SICK UP30-211112 UP30-211114 Operating instructions

Category
Measuring, testing & control
Type
Operating instructions
We reserve the right to make changes without
prior notication
UP30-211112
UP30-211114
8013373
ENGLISH
Ultrasonic sensor
with 2 switching outputs
Operating Instructions
Safety Specications
No safety component in accordance with EU machine
guidelines.
Read the operating instructions before starting operation.
Connection, assembly, and settings only by competent
technicians.
Protect the device against moisture and soiling when
operating.
Proper Use
The UP30-211112 and UP30-211114 are ultrasonic sen-
sors and is used for non-contact level detection of uids.
Starting Operation
See ow chart C.
Maintenance
SICK sensors do not require any maintenance. We recom-
mend that you clean the external lens surfaces and check
the screw connections and plug-in connections at regular
intervals.
A
UP30-211112 / UP30-211114
B
T1 D1 D2 T2
1)
Reverse-polarity protected
2)
Without load
3)
Recovery time 32 ms …180 ms according to EMC EN 50319
4)
Temperature compensation at –25 …+50 °C, can be switched off
Australia
Phone +61 3 9497 4100
1800 33 48 02 – tollfree
Belgium/Luxembourg
Phone +32 (0)2 466 55 66
Brasil
Phone +55 11 3215-4900
Ceská Republika
Phone +420 2 57 91 18 50
China
Phone +852-2763 6966
Danmark
Phone +45 45 82 64 00
Deutschland
Phone +49 211 5301-301
España
Phone +34 93 480 31 00
France
Phone +33 1 64 62 35 00
Great Britain
Phone +44 (0)1727 831121
India
Phone +91–22–4033 8333
Israel
Phone +972-4-999-0590
Italia
Phone +39 02 27 43 41
Japan
Phone +81 (0)3 3358 1341
Nederlands
Phone +31 (0)30 229 25 44
Norge
Phone +47 67 81 50 00
Österreich
Phone +43 (0)22 36 62 28 8-0
Polska
Phone +48 22 837 40 50
Republic of Korea
Phone +82-2 786 6321/4
E-Mail kang@sickkorea.net
Republika Slowenija
Phone +386 (0)1-47 69 990
România
Phone +40 356 171 120
Russia
Phone +7 495 775 05 34
E-Mail info@sick-automation.ru
Schweiz
Phone +41 41 619 29 39
Singapore
Phone +65 6744 3732
Suomi
Phone +358-9-25 15 800
Sverige
Phone +46 10 110 10 00
Taiwan
Phone +886 2 2375-6288
Türkiye
Phone +90 216 587 74 00
USA/Canada/México
Phone +1(952) 941-6780
1 800-325-7425 – tollfree
Standard factory settings of UP30 are:
■ Q
1
: operating scanning range
■ Q
2
: ½ of operating scanning range), measurement range
(scanning distance limit)
UP30-211112 UP30 -211114
Operating scanning dist. 30-500mm (700mm) 30-500mm (700mm)
Ultrasound frequency 320kHz 320kHz
Resolution 0,18 mm 0,18 mm
Reproducibility ±0,15 % of limiting
scanning
±0,15 % of limiting scanning
Accuracy ≤ 2 % of limiting scanning ≤ 2 % of limiting scanning
Supply voltage
1)
9...30 V DC 9...30 V DC
Ripple ±10 % ±10 %
Current consumption
2)
≤ 80 mA ≤ 80 mA
Standby delay < 300 ms < 300 ms
Response time
3)
110 ms 110 ms
Switching output Q1, Q2: PNP Q1, Q2: NPN
Connection type M 12, 5-pin M 12, 5-pin
Process connection G 1/2 G 1/2
Pressure resistance/ area of use 0.5 - 6 bar gauge pressure 0.5 - 6 bar gauge pressure
Enclosure rating IP 67 IP 67
Ambient operating temperature
4)
-25 ... +70 °C -25 ... +70 °C
UP30-211112 / UP30-211114
1
L+
q
2
/Q
2
M
q
1
/Q
1
4
3
2
brn
blk
blu
wht
Sync/Com
5
gra
C
Flow chart
1
Numerical parameterization by LED display
Activate/deactivate
display touch control
Restore default settings
Add-on-Menü: Additional functions
switch off the
supply voltage
switch on the supply
voltage keeping T1
pressed down until »on«
or »off« appears
»on« or
»off«
»on« or
»off«
press T1 to activate
or deactivate
do not press any key
for 20 s
normal operation
switch off the supply
voltage
switch on the supply
voltage keeping T1
pressed down approx.
15 s until »rESEt«
has passed through
normal operation
Parameterization of Teach-in
≤ ±3° ≥ ±3°
smooth not smooth
Target objects with smooth surfaces shuld be
positioned at 90 degrees, relative to the sensor,
±3 tolerance. This tolerance could be greater
for target objects with a rough surface.
keep T1 and T2 pressed down approx. 3 s
until the welcoming text has passed through
set the switching
point in mm or cm
for a simple
switching point,
press T2 until
»- - -« appears
set the sensor-
remote switching
point in mm or cm for
window operation
2 T
1 T
2 T
2 T
1
T
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T + 1 T
2 T
1 T
2 T + 1 T
2 T + 1 T
2 T + 1 T
2T
1 T
set the switching output D1
finished
1
1
2
select the normally closed ( ) /
normally open ( ) contact
set the switching
point in mm or cm
for a simple
switching point,
press T2 until
»- - -« appears
set the sensor-
remote switching
point in mm or cm for
window operation
2T
1T
2T
2T
1
T
2T + 1T
1T
2T
2T + 1T
2T
1T
2T + 1T
2T + 1T
set the switching output D2
1
1
2
select the normally closed ( ) /
normally open ( ) contact
Set the switching point
D1/D2
position object at 1
press T1/T2 until
»d1«/»d2« appears
press T1/T2 until
»d1«/»d2« appears
press T1/T2 until
»d1«/»d2« appears
current measure-
ment value
press T1/T2 until
»End« appears
Set window operation
position object at 1 position reflector at 1
Objekt bei 2
positionieren
current measure-
ment value
current measure-
ment value
Aktueller
Messwert
press T1/T2 until
»End« appears
D1/D2
Set two-way photoelectric
reflex switch
D1/D2
Set normally closed/
normally open contact
press T1/T2 until the count-
down from »- 8 -« to »- 0 -«
finishes; NC or NO
symbol appears
press T1/T2 until the count-
down from »- 8 -« to »- 0 -«
finishes; »End« appears
press T1/T2 to change the
output function
press T1 and T2
until »End« appears
NC ( ) or
NO ( ) symbol
normal operation
1
1
2
1
teach in the switching output D1/D2
NC ( ) or
NO ( ) symbol
2T + 1T
1T
2T
2T + 1T
keep T1 and T2 pressed down approx. 13 s until the welcoming
text has passed through and »Add« appears in the LED display
2T + 1T
2T
1T
2T
1T
2T + 1T
finished
»C01«: bright display
»C02«: display dimmed
»C03«: display off
The highest assigned
sensor address can
be entered optionally
for optimizing multi-
plex speed.
setting range »01«
to »10«
»F00«: no filter
»F01«: standard filter
»F02«: average value
filter
»F03«: foreground-
filter
»F04«: background-
filter
strength of the selec-
ted measurement
value filter
»P00«: weak filter
effect
to
»P09«: strong filter
effect
Influences the size of
the detection range.
»E01«: high
»E02«: standard
»E03«: low
smallest value:
blind zone
largest value:
window border near
the sensor – 1
power-save mode
measurement
value filter
filter strength foreground
suppression
multiplex operation
device address
multiplex operation
highest address
»00«: synchronization
»01« to »10«:
sensor address
for multiplex
operation
»oFF«: synchronization
deactivated
smallest value:
sensor-remote
window border
largest value:
999 mm at
UM30-21111_ and
UM30-21211_
999 cm at
UM30-21311_,
UM30-21411_ and
UM30-21511_
measurement range calibration display detection range
sensitivity
Level reflector, at
least 200 x 200 mm
2
large, aligned at a
right angle to the sen-
sor, position exactly at
a distance of 250 mm
from the sensor with
UM30-21111_ and
UM30-21211_ and
at exactly a distance
of 900 mm with all
other sensors. Set
250 mm or 900 mm
on the display. Con-
firm calibration by
pressing T1 + T2.
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1 T
2 T + 1 T
1 T
2
T
2 T + 1 T
2 T
1 T
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1 T
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1 T
2 T + 1
T
1 T
2 T
2 T + 1 T
2 T
1 T
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1 T
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1 T
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1 T
delay time in seconds
at approach of an
object between de-
tection of the object
and output of the dis-
tance value (acts like
a switch-on delay)
»00«: 0 s (no delay)
to
»20«: 20 s response
delay
response delay
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1
T
Note:
Changes to the settings
in the add-on menu can
hamper the sensor function.
A6, A7, A8, A10, A11, A12
affect the extent of the re-
sponse delay of the sensor.
hysteresis
switching output D2
smallest value:
»001«
largest value:
difference between
limiting scanning
range and switching
point –1
Hysteresis affects
both switching points
in window operation.
2 T + 1 T
1 T
2 T
2 T + 1 T
2 T
1 T
hysteresis
switching output D1
smallest value:
»001«
largest value:
difference between
limiting scanning
range and switching
point –1
Hysteresis affects
both switching points
in window operation.
2T + 1T
1T
2T
2T + 1T
2T
1T
2 Switching output Q1 Switching output Q2
0
1
D2 lights red D2 lights green
T1 D1 D2 T2 T1 D1 D2 T2
  • Page 1 1
  • Page 2 2