  • Hello! I am an AI chatbot trained to assist you with the Cash Valve PBE-1 Repair Kit Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
CASH PBE-1 REPAIR KIT
INSTALLATION INSTRUCTIONS
Before installation, these instructions must be carefully read and understood.
INSTALLATION
1. Loosen Lock Nut 1/4 turn and loosen
Adjusting Screw until the Pressure Spring is
no longer under tension. - see Fig. 1.
NOTE
When installing the Adjusting Screw during re-
assembly, tighten the screw until the Lock Nut just
touches the Spring Chamber. When the Valve is placed
in service the pressure setting should be very close to
the original setting.
2. Loosen and remove Spring Chamber and
remove Diaphragm Assembly and Seat
Ring.
3. Replace Seat Ring and Diaphragm Assembly
with components included in Kit. Ensure
the step on the Seat Ring is facing up - see
Fig 3. Also, Diaphragm Gasket must be
given a very light coating of Fluorolube and
installed between Body and Diaphragm
Assembly - see Fig 2.
IMPORTANT
Exercise care to ensure that the rounded surface of
the Ball Seat is not scratched, marred or damaged
during re-assembly.
4. Retighten Spring Chamber to 90 ft-lbs.
torque.
5. Remove Bottom Plug, Bottom Plug Gasket
and Piston Assembly and replace Gasket
and Piston Assembly with those included in
Kit - see Fig. 1. Retighten Bottom Plug to
35-40 ft-lbs. torque.
IMPORTANT
Do not overtighten.
6. Reset Adjusting Screw and tighten
LockNut- see NOTE.
Emerson.com/FinalControl © 2018 Emerson. All rights reserved. VCIOM-10771-EN 19/04
Adjusting Screw
Lock Nut
Pressure Spring
Seat Ring
Piston Assembly
Bottom Plug
Bottom Plug Gasket
Step Must
Face Up
Spring Chamber
Diaphragm
Assembly
Diaphragm
Assembly
Diaphragm
Gasket
Body
FIGURE 1
FIGURE 3
FIGURE 2
2
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Cash is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson
andthe Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by
our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without
notice.
Emerson.com/FinalControl
/