplications
forwhichithasbeendesigned:theindoorunitisnot
suitabletobeinstalledinareasusedforlaundry.
• Donotusetheunitsifdamaged.Ifproblemsoccur,switch
theunitoffanddisconnectitfromthepowersupply.
• Inordertopreventelectricshocks,firesorinjuries,always
stoptheunit,disabletheprotectionswitchandcontact
SAMSUNG’stechnicalsupportiftheunitproducessmoke,if
thepowercableishotordamagedoriftheunitisverynoisy.
• Alwaysremembertoinspecttheunit,electricconnections,
refrigeranttubesandprotectionsregularly.Theseoperations
shouldbeperformedbyqualifiedpersonnelonly.
• Theunitcontainsmovingparts,whichshouldalwaysbe
keptoutofthereachofchildren.
• Donotattempttorepair,move,alterorreinstalltheunit.
Ifperformedbyunauthorizedpersonnel,theseoperations
maycauseelectricshocksorfires.
• Donotplacecontainerswithliquidsorotherobjectsonthe
unit.
• Allthematerialsusedforthemanufactureandpackaging
oftheairconditionerarerecyclable.
• Thepackingmaterialandexhaustbatteriesoftheremote
controller(optional)mustbedisposedofinaccordancewith
currentlaws.
• Theairconditionercontainsarefrigerantthathastobe
disposedofasspecialwaste.Attheendofitslifecycle,the
airconditionermustbedisposedofinauthorisedcentres
orreturnedtotheretailersothatitcanbedisposedof
correctlyandsafely.
• Donotusemeanstoacceleratethedefrostoperationorto
clean,otherthanthoserecommendedbySamsung.
• Donotpierceorburn.
• Beawarethatrefrigerantsmaynotcontainanodour.
Installing the unit
WARNING
IMPORTANT: When installing the unit, always remember to
connect first the refrigerant tubes, then the electrical lines.
• Alwaysdisassembletheelectriclinesbeforetherefrigerant
tubes.
• Uponreceipt,inspecttheproducttoverifythatithasnot
beendamagedduringtransport.Iftheproductappears
damaged,DONOTINSTALLitandimmediatelyreportthe
damagetothecarrierorretailer(iftheinstallerorthe
authorizedtechnicianhascollectedthematerialfromthe
retailer.)
• Aftercompletingtheinstallation,alwayscarryouta
functionaltestandprovidetheinstructionsonhowto
operatetheairconditionertotheuser.
• Donotusetheairconditionerinenvironmentswith
hazardoussubstancesorclosetoequipmentthatrelease
freeflamestoavoidtheoccurrenceoffires,explosionsor
injuries.
Safety Information
Safety Information
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 3 2019-08-27 오후 3:49:06
4
English
Safety Information
Safety Information
• Donotinstalltheproductinaplacewherethermohygrostat
isneeded(suchasserverroom,machineryroom,computer
room,etc.)Thoseplacesdonotprovideguaranteed
operationconditionoftheproductthereforeperformance
canbepoorintheseplaces.
• Donotinstalltheproductinashiporavehicle(suchasa
campervan).Salt,vibrationorotherenvironmentalfactor
maycausetheproductmalfunction,electricshockorfire.
• Ourunitsshouldbeinstalledincompliancewiththespaces
shownintheinstallationmanual,toensureaccessibility
frombothsidesandallowrepairsormaintenance
operationstobecarriedout.Theunit’scomponentsshould
beaccessibleandeasytodisassemblewithoutendangering
peopleandobjects.
Forthisreason,whenprovisionsoftheinstallationmanual
arenotcompliedwith,thecostrequiredtoaccessand
repairtheunits(inSAFETYCONDITIONS,assetoutin
prevailingregulations)withharnesses,ladders,scaffolding
oranyotherelevationsystemwillNOTbeconsideredpart
ofthewarrantyandwillbechargedtotheendcustomer.
Do not install the air conditioner in following places.
• Placewherethereismineraloilorarsenicacid.Resinparts
flameandtheaccessoriesmaydroporwatermayleak.
Thecapacityoftheheatexchangermayreduceortheair
conditionermaybeoutoforder.
• Theplacewherecorrosivegassuchassulphuricacidgas
generatesfromtheventpipeorairoutlet.
• Thecopperpipeorconnectionpipemaycorrodeand
refrigerantmayleak.
• Theplacewherethereisamachinethatgenerates
electromagneticwaves.Theairconditionermaynotoperate
normallyduetocontrolsystem.
• Theplacewherethereisadangerofexistingcombustible
gas,carbonfibreorflammabledust.
• Theplacewherethinnerorgasolineishandled.Gasmay
leakanditmaycausefire.
Power supply line, fuse or circuit
breaker
WARNING
• Alwaysmakesurethatthepowersupplyiscompliantwith
currentsafetystandards.Alwaysinstalltheairconditioner
incompliancewithcurrentlocalsafetystandards.
• Alwaysverifythatasuitablegroundingconnectionis
available.
• Verifythatthevoltageandfrequencyofthepowersupply
complywiththespecificationsandthattheinstalledpower
issufficienttoensuretheoperationofanyotherdomestic
applianceconnectedtothesameelectriclines.
• Alwaysverifythatthecut-offandprotectionswitchesare
suitablydimensioned.
• Verifythattheairconditionerisconnectedtothepower
supplyinaccordancewiththeinstructionsprovidedinthe
wiringdiagramincludedinthemanual.
• Alwaysverifythatelectricconnections(cableentry,section
ofleads,protections…)arecompliantwiththeelectric
specificationsandwiththeinstructionsprovidedinthe
wiringscheme.Alwaysverifythatallconnectionscomply
withthestandardsapplicabletotheinstallationofair
conditioners.
• Devicesdisconnectedfromthepowersupplyshouldbe
completelydisconnectedintheconditionofovervoltage
category.
• Besurenottoperformpowercablemodification,extension
wiring,andmultiplewireconnection.
Itmaycauseelectricshockorfireduetopoor
connection,poorinsulation,orcurrentlimitoverride.
Whenextensionwiringisrequiredduetopowerline
damage,referto"Step 14 Optional: Extending the
power cable"intheinstallationmanual.
CAUTION
Make sure that you earth the cables.
• Donotconnecttheearthwiretothegaspipe,water
pipe,lightingrodortelephonewire.Ifearthingisnot
complete,electricshockorfiremayoccur.
Install the circuit breaker.
• Ifthecircuitbreakerisnotinstalled,electricshockor
firemayoccur.
Make sure that the condensed water dripping from the
drain hose runs out properly and safely.
Install the power cable and communication cable of
the indoor and outdoor unit at least 1m away from the
electric appliance.
Install the indoor unit away from lighting apparatus
using the ballast.
• Ifyouusethewirelessremotecontrol,receptionerror
mayoccurduetotheballastofthelightingapparatus.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 4 2019-08-27 오후 3:49:06
5
Installation Procedure
English
Installation Procedure
Installation Procedure
Step 1 Checking and preparing
accessories
Thefollowingaccessoriesaresuppliedwiththeindoor
unit.Thetypeandquantitymaydiffer,dependingonthe
specifications.
Insulation pipe Cable-tie Drain hose
Installation manual
Clamp User manual
Installation template
Dimension gauge
Step 2 Choosing the installation location
Installation location requirements
• Theremustbenoobstaclesneartheairinletandoutlet.
• Installtheindoorunitonaceilingthatcansupportitsweight.
• Maintainsufficientclearancearoundtheindoorunit.
• Beforeinstallingtheindoorunit,besuretocheckwhetherthe
chosenlocationiswell-drained.
• Theindoorunitmustbeinstalledsuchthatitisbeyondpublic
accessandisnottouchablebyusers.
• Rigidwallwithoutvibration.
• Whereitisnotexposedtodirectsunshine.
• Wheretheairfiltercanberemovedandcleanedeasily.
• Theplacewhereanimalsmayurinateontheproduct
Ammoniamaybegenerated.
• Theplacewhereisclosetoheatsources.
• Donotusetheindoorunitforpreservationoffood
items,plants,equipment,andartworks.Thismaycause
deteriorationoftheirquality.
• Donotinstalltheindoorunitifithasanydrainageproblem.
WARNING
• BecauseyourairconditionercontainsR-32
refrigerant,makesurethatitisinstalled,operated,
andstoreditinaroomwhosefloorareaislarger
thantheminimumrequiredfloorareaspecifiedinthe
followingtable:
m (kg) Ceiling-mounted type (A, m)
≤1.842 Norequirement
1.843 3.64
1.9 3.75
2.0 3.95
2.2 4.34
2.4 4.74
2.6 5.13
2.8 5.53
3.0 5.92
3.2 6.48
3.4 7.32
3.6 8.20
3.8 9.14
4.0 10.1
4.2 11.2
4.4 12.3
4.6 13.4
4.8 14.6
5.0 15.8
5.2 17.1
m:Totalrefrigerantchargeinthesystem
A:Minimumrequiredfloorarea
• IMPORTANT:it’smandatorytoconsidereitherthe
tableaboveortakingintoconsiderationthelocallaw
regardingtheminimumlivingspaceofthepremises.
• Minimuminstallationheightofindoorunitis0.6m
forfloormounted,1.8mforwall,2.2mforceiling.
CAUTION
• Asarule,theunitcannotbeinstalledataheightof
lessthat2.5m.
• Ifyouinstallthecassetteorducttypeindooruniton
theceilingwithhumidityover80%,youmustapply
extra10mmofpolyethylenefoamorotherinsulation
withsimilarmaterialonthebodyoftheindoorunit.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 5 2019-08-27 오후 3:49:07
6
Installation Procedure
Installation Procedure
English
Indoor unit dimensions
(Unit:mm)
Category Square panel Circular panel
Front
1000
358
Ceiling opening dimension
960 (950 - 960)
Ceiling opening dimension
960 (950 - 960)
116
1050
883
Large+,
Large
385
166
66
357
404
128
181
190
317
Drain hose
connector
Refrigerant
pipe
Wire insert hole
100
153
162
289
138
94
Small
385
166
66
357
404
128
181
190
233
Drain hose
connector
Refrigerant
pipe
Wire insert hole
100
153
162
205
138
94
Common
646
646
942
787
80
ø100
H1
H1Large+,Large:180,Small:150
H2Large+,Large:152,Small:122
H2
Square panel Circular panel
Model AC071TN4PKG AC100TN4PKG AC120TN4PKG AC140TN4PKG
Chassis Large Large+
Net dimension (W × D × H) mm 947X947X365 947x947x365 947x947x365 947x947x365
Net weight kg 23.5 25.5 25.5 25.5
Liquid pipe connection mm 6.35 9.52 9.52 9.52
Gas pipe connection mm 15.88 15.88 15.88 15.88
Drain hose connection mm Outerdiameter:Ø32,Innerdiameter:Ø26.5
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 6 2019-08-27 오후 3:49:08
7
Installation Procedure
English
• Thecircularpanelisbydefaultavailableinexposed
installation.
• Makeinspectionholesontheceilingforeasier
installationandmaintenance,asshowninthe
followingtable.(Thesizeofaninspectionholemust
beatleast450mmx450mm.)
• Asuspendedceilingstructurecansubstituteforthe
inspectionholes.
Category
Inspection hole
Recessed installation
Exposed
installation
Integrated suspended
Square panel
1ea
-
Circular panel
2ea
•
Fortherecessedinstallationofthecircularpanel
Refrigerant
pipe
Connection part of the
drain hose
Indoor unit
display
Inspection hole
1050
(Unit: mm)
883
ø1010 to 1020
Ceiling opening diameter
ø1010 to 1020
Inspection hole
NOTE
• Theclearancebetweenthepanelandtheinspection
holeis15to20mmonaside.
Spacing requirements
A
A : 1500 mm or more
A
A
A
'C'
Indoor unit
2500 mm or more
Obstruction
20 mm
1500 mm or
more
10 mm
(Unit:mm)
Model
AC071TN4PKG AC100TN4PKG AC120TN4PKG AC140TN4PKG
C 345 345 345 345
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 7 2019-08-27 오후 3:49:08
8
Installation Procedure
Installation Procedure
English
CAUTION
• Complywiththelengthandheightlimitsdescribedinthe
figureabove.
• FortheproductthatusestheR-32refrigerant,Installthe
indoorunitonthewall1.8morhigherfromthefloor.
• Theindoorunitmustbeinstalledaccordingtothe
specifieddistancesinordertopermitaccessibilityfrom
eachside,toguaranteecorrectoperation,maintenance,
andrepairoftheunit.
Thecomponentsoftheindoorunitmustbereachableand
removableundersafeconditionsforpeopleandtheunit.
• Donotholdthedischargewhilecarryingtheindoorunit
toavoidthepossibilityofbreakage.
• Youmustholdthehangerplateonthecornerandcarry
theindoorunit.
Step 3 Optional: Insulating the body
of the indoor unit
Ifyouinstallacassettetypeindoorunitontheceiling
whentemperatureisover27°Candhumidityisover
80%,youmustapplyanextra10mmthickpolyethylene
insulationorasimilartypeofinsulationtothebodyof
theindoorunit.
Cutawaythepartwherepipesarepulledoutforthe
insulatingwork.
A
Insulatetheendofthepipeandsomecurvedareaby
usingseparateinsulator.
NOTE
• A:Referencefortheoutercircumferenceoftheunit
(Wheninsulatingthebodyoftheindoorunit,useAas
thereferenceforitsoutercircumference.)
(Unit:mm)
Indoor unit type and models Dimensions
360cassettetype<L>
(947X947X365)
AC071TN4PKG 2610X215
360cassettetype<L+>
(947x947x365)
AC100TN4PKG
2610x215AC120TN4PKG
AC140TN4PKG
Step 4 Installing the indoor unit
Whendecidingonthelocationoftheairconditionerthe
followingrestrictionsmustbetakenintoaccount.
1 Determinethepositionsofthepipeandthedrain
hoseholeasshowninthepatternsheet,anddrillthe
holewithaninnerdiameterof14mm.
NOTE
• Sincethediagramismadeofpaper,itmayshrinkor
stretchslightlyduetotemperatureorhumidity.Forthis
reason,beforedrillingtheholes,besuretomaintainthe
correctdimensionsbetweenthemarkings.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 8 2019-08-27 오후 3:49:08
9
Installation Procedure
English
2 Performthefollowingstepstoinstallinspectionholes
inaccordancewiththepaneltype.
a Fortherecessedinstallationofthesquarepanel.
• Installaninspectionholetothedirectionof
connectionpartsoftherefrigerantpipeandthe
drainhose.(1point)
Indoor unit
display
Refrigerant pipe
Inspection hole
b Forrecessedinstallationofthecircularpanel
• Installinspectionholestobothdirectionsofthe
connectionpartoftherefrigerantpipeandthe
drainhoseandoftheindoorunitdisplay.
(2points)
Refrigerant pipe
Indoor unit display
Inspection hole
Inspection hole
3 Insertboltanchors,useexistingceilingsupportsor
constructasuitablesupportasshowninfigure.
Concrete
Hole in anchor
Hole in plug
Suspension bolt (M10) - eld supply
Insert
4 Installthesuspensionbolts,dependingontheceiling
type.
Ceiling support
CAUTION
• Makesurethattheceilingisstrongenoughtosupport
theweightoftheindoorunit.Beforehangingthe
unit,testthestrengthofeachattachedsuspension
bolt.
• Ifthelengthofthesuspensionboltismorethan1.5
m,youarerequiredtopreventvibration.
5 Screweightpairsofnutsandwasherstothe
suspensionbolts,makingspaceforhangingthe
indoorunit.
CAUTION
• Youmustinstallallofthesuspensionrods.
• Itisimportanttoleavesufficientspaceinthefalse
ceilingtoallowaccessformaintenanceorrepairsto
thedrainagepipeconnection,therefrigerantpipe
connection,ortoremovetheunitifnecessary.
6 Hangtheindoorunittothesuspensionboltsbetween
twonuts.Cutapadstopperandplaceitonthe
suspensionboltstoholdthewashers.Removethe
stopperandscrewthenutstofixtheunit.
Pad stopper
Bracket
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 9 2019-08-27 오후 3:49:09
10
Installation Procedure
Installation Procedure
English
7 Adjusttheunittotheappropriateposition,takinginto
accounttheinstallationareaforthefrontpanel.
• Placethepatternsheetontheindoorunit.
• Adjustthespacebetweentheceilingandthe
indoorunitbyusingadimensiongauge.
• Fixtheindoorunitsecurelyafteradjustingthe
leveloftheunitbyusingaleveller.
• Removethepatternsheet,connecttheother
cables.andinstallthefrontpanel.
For the recessed installation
of the square panel: 11.5 mm
For the recessed installation
of the circular panel: 41.5 mm
Indoor unit
Ceiling
Gauge of dimensions
Step 5 Purging inert gas from the
indoor unit
Theindoorunitcomeswithnitrogengas(inertgas)
chargedatthefactory.Therefore,allinertgasmustbe
purgedbeforeconnectingtheassemblypiping.
Unscrew the pinch pipe at the end of each refrigerant
pipe.
Liquid side
Gas side
Insulator
NOTE
• Topreventdirtorforeignobjectsfromgettinginto
thepipesduringinstallation,donotremovethepinch
pipecompletelyuntilyouarereadytoconnectthe
piping.
Step 6 Cutting and flaring the pipes
1 Makesurethatyouhavetherequiredtoolsavailable:
pipecutter,reamer,flaringtool,andpipeholder.
2 Ifyouwishtoshortenthepipes,cutthemwithapipe
cutter,ensuringthatthecutedgeremainsata90°
angletothesideofthepipe.Refertotheillustrations
belowforexamplesofedgescutcorrectlyand
incorrectly.
Pipe cutter
Pipe
Oblique
Rough
Burr
3 Topreventanygasfromleakingout,removeallburrs
atthecutedgeofthepipe,usingareamer.
4 Slideaflarenutontothepipeandmodifytheflare.
Pipe
Flare
D
A
Flare
R 0.4 to 0.8 mm
D
L
90° ±2°
45° ±2°
Outer Diameter (D) Depth (A) Flare dimension (L)
Ø6.35mm 1.3mm 8.7to9.1mm
Ø9.52mm 1.8mm 12.8to13.2mm
Ø12.70mm 2.0mm 16.2to16.6mm
Ø15.88mm 2.2mm 19.3to19.7mm
Ø19.05mm 2.2mm 23.6to24.0mm
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 10 2019-08-27 오후 3:49:09
11
Installation Procedure
English
5 Checkthattheflaringiscorrect,referringtothe
illustrationsbelowforexamplesofincorrectflaring.
Correct
Inclined
Damaged
Surface
Cracked
Uneven
Thickness
Step 7 Connecting the assembly
pipes to the refrigerant pipes
There are two refrigerant pipes of different diameters :
• Asmalleronefortheliquidrefrigerant.
• Alargeroneforthegasrefrigerant.Theinsideof
copperpipemustbecleanandhasnodust.
1 Removethepinchpipeonthepipesandconnectthe
assemblypipestoeachpipe,tighteningthenuts,first
manuallyandthenwithatorquewrench,aspanner
applyingthefollowingtorque.
Torque
wrench
Flare nut
Spanner
Union
Outer Diameter (mm) Torque (N•m)
Ø6.35 14to18
Ø9.52 34to42
Ø12.70 49to61
Ø15.88 68to82
Ø19.05 100to120
(1N•m=10kgf•cm)
NOTE
• Ifthepipesmustbeshortened,seeStep 6 Cutting
and flaring the pipesonpage10.
2 Besuretouseaninsulatorthickenoughtocoverthe
refrigeranttubetoprotectthecondensatewateron
theoutsideofthepipefallingontothefloorandto
improvetheefficiencyoftheunit.
3 Cutoffanyexcessfoaminsulation.
4 Makesurethattherearenocracksorwavesonthe
bentarea.
5 Itwouldbenecessarytodoubletheinsulation
thickness(10mmormore)topreventcondensation
evenontheinsulatorwheniftheinstalledareais
warmandhumid.
CAUTION
• Connecttheindoorandoutdoorunitsusingpipes
withflaredconnections(notsupplied).Forthelines,
useinsulated,unwelded,degreasedanddeoxidized
copperpipe(CuDHPtypetoISO1337orUNIEN
12735-1),suitableforoperatingpressuresofatleast
4.2MPaandforaburstpressureofatleast20.7MPa.
Copperpipeforhydro-sanitaryapplicationsis
completelyunsuitable.
• Forsizingandlimits(heightdifference,linelength,
max.bends,refrigerantcharge,etc.)seetheoutdoor
unitinstallationmanual.
• Allrefrigerantconnectionmustbeaccessible,inorder
topermiteitherunitmaintenanceorremovingit
completely.
• Ifthepipesrequirebrazing,makesurethatoxygen
freenitrogen(OFN)isflowingthroughthesystem.
• Nitrogenblowingpressurerangeis0.02to0.05MPa.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 11 2019-08-27 오후 3:49:09
12
Installation Procedure
Installation Procedure
English
Step 8 Performing the gas leak test
Toidentifypotentialgasleaksontheindoorunit,inspect
theconnectionareaofeachrefrigerantpipeusingaleak
detectorforR-410A.
Beforerecreatingthevacuumandrecirculatingthe
refrigerantgas,pressurizethewholesystemwith
nitrogen(usingacylinderwithapressurereducer)ata
pressureabove4MPainordertoimmediatelydetect
leaksontherefrigerantfittings.
Madevacuumfor15minutesandpressurizingsystem
withnitrogen.
Liquid side
Gas side
Insulator
Step 9 Insulating the refrigerant pipes
Onceyouhavecheckedthattherearenoleaksinthe
system,youcaninsulatethepipingandhose.
1 Toavoidcondensationproblems,placeAcrylonitrile
ButadienRubberseparatelyaroundeachrefrigerantpipe.
No gap
NBR
NOTE
• Alwaysmaketheseamofpipesfaceupwards.
2 Windinsulatingtapearoundthepipesanddrainhose
avoidingcompressingtheinsulationtoomuch.
Indoor unit
Insulation cover pipe
Insulation pipe
Be sure to overlap
the insulation.
CAUTION
• Besuretowrapinsulationtightlywithoutanygaps.
3 Finishwrappinginsulatingtapearoundtherestofthe
pipesleadingtotheoutdoorunit.
4 Thepipesandelectricalcablesconnectingtheindoor
unitwiththeoutdoorunitmustbefixedtothewall
withsuitableducts.
CAUTION
• Makesurethatallrefrigerantconnectionmustbe
accessibleforeasymaintenanceanddetachment.
• Installtheinsulationnottogetwiderandusethe
adhesivesontheconnectionpartofittoprevent
moisturefromentering.
• Windtherefrigerantpipewithinsulationtapeifitis
exposedtooutsidesunlight.
• Installtherefrigerantpiperespectingthatthe
insulationdoesnotgetthinneronthebentpartor
hangerofpipe.
• Addtheadditionalinsulationiftheinsulationplate
getsthinner.
Refrigerant pipe insulation
a x 3
Hanger
Additional insulation
a
5 Selecttheinsulationoftherefrigerantpipe.
• Insulatethegassideandliquidsidepipe,noting
theinsulationthicknessthatmustdifferaccording
tothepipesize.
• Standard:Lessthananindoortemperatureof30°C,
withhumidityat85%.Ifinstallinginahighhumidity
environment,useonegradethickerinsulatorby
referringtothetablebelow.Ifinstallinginan
unfavourableenvironment,usethickerone.
• Theheat-resistancetemperatureoftheinsulator
mustbemorethan120°C.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 12 2019-08-27 오후 3:49:10
13
Installation Procedure
English
Pipe
Pipe size
(mm)
Insulation type (heating/cooling)
Remarks
Standard
(Less than 30°C,
85%)
High humidity
(Over 30°C, 85%)
EPDM, NBR (mm)
Liquid
pipe
Ø6.35to
Ø9.52
9t 9t
Theinternal
temperature
ishigher
than120°C.
Ø12.7to
Ø19.05
13t 13t
Gas
pipe
Ø6.35 13t 19t
Ø9.52
19t 25t
Ø12.70
Ø15.88
Ø19.05
• Wheninstallinginsulationintheplacesand
conditionsbelow,usethesameinsulationthatis
usedforhighhumidityconditions.
<Geological condition>
Highhumiditylocationssuchasshorelines,hot
springs,lakeorriversides,andridges(whenpartof
thebuildingiscoveredbyearthandsand)
<Operation purpose condition>
Restaurantceiling,sauna,swimmingpooletc.
<Building construction condition>
Ceilingsfrequentlyexposedtomoistureandcooling
arenotcovered.Forexample,pipesinstalledata
corridorofadormitoryandstudioornearanexitthat
opensandclosesfrequently.
Places(wherethepipesareinstalled)thatarehighly
humidduetoalackofventilation.
Step 10 Installing the drain hose and
drain pipe
1 Pushthesupplieddrainhoseasfaraspossibleover
thedrainsocket.
2 Tightenthemetalclampasshowninthepicture.
3 Wrapthesuppliedlargesealingpadoverthemetal
clampanddrainhosetoinsulateandfixitwith
clamps.
4 Insulatethecompletedrainpipinginsidethebuilding
(fieldsupply).
Ifthedrainhosecannotbesufficientlysetonaslope,
fitthehosewithdrainraisingpiping(fieldsupply).
5 Pushthedrainhoseuptoinsulationwhenconnecting
thedrainhosetodrainsocket.
Metal clamp
Drain socket
Drain hose
Large seailng pad
Be sure to bond the drain
hose and the main pipe.
Drain pipe
Drain hose
PVC Tube Joint
+ VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 13 2019-08-27 오후 3:49:10
14
Installation Procedure
Installation Procedure
English
CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
• Installairventilationtodraincondensationsmoothly.
Air ventilation
Ceiling
• Ifitisnecessarytoincreasetheheightofthedrain
pipe,installthedrainpipestraightwithin300mm
fromthedrainhoseport.Ifitisraisedhigherthan
550mm,theremaybewaterleaks.
Band joint
300 mm
or less
20 mm or more
Drain hose
Ceiling
550 mm or less
• Donotgivethehoseanupwardgradientbeyond
theconnectionport.Thiswillcausewatertoflow
backwardswhentheunitisstopped,resultingin
waterleaks.
Under gradient
Ceiling
• Donotapplyforcetothepipingontheunitside
whenconnectingthedrainhose.Thehoseshouldnot
beallowedtohangloosefromitsconnectiontothe
unit.Fastenthehosetoawall,frameorothersupport
asclosetotheunitaspossible.
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
• Installhorizontally.
Indoor unit
Be horizontal
Flexible hose
• Max.allowableaxisgap.
Indoor unit
Max. 20 mm
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 14 2019-08-27 오후 3:49:11
15
Installation Procedure
English
• Max.allowablebendingangle.
Indoor unit
Max. 30˚
NOTE
• Ifaconcentrateddrainpipeisinstalled,refertothe
figurebelow.
Centralized horizontal drain
pipe
(more than 1/100 slope)
Main drain pipe
Full thread bolt hanger
1000 to 1500 mm
300 to
550 mm
200 mm
or more
Individual
air vent
Main air vent
(must be installed)
Step 11 Performing the drainage test
1 Doaleaktestattheconnectionpartoftheflexible
hoseandthedrainpipe:
a Connectageneralhosetotheconnectionpartof
theflexiblehoseoftheindoorunit,andpourin
somewater.
Hose
Flexible hose
Water leakage
check part
b Afterpouringsomewater,reassembletherubber
capontheconnectionpartofaflexiblehoseof
theindoorunitandfirmlytightenitwithaband
topreventleakage.
c Checktheleaktestatthepartwheretheadhesive
fortheflexiblehoseandthedrainpipeisused.
CAUTION
• Theleaktestmustbeperformedforatleast24hours.
2 Checkthecondensedwaterdrainage:
a Pourabout2litersofwaterintotheindoorunit
drainpanasshowninthepicture.
b Whentheelectriccableconnectioniscompleted
• Turnontheindoorunitandoutdoorunit.
• OperateintheCoolmode.
CAUTION
• OnlyintheCoolmode,youcancheckthecorrect
operationofthedrainpump.
Whentheelectriccableconnectionhasnotbeen
completed
• Removethecontrolboxcoveroftheindoorunit.
• Connectthepowersupply(220~240V,50Hz)to
theLandNterminals.
• Reassemblethecontrolboxcoverandturnonthe
indoorunit.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 15 2019-08-27 오후 3:49:11
16
Installation Procedure
Installation Procedure
English
CAUTION
• Whenthefloatswitchisnotdetecteddueto
insufficientwateronthedrainpan,thedrain
pumpwillnotwork.
• Ifthepowersupplyisdirectlyconnectedtothe
LandNterminals,communicationerrormessage
mightappear.
• Aftercompletingthedrainagecheck,turnthe
unitoffanddisconnectthepowersupply.
• Reassemblethecontrolboxcover.
c Checkwhetherthedrainpumpworkscorrectly.
d Checkwhetherthedrainageisperforming
correctlyattheendofthedrainpipe.
e Checkforleakageatthedrainpipeanddrainpipe
connectionpart.
f Whenleakageoccurs,checkwhethertheindoor
unitislevelandcheckthedrainhoseconnection
part,drainpipeconnectionpartanddrainpump
connection.
g Whenthedrainagecheckiscompletedandthe
condensedwaterremainsonthedrainpan,
removethewater.
Step 12 Optional: For the installation
of the circular panel
Making a circular opening on the ceiling
Useapapercompassprintedontheindoorunitpackage.
(attachedinsidetotheupperpart)
1 Useaboltorapintofixpivotpointofthepaper
compassoncenteroftheceiling.(inthemiddleof
locationforinstallation)
2 Putapencilattheoppositesideofthepivotpoint
fixedinplace.
3 Rotatethepapercompassonitspivotpointtodrawa
lineontheceiling.
4 Rotatethepapercompassdiametricallytodrawa
circleontheceiling.
For the painting of the panel
• Makesuretoonlyapplypaintsandvarnishesfor
resins(ABS,HIPS)orpaintthinners.
• Ifyouapplylacquersforgeneraluseonthepanel,it
mayleadtodiscolorationorerosiononthesurfaceof
thepanel.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 16 2019-08-27 오후 3:49:11
17
Installation Procedure
English
Step 13 Connecting the power and
communication cables
CAUTION
• Alwaysremembertoconnecttherefrigerantpipes
beforeperformingtheelectricconnections.
Whendisconnectingthesystem,alwaysdisconnect
theelectriccablesbeforedisconnectingthe
refrigerantpipes.
• FortheproductthatusestheR-32refrigerant,be
cautiousnottogenerateasparkbykeepingthe
followingrequirements:
Donotremovethefuseswithpoweron.
Donotdisconnectthepowerplugfromthewall
outletwithpoweron.
Itisrecommendedtolocatetheoutletinahigh
position.Placethecordssothattheyarenot
tangled.
• Alwaysremembertoconnecttheairconditionerto
thegroundingsystembeforeperformingtheelectric
connections.Useacrimpringterminalattheendof
eachwire.
Theindoorunitispoweredthroughtheoutdoorunitby
meansofaH07RN-Fconnectioncable(oramorepower
model),withinsulationinsyntheticrubberandajacket
inpolychloroprene(neoprene),inaccordancewiththe
requirementsspecifiedinthestandardEN60335-2-40.
1 Removethescrewontheelectricalcomponentbox
andremovethecoverplate.
2 Routetheconnectioncordthroughthesideofthe
indoorunitandconnectthecabletotheterminals
refertothefigurebelow.
3 Routetheotherendofthecabletotheoutdoorunit
throughtheceiling&theholeonthewall.
4 Reassembletheelectricalcomponentboxcover,
carefullytighteningthescrew.
Wiring terminals) 1 phase
1(L) 2(N) L N
F1 F2
F1 F2
L N
Indoor power
Main power cable
Communication
cable
Indoor unit
Outdoor unit
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 17 2019-08-27 오후 3:49:11
18
Installation Procedure
Installation Procedure
English
Wiring terminals) 3 phase
1(L) 2(N) L1(R) L2(S) L3(T) N
F1 F2
F1 F2
L N
Indoor power
Main power cable
Communication
cable
Indoor unit
Outdoor unit
NOTE
• Insertthepowerandthecommunicationcablesto
thecableinserthole,thenarrangeandconnectthe
cables,asshowninthefigure:
Cable insert
hole
Power cable Communication
cable
Indoor power supply
Power supply Max/Min(V) Indoor power cable
220to240V,50Hz
±10%
0.75mm²,3wires
Communication cable
0.75mm²,2wires
AC power: M4 screw
Communication: M3.5 screw
9.8
12.6
7.5
9.0
19
13.8
(Unit: mm)
Tightening torque (kgf • cm)
M3.5 8.0to12.0
M4 12.0to18.0
• 1N·m=10kgf·cm
• Powersupplycordsofpartsofappliancesfor
outdooruseshallnotbelighterthanpolychloroprene
sheathedflexiblecord.(CodedesignationIEC:60245
IEC57/CENELEC:H05RN-ForIEC:60245IEC66/
CENELEC:H07RN-F)
• Sinceithastheexternalpowersupply,refertothe
outdoorunitinstallationmanualforMAINPOWER.
CAUTION
• Wheninstallingtheindoorunitinacomputer
roomornetworkroom,usethedoubleshielded
communicationcable(tapealuminum/polyester
braid+copper)ofFROHH2Rtype.
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 18 2019-08-27 오후 3:49:12
19
Installation Procedure
English
Step 14 Optional: Extending the
power cable
1 Preparethefollowingtools.
Tools Spec Shape
Crimpingpliers MH-14
Connectionsleeve
(mm)
20xØ6.5
(HxOD)
Insulationtape
Width19
mm
Contractiontube
(mm)
70xØ8.0
(LxOD)
2 Asshowninthefigure,peelofftheshieldsfromthe
rubberandwireofthepowercable.
• Peeloff20mmofcableshieldsfromthepre-
installedtube.
CAUTION
• Forinformationaboutthepowercable
specificationsforindoorandoutdoorunits,refer
totheinstallationmanual.
• Afterpeelingoffcablewiresfromthepre-installed
tube,insertacontractiontube.
• Ifcablewiresareconnectedwithoutusing
connectingsleeves,theircontactareabecomes
reduced,orcorrosiondevelopsontheouter
surfacesofthewires(copperwires)overalong
time.Thismaycauseanincreaseofresistance
(reductionofpassingcurrent)andconsequently
mayresultinafire.
20 20 20
60
120
180
Powercable
202020
60
120
Pre-installedtube
forthepowercable
(Unit:mm)
3 Insertbothsidesofcorewireofthepowercableinto
theconnectionsleeve.
• Method 1:Pushthecorewireintothesleevefrom
bothsides.
• Method 2:Twistthewirecorestogetherandpush
itintothesleeve.
Connection sleeve Connection sleeve
Method 1 Method 2
4 Usingacrimpingtool,compressthetwopointsand
flipitoverandcompressanothertwopointsinthe
samelocation.
• Thecompressiondimensionshouldbe8.0.
Compression
dimension
• Aftercompressingit,pullbothsidesofthewireto
makesureitisfirmlypressed.
Compressit4times
5mm
Method1
Compressit4times
5mm
Method2
5 Wrapitwiththeinsulationtapetwiceormoreand
positionyourcontractiontubeinthemiddleofthe
insulationtape.
40mm
Insulationtape
Method1
35mm
Insulationtape
Method2
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 19 2019-08-27 오후 3:49:12
20
Installation Procedure
Installation Procedure
English
6 Applyheattothecontractiontubetocontractit.
Contractiontube
Contractiontube
Method1
Method2
7 Aftertubecontractionworkiscompleted,wrapitwith
theinsulationtapetofinish.
Threeormorelayersofinsulationarerequired.
Insulationtape
Insulationtape
Method1
Method2
CAUTION
• Makesurethattheconnectionpartsarenotexposed
tooutside.
• Besuretouseinsulationtapeandacontractiontube
madeofapprovedreinforcedinsulatingmaterialsthat
havethesamelevelofwithstandvoltagewiththe
powercable.(Complywiththelocalregulationson
extensions.)
WARNING
• Incaseofextendingtheelectricwire,pleaseDONOT
usearound-shapedPressingsocket.
Incompletewireconnectionscancauseelectric
shockorafire.
Step 15 Setting the indoor unit
addresses and the installation options
Youcannotsetbothoftheindoorunitaddressesand
theinstallationoptionsinabatch:setbothofthem
respectively.
Common steps for setting the addresses and
options
AR-KH00E/AR-KH03E remote control (for 360 cassette
only)
Temperature
button
Timerbutton
Wheel
Modebutton
Setting the
option values
Entering the
mode for setting
the options
NOTE
• Theremotecontroldisplaymayvarydependingon
themodel.
1 Enterthemodeforsettingtheoptions:
a Removethebatteriesfromtheremotecontrol.
b Whileholdingdownthe
(Temp)and
(Timer)buttonssimultaneously,insertthe
batteriesintotheremotecontrol.
c Makesurethatyouareenteredtothemodefor
settingtheoptions:
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 20 2019-08-27 오후 3:49:13
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40