Schneider Electric SpaceLogic™ IP-IO Instruction Sheet

  • Hello! I've reviewed the installation sheet for the Schneider Electric SpaceLogic IP-IO I/O Modules, including models SXWIPIOAA10001, SXWIPIOBA10001, and SXWIPIOCA10001, as well as the MP-C Display and DIN-rail end clip. This document provides detailed instructions for installation, including wiring, safety precautions and technical specifications. I'm ready to answer any questions you might have regarding these devices.
  • What are the supported input voltage ratings for the IP-IO module?
    What is the recommended screw tightening torque for wiring?
    What are the IP address assignment methods supported by the IP-IO module?
Installation Sheet MFR1557001-03 / 02-33031-02-en, May 2022 | 1
SpaceLogic™ IP-IO
I/O Module Models
Part numbers: SXWIPIOAA10001, SXWIPIOBA10001, and SXWIPIOCA10001
Regulatory Compliance and Safety Information
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
Carefully read these instructions and all information relevant for this product before trying to install it. See the list of technical literature.
The technical literature and declarations of conformity can be accessed on the Schneider Electric Exchange website, ecobuilding.schneider-
electric.com. Contact your local Schneider Electric sales office for a hard copy of the documentation or for additional information.
Technical Literature
SpaceLogic Hardware Reference Guide, 04-XX001-XX-en
Dimensions
Installation Orientation Restrictions Installing the Device on a DIN Rail
NOTICE
EQUIPMENTEQUIPMENT DAMAGEDAMAGE
Use the DIN rail end clip when you install the device on a vertical
DIN rail.
FailureFailure toto followfollow thesethese instructionsinstructions cancan resultresult inin equipmentequipment
damage.damage.
MFR1557001-03 / 02-33031-02-en, May 2022 | 2
Installing the Device on a Flat Surface
Connections
DANGER
HAZARDHAZARD OFOF ELECTRICELECTRIC SHOCK,SHOCK, EXPLOSION,EXPLOSION, OROR ARCARC FLASHFLASH
Disconnect all line voltage connected to the IP-IO module and its relay outputs before working on the device.
More than one disconnect switch may be required to de-energize this equipment before servicing.
Connect only devices with safe extra low voltage equipment (SELV/PELV) inputs/outputs to the IP-IO module universal inputs/outputs.
FailureFailure toto followfollow thesethese instructionsinstructions willwill resultresult inin deathdeath oror seriousserious injury.injury.
NOTICE
EQUIPMENTEQUIPMENT DAMAGEDAMAGE
Before powering up the IP-IO module, ensure that the input power polarity is correct, the voltage level meets the specifications of the
module, and the terminal blocks are plugged into the correct connector headers on the module.
FailureFailure toto followfollow thesethese instructionsinstructions cancan resultresult inin equipmentequipment damage.damage.
MFR1557001-03 / 02-33031-02-en, May 2022 | 3
Connections, continued
Wiring
Recommended screw tightening torque: 0.56 Nm (5 lbf.in)
For information on wiring, see the SpaceLogic Hardware Reference Guide.
Part Numbers
ProductProduct PartPart numbernumber
IP-IO-DI10 SXWIPIOAA10001
IP-IO-UIO10 SXWIPIOBA10001
IP-IO-UIO5DOFA4 SXWIPIOCA10001
MP-C DISPLAY
(MP-C override display module) SXWMPCDSP10001
DIN-rail end clip, 25 pieces SXWDINEND10001
Specifications
AC input
NominalNominal voltagevoltage
24 VAC 50/60 Hz
PowerPower consumptionconsumption
17 VA
DC input
NominalNominal voltagevoltage
24 to 30 VDC
PowerPower consumptionconsumption
9 W
Port types
USBUSB devicedevice portport
Mini-B
USBUSB hosthost portport
Type-A
EthernetEthernet portport 11 andand 22
10/100BASE-TX RJ45
Operation environment
AmbientAmbient temperature,temperature, operatingoperating
0 to 50 °C (32 to 122 °F) at normal operation
-40 to +60 °C (-40 to +140 °F) for rooftop
applications, horizontal installation only
See section Installation Orientation
Restrictions.
MP-C Display temperature range: -30 to +60
°C (-22 to +140 °F)
HumidityHumidity
Maximum 95 % RH non-condensing
MFR1557001-03 / 02-33031-02-en, May 2022 | 4
www.se.com/buildings
© 2022 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
Mechanical
IngressIngress protectionprotection ratingrating
IP 20
PlasticPlastic flameflame ratingrating
UL94-5VB
IP networking
IPIP addressaddress assignmentassignment methodsmethods
Static, DHCP (default), Auto-IP (address
range 169.254.0.1 to 169.254.255.254,
subnet mask 255.255.0.0)
DI – Digital inputs
InputInput ratingrating
24 VDC , 2.4 mA
ChannelsChannels
IP-IO-DI10: 10; IP-IO-UIO10: 0; IP-IO-
UIO5DOFA4: 0
Ub – Universal I/O
InputInput ratingrating
24 VDC , 2.4 mA
VoltageVoltage outputoutput ratingrating
0 to 10 VDC , 5 kohm (min.)
ChannelsChannels
IP-IO-DI10: 0; IP-IO-UIO10: 10; IP-IO-
UIO5DOFA4: 5
DO – Relay outputs
RelayRelay contactcontact ratingrating
250 VAC / 30 VDC , 2 A
Pilot Duty (C300)
ChannelsChannels
IP-IO-DI10: 0; IP-IO-UIO10: 0; IP-IO-
UIO5DOFA4: 3
DO – High power relay outputs
RelayRelay contactcontact ratingrating
250 VAC / 24 VDC , 12 A
Pilot Duty (B300)
ChannelsChannels
IP-IO-DI10: 0; IP-IO-UIO10: 0; IP-IO-
UIO5DOFA4: 1
Addendum - California Proposition 65 Warning Statement for California Residents
WARNING:WARNING: This product can expose you to chemicals including lead which is known to the State of California
to cause cancer and which is known to the State of California to cause birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov
Specifications, continued
/