English
5SYSAQUA
Rated heat output (*) Prated 35 kW Seasonal space heating energy
efciency hs132 %
Declared capacity for heating for part load at indoor
temperature 20 °C and outdoor temperature Tj
Declared coefcient of performance or primary
energy ratio for part load at indoor temperature 20
°C and outdoor temperature Tj
Tj=-7 °C Pdh 22.43 kW Tj=-7 °C COPd 2.72
Tj=+2 °C Pdh 27.70 kW Tj=+2 °C COPd 3.27
Tj=+7 °C Pdh 23.04 kW Tj=+7 °C COPd 5.22
Tj=+12 °C Pdh 25.95 kW Tj=+12 °C COPd 6.02
Tj= bivalent temperature Pdh 25.70 kW Tj= bivalent temperature COPd 3.00
Tj=-15 °C Pdh 21.53 kW Tj=-15 °C COPd 2.24
Bivalent temperature Tbiv -3.5 °C operation limit temperature TOL -20 °C
Cycling interval capacity for heating Pcych kW Cycling interval efficiency COPcyc
Degradation co-efficient (**) Cdh 0.9 Heating water operating limit temperature WTOL 55 °C
Power consumption in modes other than active
mode Supplementary heater
Off mode POFF kW Rated heat output Psup kW
Thermostat-off mode PTO 0.351 kW Type of energy input
Standby mode PSB 0.110 kW
Crankcase heater mode PCK 0.110 kW
Other items
Capacity control Staged Rated air flow rate, outdoors 16 000
m3/h
Sound power level, indoors/
outdoors LWA -/76 dB Annual energy consumption QHE
21 391
kWh
Model(s): SYSAQUAH 35
Air-to-water heat pump: yes
Water-to-water heat pump: no
Brine-to-water heat pump: no
Low-temperature heat pump: no
Equipped with a supplementary heater: no
Heat pump combination heater: no
Parameters shall be declared for medium-temperature application, except for low-temperature heat
pumps. For low- temperature heat pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Contact details:
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is
equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefcient is Cdh = 0.9.
Systemair AC SAS
Route de Verneuil
27570 Tillières-sur-Avre
FRANCE