Schneider Electric N00-809-04_PMSet U Automatic Circuit Recloser User guide

Type
User guide
Set Series
PMSet™ U
Automatic Circuit Recloser with PowerLogic
ADVC Controller
Installation, Operation and Maintenance Manual
N00-809-04
07/2023
www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Featuring outstanding medium-voltage (MV) and low-voltage (LV) switchboards,
motor control centres and power distribution solutions for high-performance power
applications, Schneider Electric's Set Series is best-in-class solutions based on high
levels of safety and an optimised footprint. Built on a modular architecture and
incorporating smart connected devices for maximum safety, reliability, performance
and energy efficiency, the Set Series is delivered to customers directly from our
Schneider Electric plants or via a global network of licensed partner panel builders,
who are trained and audited to provide quality equipment and support.
Legal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal InformationLegal Information
Set Series
Table of Contents
Safety Information ......................................................................................5
About the Book...........................................................................................6
Introduction................................................................................................7
Scope of the Manual .............................................................................8
Design Overview ......................................................................................10
General Overview of the ACR .............................................................. 11
PowerLogic ADVC ..............................................................................15
Optional HV Accessories .....................................................................15
Installation ...............................................................................................17
Transport, Handling and Workshop Tests..............................................18
Site Installation ...................................................................................24
Communications and Accessories Installation ............................................43
Customer Accessories and Communication Equipment .........................44
Input Output Expander Installation .......................................................46
Installation Testing....................................................................................48
Operator Tests....................................................................................49
Terminal Designation and Phase Rotation.............................................53
Power Flow Direction Setting ...............................................................55
Power Flow Direction Testing...............................................................56
Control Electronics Operation .................................................................... 60
Introduction ........................................................................................61
OCP ........................................................................................................66
Introduction ........................................................................................67
setVUE Panel Interface.......................................................................68
flexVUE Panel Interface......................................................................72
Event Log ................................................................................................81
Power System Measurements ...................................................................86
Accessories Installation.............................................................................89
IOEX Module......................................................................................90
Fast Trip Input Module.........................................................................93
IOEX Electrical Connections ................................................................97
FTIM Electrical Connections ................................................................99
Maintenance .......................................................................................... 107
Overview of ACR Maintainance.......................................................... 108
PowerLogic ADVC Operating Conditions ............................................ 108
Ratings and Specifications ...................................................................... 111
Equipment and Crating Dimensions ................................................... 112
ACR General Specifications .............................................................. 112
PowerLogic ADVC General Specifications .......................................... 114
Appendices .............................................................................................. 119
Replaceable Parts and Tools ...................................................................120
Dimensions............................................................................................125
Calibration of SwitchGear and Controller .................................................. 127
Glossary ...................................................................................................131
N00-809-04 3
Safety Information
Safety Information
Important Information
Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this documentation or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and its installation, and has received safety
training to recognize and avoid the hazards involved.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an
electrical hazard exists which will result in personal injury if the instructions are not
followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
!
DANGER
WARNING indicates a hazardous situation which, if not avoided, could result in death or
serious injury.
WARNING
!
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
CAUTION
!
NOTICE is used to address practices not related to physical injury.
NOTICE
N00-809-04 5
About the Book
About the Book
Document Scope
This document describes the installation and maintenance procedures for the
PMSet™ U-Series Automatic Circuit Recloser (ACR) with PowerLogic ADVC
Controller (ADVC) Range.
Validity Note
This document is valid for PMSet U-Series remotely controlled and monitored
ACR which consists of a PMSet U-Series ACR combined with an PowerLogic
ADVC.
Related Documents
Title of Documentation Reference Number
U-Series ACR U27-12/15
U27-12/27
Advanced Controller Operational Manual N00-812
You can download these technical publications and other technical information
from our website at www.se.com/ww/en/download/.
Trademark Notice
All trademarks are owned by Schneider Electric Industries SAS or its affiliated
companies.
Well-being
Performance
Circular
Performance
Resource
Performance
RoHS Compliant
SVHC Free
SF6 Free
60% Recyclable
End of Life Instructions
Maintenance Free
Optimized Energy Performance
Reduced CO2 Emissions
PEP (Product Enviromental
Profile) Ecopassport Declaration
Schneider Electric’s ecoDesign Way program was reviewed and validated by UL Environment to meet the
requirements of the ANSI / IEC 62430
Sustainable
performance,
by design
Premium
Green TM
6 N00-809-04
Introduction
Introduction
What’s in This Chapter
Scope of the Manual........................................................................................8
N00-809-04 7
Introduction
Scope of the Manual
This manual describes the installation and maintenance of the PMSet U-Series
ACR and the PowerLogic ADVC.
While every care has been taken in the preparation of this manual, no
responsibility is taken for loss or damage incurred by the purchaser or user due to
any error or omission in the document. Inevitably, not all details of equipment are
provided nor are instructions for every variation or contingency during installation,
operation, or maintenance.
For additional information on specific problem or requirements, kindly contact the
manufacturer or your distributor.
Switchgear and Controller Architecture
PowerLogic ADVC Controller block diagram
Switchgear
Control cable
ADVC Controller
Control and
Protection
Enclosure
Power Supply Module
Accessory
mounting
tray(s)
CVT
(optional)
Modem
Trip & Close
Capacitors
LAN-1/2
Communication
Interface
Uninterruptible Power Supply
Batteries
MCB
MCB
MCBs
Filters
Txfr
Txfr
Aux supply 1
Aux supply 2
(optional)
Power Outlet
(optional)
Operator
Interface
Filters
DSP
Microprocessor
Switchgear power
IOEX
USB
USB-1/2/3
CVT
CT
Operating
mechanism
8 N00-809-04
Introduction
Symbols
The following symbols are used throughout this manual (and others). They are
designed to give a quick way of indicating information that is designed for specific
areas of interest.
Symbol Meaning
The set symbol indicates that the adjacent information only relates to the
PowerLogic ADVC SetVUE Operator Interface (O.I.).
The flex symbol indicates that the adjacent information only relates to the
PowerLogic ADVC flexVUE O.I.
Panel messages or Menu Navigation follows these icons in DOT MATRIX FONT.
Software Identification
The software loaded into the PowerLogic ADVC is identified by its version number
which has the form:
AXX-XX.XX.
This precisely identifies the software loaded into the microprocessor on the
controller.
In order to obtain effective technical support from the manufacturer or your
distributor, it is necessary to record the software version and to quote these when
making your inquiry. Without this information, it is impossible for the customer
service department to identify the software and provide correct support.
The software version is shown on the Operator Control Panel (OCP)
Switchgear Wear/General Details page, in the field App.Ver:
NOTE: Images are for illustrative purposes only.
Switchgear Status can be found on the flexVUE at the following location:
OPERATOR MENU > Switchgear Status > Switchgear Info
For more information on how to use the O.I., refer to Operator Control Panel, page
66.
Revision Record
Level Date Comment
R00 December, 2017 PowerLogic ADVC updates
R01 December, 2019 Rating corrections update
R02 September, 2020 ACR and ADVC updates
R03 November, 2020 ACR variant-U27 Lite updates
N00-809-04 9
Design Overview
Design Overview
What’s in This Chapter
General Overview of the ACR ........................................................................ 11
PowerLogic ADVC.........................................................................................15
Optional HV Accessories................................................................................15
10 N00-809-04
Design Overview
General Overview of the ACR
The remotely controlled and monitored PMSet U-Series ACR is combined with an
PowerLogic ADVC.
The PMSet U-Series ACR:
Consists of vacuum interrupters encapsulated with Hydrophobic
cyclo-aliphatic epoxy resin casting.
Is operated by a single magnetic actuator ganged with the three Vacuum
Interrupters for both tripping and closing.
The actuator and the associated mechanism is enclosed in a 316-grade
stainless steel tank and lid in the PMSet U-Series ACR. It is enclosed in a
mild steel tank coated with zinc rich epoxy and special powder paint system
for outdoor use in U27 Lite.
The hydrophobic cyclo-aliphatic epoxy resin casting assemblies are bolted to
the lid.
An external pointer, clearly visible on the tank, indicates the ON/OFF
condition of the ACR.
The upper terminals of the ACR are identified as the X-Side terminals
(X, XX, XXX for the three phases) and the lower terminals of the ACR are
identified as the I-Side terminals (I, II, III for the three phases). Terminal
Markers are clearly visible on the side of the tank.
The information such as serial number, switchgear type, operations and
contact wear, are stored in an electronic module mounted on the bottom of
the ACR which is independent of the PowerLogic ADVC.
Operation of the ACR is via low voltage magnetic actuator activated by
closing and opening capacitors housed in the PowerLogic ADVC which in
turn are charged by the onboard power supply. Power supply system consists
of 2 x 12 V 12 Ah sealed lead acid batteries connected in series to provide a
system voltage of 24 Vdc.
Local electrical close operation of the switchgear is achieved by dedicated
keypad buttons on the PowerLogic ADVC. Red is for close and green is for
open. Each button has an inbuilt same colour Light Emitting Diodes (LED) for
indication.
NOTE: This ACR is not suitable for use as a point of isolation. If work on the
electrical system is to be carried out, deenergize the recloser and confirm
electrical and mechanical indications.
N00-809-04 11
Design Overview
PMSet U-Series ACR Construction
X-Terminal
I-Terminal
Vacuum
Interupter
Housing
Encapsultaed
CT and CVT
Operating mechanism
Located in Tank
Flanges for pole mounting
and surge arrestor brackets.
12 N00-809-04
Design Overview
The ACR Features
Line Voltage Sensing
The ACR senses the line voltage on the I-Side terminals. This enables voltage
measurement, power measurement, directional blocking and different protection
protocols. In order to measure the voltage on the Xside as well, refer to Optional
HV Accessories, page 15.
Current Measurement
Each phase has a Current Transformer (CT) over moulded on the Iside. This
enables current measurement on these phases. For more information, refer to CT
in ACR General Specifications, page 112.
Line Connection or Terminals
High voltage terminals are Ø20 mm tin plated copper stems with M10 x 1.5
threaded holes at the end. This means that connections can be either parallel
groove connectors suitable for the cable type or Standard lugs with 10 mm
diameter holes.
Manual Trip Operation
The main tank is equipped with a manual trip lever that can be operated from
ground level by a hook stick which performs open and lockout simultaneously. The
mechanical lever electronically inhibits both local and remote closing. The position
of the lever is indicated to the PowerLogic ADVC by an associated micro-switch.
The manual trip ring remains in the down position until physically returned to the
normal position by the operator.
N00-809-04 13
Design Overview
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Do not operate the manual trip lever when the ACR is in OFF position.
Failure to follow these instructions can result in injury or equipment
damage.
Lockout-Close Inhibit
Make sure the ACR is in open position. Activate the isolating switches located on
the PowerLogic ADVC for lockout-only feature, which when activated inhibits the
close command.
TRIP CIRCUIT
Disables all trip operations. When the switch is in the Disable position, the trip coil
in the recloser is electrically disconnected from the control electronics. Thus, the
switch provides a physical isolation point for the control circuitry. The recloser
cannot be opened, and an audible alarm in the panel sounds and the DISABLED
LED in the TRIP key flashes. The TRIP key operates normally when the switch is
in the Enable position. This switch also stops a close operation, so that the
switchgear cannot be closed unless it is able to trip.
CLOSE CIRCUIT
Disables all close operations. When the switch is in the disable position, the close
coil in the recloser is electrically disconnected from the control electronics. Thus
the switch provides a physical isolation point for the control circuitry. The recloser
cannot be closed and an audible alarm in the panel sounds and the DISABLED
LED in the CLOSE key flashes. The CLOSE key operates normally when the
switch is in the Enable position.
14 N00-809-04
Design Overview
PowerLogic ADVC
The PowerLogic ADVC is a stainless steel 316 enclosure. The U27 Lite controller
is a mild steel enclosure coated with zinc rich epoxy and special powder paint
system for outdoor use. The PMSet U-Series ACR connects to the PowerLogic
ADVC by a control cable that plugs into the bottom of the ACR. CTs and voltage
screens embedded in the epoxy resin mouldings send signals to the control
electronics which monitors phase current, earth current, and phase/earth
voltages.
If the control cable is disconnected (at either end) the CTs and voltage screens are
automatically shorted by circuitry on the Switchgear Cable Entry Module (SCEM)
card mounted inside the tank of the circuit breaker.
The PowerLogic ADVC reads and displays the information which is stored in the
ACR and provides protection and communication properties for the ACR.
CAUTION
HAZARD OF INCORRECT USE AND OPERATION
For protection, communication, and measurement features, refer to PowerLogic
ADVC Operational Manual (N00-812).
Failure to follow these instructions can result in injury or equipment
damage.
The PowerLogic ADVC is powered by an auxiliary voltage supply of 110, 220, or
240 Vac.
The customer compartment provides ample room for equipment. Standard
communications cables can be used for connection to the communications ports
on the PowerLogic ADVC and power is readily accessible from the programmable
power terminal block. For more information, refer to Communications and
Accessories Installation, page 43.
Optional HV Accessories
Surge Arresters
Surge arresters can be directly fitted to the ACR, using surge arrester mounting
bracket (depending on mounting method) and must be fitted during installation.
External Capacitive Voltage Transducer
Some automation systems may require voltage sensing on both sides of the ACR
when it is open. To satisfy this requirement, optional Capacitive Voltage
Transducer (CVT) may be installed to provide voltage sensing on the X-Side
terminals of the ACR.
Voltage Transformer
An external transformer is mounted on the power pole as shown in the below
figure which also shows suggested HV connections. The secondary of the
external transformer connects into the SCEM on the underside of the circuit
breaker. To connect the transformer secondary remove the SCEM compartment
cover plate, pass the cable which is pre-fitted with a cable gland through the hole,
attach the gland, connect the auxiliary supply to the screw terminal block on the
SCEM and replace the compartment cover.
N00-809-04 15
Design Overview
16 N00-809-04
Installation
Installation
What’s in This Chapter
Transport, Handling and Workshop Tests ........................................................18
Site Installation..............................................................................................24
N00-809-04 17
Installation
Transport, Handling and Workshop Tests
General
Each crate includes the following:
• ACR
Pole mounting bracket with clamps if ordered. If a substation mounting
bracket was ordered, it must be attached to the outside of the crate.
Six connectors if ordered.
The appropriate mounting kit.
PowerLogic ADVC cubicle (which normally contains two batteries unless
arrangements have been made to ship batteries separately).
Control cable.
On receipt, the contents must be checked for shipping damage and the
manufacturer informed immediately if any is found.
NOTICE
HAZARD OF WATER INGRESS
Make sure that the PowerLogic ADVC is stored indoors until installation on site.
If storage outdoors is unavoidable, make sure that the PowerLogic ADVC is
kept in an upright position.
Failure to follow these instructions can result in equipment damage.
Unpacking Procedure
The basic list of tools which are required for unpacking are as follows:
Wrecking bar to remove nails.
Four D-shackles, four slings and crane with a working load of 200 kg to lift the
ACR.
Screwdriver or battery drill with 8 mm socket.
16 mm Spanner or Socket.
The following is the list of procedures for unpacking:
1. Remove top of crate and lift out the control cable. Store carefully in a clean
dry place.
2. Unscrew and remove the four screws located on the wall of the crate. The
mounting bracket, mounting kit and the two pieces of wood that the screws
are removed that are helps to secure together. Lift the complete mounting
bracket out of the crate.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Two people are required to lift the heavy accessory (> 15 kg), or with a
lifting equipment.
Visually inspect the equipment after opening the crate, and check for
any damages.
Failure to follow these instructions can result in injury or equipment
damage.
18 N00-809-04
Installation
3. Fit D-shackles to the lifting points on the ACR and lift it out of the crate and on
to the solid level ground using the crane.
CAUTION
HAZARD OF EQUIPMENT DAMAGE INSIDE THE CRATE
Handle crowbar/pry bar carefully to help prevent the equipment damage
inside the crate.
Failure to follow these instructions can result in injury or equipment
damage.
4. Tip the crate on to its side.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Two people are required to lift the PowerLogic ADVC which weighs ~ 40
kg (88lb) and the heavy accessory (> 15 kg), or with a lifting equipment.
PowerLogic ADVC lifting hooks must be used for lifting with a lifting
equipment. See the below image Lifting hooks of PowerLogic ADVC.
The timber pallet must be transported by hand pallet truck, crane, or
forklift truck.
Failure to follow these instructions can result in injury or equipment
damage.
Lifting hooks
Lifting hooks of PowerLogic ADVC
5. Remove the bolts which attach the PowerLogic ADVC and slide the unit from
the crate.
Recloser Lifting Procedure
The wooden crate must be transported by hand pallet truck, crane, or forklift truck.
The lifting procedure must be followed. The slinging recommendation is as shown
in the below figure and perform the following procedures.
1. The slings/chains must be approved and in good condition.
N00-809-04 19
Installation
2. Recloser to be lifted with the help of four lifting lugs.
3. The lifting hook must be placed minimum 650 mm above the top connector of
bushings.
4. Make sure to balance the main tank weight so that the chains/sling does not
touch the sides of the bushings throughout the lift.
5. When moving and lifting, special care must be taken not to damage the
bushings and bushing terminals.
Control Cable Connection
When installing or testing the ACR it is necessary to connect and disconnect the
control cable either from the ACR, the PowerLogic ADVC or both. The control
cable is plugged into the base of the ACR and the other end into the PowerLogic
ADVC at the bottom, right-most side on the Control and Protection Enclosure
(CAPE).
The following is the list of correct technique of the cable connection towards the
controller side:
1. Power down the control cubicle by switching off all Miniature Circuit Breakers
(MCBs). This must be done whenever connecting or disconnecting the control
cable.
2. To connect the control cable, hold the plug by the long sides, check
orientation, gently locate it on the socket and push firmly home. Check
whether it has locked by wriggling the plug.
20 N00-809-04
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134

Schneider Electric N00-809-04_PMSet U Automatic Circuit Recloser User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI