APC 10-30 KVA 208/220 V User manual

Category
Power supply units
Type
User manual

This manual is also suitable for

SingleandParallel
Installation
MGE™Galaxy™3500
10-30kVA208/220V
test
AmericanPowerConversionLegalDisclaimer
TheinformationpresentedinthismanualisnotwarrantedbytheAmericanPowerConversion
Corporationtobeauthoriative,errorfree,orcomplete.Thispublicationisnotmeanttobe
asubstitutefordetailedoperationalandsitespecicdevelopmentplan.Therefore,American
PowerConversionCorporationassumesnoliabilityfordamages,violationsofcodes,improper
installation,systemfailures,oranyotherproblemsthatcouldarisebasedontheuseofthis
Publication.
TheinformationcontainedinthisPublicationisprovidedasisandhasbeenpreparedsolely
forthepurposeofevaluatingdatacenterdesignandconstruction.ThisPublicationhasbeen
compiledingoodfaithbyAmericanPowerConversionCorporation.However,nopresentation
ismadeorwarranty,eitherexpressorimplied,astothecompletenessoraccuracyofthe
informationthisPublicationcontains.
NOEVENTSHALLAMERICANPOWERCONVERSIONCORPORA TIONBELIABLE
FORANYDIRECT,INDIRECT,CONSEQUENTIAL,PUNITIVE,SPECIAL,OR
INCIDENTALDAMAGES(INCLUDING,WITHOUTLIMITATION,DAMAGESFOR
LOSSOFBUSINESS,CONTRACT,REVENUE,DATA,INFORMA TION,ORBUSINESS
INTERRUPTION)RESULTINGFROM,ARISINGOUT,ORINCONNECTIONWITHTHE
USEOF,ORINABILITYTOUSETHISPUBLICA TIONORTHECONTENT,EVENIF
AMERICANPOWERCONVERSIONCORPORATIONHASBEENEXPRESSLYADVISED
OFTHEPOSSIBILITYOFSUCHDAMAGES.AMERICANPOWERCONVERSION
CORPORATIONRESERVESTHERIGHTTOMAKECHANGESORUPDATESWITH
RESPECTTOORINTHECONTENTOFTHEPUBLICA TIONORTHEFORMAT
THEREOFA TANYTIMEWITHOUTNOTICE.
Copyright,intellectual,andallotherproprietaryrightsinthecontent(includingbutnotlimited
tosoftware,audio,video,text,andphotographs)restswithAmericanPowerConversion
Corporationoritslicensors.Allrightsinthecontentnotexpresslygrantedhereinarereserved.
Norightsofanykindarelicensedorassignedorshallotherwisepasstopersonsaccessing
thisinformation.
ThisPublicationshallnotbeforresaleinwholeorinpart.
TableofContents
IMPORTANTSAFETYINSTRUCTIONSSAVETHESE
INSTRUCTIONS...............................................................................................................1
Specications...................................................................................................................2
ACInputSpecications..............................................................................................2
ACBypassInputSpecications..............................................................................2
ACOutputSpecications..........................................................................................3
BatterySpecications................................................................................................3
RecommendedCableSizes......................................................................................4
ConnectionTerminals................................................................................................4
TorqueSpecications................................................................................................4
FusesandBreakers....................................................................................................5
SingleUtility/MainsSystem.......................................................................................5
DualUtility/MainsSystem..........................................................................................5
ParallelSystem..........................................................................................................6
FuseandBreakerSizesinSingleSystems................................................................6
FuseandBreakerSizesinParallelSystems..............................................................6
MinimumBreakerSettings........................................................................................7
MechanicalInstallation...............................................................................................8
Clearance.......................................................................................................................8
LeveltheCabinet.........................................................................................................8
RemovetheFrontPanel............................................................................................9
FloorAnchoring..........................................................................................................9
HolePositionsforaStand-aloneUPSEnclosurewithL-shapedAnchoring
Brackets....................................................................................................................10
HolePositionsforUptoFourUPSUnitsinParallelwithU-shapedAnchoring
Brackets...................................................................................................................10
ConnectFloorAnchoringBracketstotheUPSandXRBatteryEnclosurefor
Stability......................................................................................................................11
RemovetheBatteryModules.....................................................................................12
InstalltheBayingKit(Optional)forInterconnectionofEnclosuresandSeismic
Anchoring..................................................................................................................13
InstallXRBatteryEnclosures(Option)..............................................................16
RemovetheCableLandingCoverandBottomPlates......................................16
ConnectBatteryPowerinInstallationswithBusbars.......................................17
IsolatorInstallationPrinciple.....................................................................................17
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
i
InstallBusbarsin523mm(20.59in)UPSSystemwiththeUPSPlacedtotheLeft
(seenfromthefront)..................................................................................................18
InstallBusbarsin523mm(20.59in)UPSSystemwiththeUPSPlacedtothe
Right(seenfromthefront)........................................................................................19
InstallBusbarsin352mm(13.85in)UPSSystemwiththeUPSPlacedtothe
Right(seenfromthefront)........................................................................................20
InstallBusbarsin352mm(13.85in)UPSSystemwiththeUPSPlacedtotheLeft
(seenfromthefront)..................................................................................................21
ConnectBatteryPowerinInstallationswithCables..........................................22
ConnectPowerCablesBetweentheUPSandtheXRBatteryEnclosure..................22
ConnectPowerCablesbetweenTwoXRBatteryEnclosures....................................23
ConnectthePowerCablestotheUPS...............................................................25
SingleSystem10-30kVA208V................................................................................25
SingleSystem10-30kVA480V................................................................................26
PrepareforCables.......................................................................................................27
BottomCableEntry...................................................................................................27
ConnecttheACInputandACOutputCables......................................................28
SingleMains..............................................................................................................28
DualMains.................................................................................................................28
ConnecttheDCBatteryCables(ifapplicable)...........................................................29
ConnecttheCommunicationCables..................................................................30
PrepareforCommunicationCables........................................................................30
OverviewofPinConnections...................................................................................31
J106...........................................................................................................................31
EPOinSingleSystems...............................................................................................32
EPOinParallelSystems............................................................................................33
ConnectCommunicationCablesbetweenUPSandXRBattery
Enclosure.......................................................................................................................34
ConnectAPCCommunicationOptions.................................................................35
ConnectCommunicationCablesinParallelSystem..........................................36
OverviewofthePBusCables....................................................................................36
PrepareforCables.....................................................................................................37
UPSUnitsApartwithoutConduitsandInterconnection..................................38
UPSUnitsBayedTogetherwithoutConduits......................................................39
UPSUnitsApartorBayedTogetherwithConduits...........................................40
InstallSeismicOption..................................................................................................42
InstalltheSeismicBatteryLock..............................................................................42
ii
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
InstalltheSeismicStabilizingBrackets................................................................42
FinalMechanicalInstallation...................................................................................44
ConnectBatterySecuringBracketsforStability................................................44
ReinstalltheTopCoverandtheFrontPanel.......................................................45
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
iii
iv
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
IMPORTANTSAFETYINSTRUCTIONS
SAVETHESEINSTRUCTIONS
WARNING:ALLsafetyinstructionsintheSafetySheet(990-2940)mustberead,
understood,andfollowedwheninstallingtheUPSsystem.Failuretodosocouldresult
inequipmentdamage,seriousinjury,ordeath.
WARNING:AftertheUPShasbeenelectricallywired,donotstartitup.Start-upis
commissionedtoauthorizedpersonnelfromSchneiderElectric.
WARNING:WhentheUPSinputisconnectedthroughexternalisolatorsthat,when
opened,isolatetheneutral,orisconnectedtoanITpowerdistributionsystem,alabel
mustbettedattheUPSinputterminalsbytheUPSsupplier,andonallprimary
powerisolatorsinstalledremotefromtheUPSareaandonexternalaccesspoints
betweensuchisolatorsandtheUPSbytheuser,displayingthefollowingtext(or
equivalent):"Riskofvoltagebackfeed.Beforeworkingonthiscircuit,isolatetheUPS
andcheckforhazardousvoltagebetweenallterminalsincludingtheprotectiveearth."
Caution:Allelectricalpowerandpowercontrolwiringmustbeinstalledbyaqualied
electricianandmustcomplywithlocalandnationalregulationsformaximumpowerrating.
Caution:Waituntilthesystemisreadybepoweredupbeforeinstallingbatteries.Failure
todosocanresultinadeepdischargeofthebatteriesandcausepermanentdamage(the
timefromthebatteryinstallationtimetilltheUPSispoweredupshouldnotexceed72
hoursor3days.
Note:ThesystemisdesignedforconnectiontoanITpowerdistributionsystem.
Note:Theparallelcablesmustberunbytheelectricianbutnotattached.Theeldservice
engineerfromSchneiderElectricwillinstalltheparallelcommunicationboxandattachall
cablestotheUPSunits.
Note:UptofourUPSunitscanruninparallel.
Note:EnsurethattheallUPSunitsareintheirnallocationpriortotheinstallation.
Note:Batteryandutility/mainspowermustnotbeconnecteduntilallotherwiringhas
beencompleted.
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
1
Specications
WARNING:TheUPSmustbesuppliedfroma208/120Vor220/127V4W+GND
60HZsource.
ACInputSpecications
10kV A15kV A20kV A30kV A
208V220V208V220V208V220V208V220V
Connectiontype4-wire(3PH+N+G)
Inputfrequency
(Hz)
40-70
Ithd<5%atfullload
Nominputcurrent
(A)
24.323.036.634.648.645.873.269.0
Maxinputcurrent
(A)
26.725.240.238.053.050.180.175.8
Inputcurrent
limitation(A)
32.832.849.549.565.265.298.898.8
Inputpowerfactor
correction
>0.98atload>50%
MaximumShort
CircuitWithstand
(kA)
30
ACBypassInputSpecications
10kV A15kV A20kV A30kV A
208V220V208V220V208V220V208V220V
Connectiontype4-wire(3PH+N+G)
Inputfrequency
(Hz)
50+/-10or60+/-10
Nominputcurrent
(A)
27.826.241.639.4
55.5
52.583.378.7
2
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
ACOutputSpecications
10kV A15kV A20kV A30kV A
208V220V208V220V208V220V208V220V
Connectiontype4-wire(3PH+N+G)
Overloadcapacity150%for1minute(normaloperation)
125%for10minutes(normaloperation)
150%for1minute(batteryoperation)
125%for10minutes(batteryoperation)
110%continuous(bypassoperation)
800%for500ms(bypassoperation)
V oltagetolerance160-240Vfor208Vsystems
160-253Vfor220Vsystems
Nomoutput
current(A)
27.826.241.639.4
55.5
52.583.378.7
Outputfrequency
(synctomains)
50Hz±0.1Hz,±3Hz,±10Hz
60Hz±0.1Hz,±3Hz,±10Hz
Slewrate(Hz/Sec)
0.25-1
TotalHarmonic
Distortion(THD)
<1.5%linear
<3.5%non-linear
Loadpowerfactor0.5leadingto0.5lagging
Dynamicload
response
±5%
Outputvoltage
regulation
±1%
BatterySpecications
Type
VRLA
Nominalvoltage(VDC)+/-192
Floatvoltage(VDC)+/-219
Endofdischargevoltage(VDC)+/-154
Batterycurrent(atfullload)66.5Aat+/-192V
Max.current(atendofdischarge)
83.2Aat+154V
Max.chargingpower10kV A:1600W
15kV A:2400W
20kV A:3200W
30kV A:3200W
Typicalre-chargetime5hours
Endvoltage1.6-1.75V/cell(automatic,dependingonload)
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
3
RecommendedCableSizes
WARNING:At100%switchmodeload,theneutralmustberatedfor200%phase
current.
Caution:Allwiringmustcomplywithallapplicablenationaland/orelectricalcode.
Note:Therecommendedcablesizesarebasedonanenvironmentwithanambient
temperatureof30°C(86°F).Usestrandedcoppercables.
10kV A15kV A20kV A30kV A
Utility/mainsinput
8AWG6AWG4AWG1AWG
Staticbypassinput
8AWG6AWG4AWG1AWG
DCinput
1AWG1AWG1AWG1AWG
Output8AWG6AWG4AWG1AWG
ConnectionTerminals
Cablesize(A WG)CablelugtypeCrimpingtoolDieTerminalbolt
diameter
12YA12CL2TC38MD7-34RW12CVT
6mm(0.2in)
8YA8CL2TC38MD7-34RW8CVT
6mm(0.2in)
6YA6CL2TC38MD7-34RW6CVT
6mm(0.2in)
4YA4CL2TC38MD7-34RW4CVT
6mm(0.2in)
1YA1CL2TC38MD7-34RW1CVT
6mm(0.2in)
TorqueSpecications
Thepowerwiringshouldbetorquedto7Nm(45lbf-in).
4
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
FusesandBreakers
SingleUtility/MainsSystem
Q1:Utility/mainsinput
Q2:UPSoutput
Q3:Manualbypass
MBS:Mechanicalbypassswitch
DualUtility/MainsSystem
Q1:Utility/mainsinput
Q2:UPSoutput
Q3:Manualbypass
Q5:Staticbypassinput
MBS:Mechanicalbypassswitch
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
5
ParallelSystem
Q1:Utility/mainsinput
Q2:UPSoutput
Q3:Manualbypass
Q4:Systemoutput
Q5:Staticbypassinput
FuseandBreakerSizesinSingleSystems
10kV A15kV A20kV A30kV A
UtilityinputQ1
35A60A80A110A
Staticbypassinput
Q5
35A60A80A110A
UPSoutputQ235A60A80A110A
ManualbypassQ3
35A60A80A110A
FuseandBreakerSizesinParallelSystems
Q3andQ4inParallelCapacitySystems
Unitsinparallel10kV A15kV A20kV A30kV A
270A110A150A225A
3110A175A225A350A
4150A225A300A450A
Q3andQ4inRedundantParallelSystems(n+1)
Unitsinparallel10kV A15kV A20kV A30kV A
235A60A80A110A
370A110A150A225A
4110A175A225A350A
6
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
MinimumBreakerSettings
800%overload
bypass
operation
150%overload
normal/battery
operation
125%overload
normal/battery
operation
Continuously
Duration500ms60s10min
Mainsinput
-
1
--
34A
Staticbypass
input
223A
--
31A
10kV A
UPSoutput223A42A35A31A
Mainsinput
-
1
--
51A
Staticbypass
input
333A
--
46A
15kV A
UPSoutput333A63A52A46A
Mainsinput
-
1
--
68A
Staticbypass
input
444A
--
62A
20kV A
UPSoutput444A84A70A62A
Mainsinput
-
1
--
99A
Staticbypass
input
667A
--
92A
30kV A
UPSoutput667A125A105A92A
1
Forsinglemainssystems,usethehighervalueofmainsandstaticbypass
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
7
MechanicalInstallation
Clearance
Note:Clearancedimensionsarepublishedforairowandserviceaccessonly.Consultwith
thelocalsafetycodesandstandardsforadditionalrequirementsinyourlocalarea.
LeveltheCabinet
WARNING:Thesystemmustbeinstalledonaleveloor .Thelevelingfeetwillstabilize
thecabinet,butwillnotaccountforabadlyslopedoor.
1.Takethe13/14mmwrenchattachedtothe
pallet.
2.Adjustthefourlevelingfeetandensurethat
thesystemislevel.
Note:Donotmovethecabinetafterthelevelingfeethavebeenlowered.
8
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
RemovetheFrontPanel
1.Useacoinorsimilartoturnthetwoblacklock
devicesoneithersideofthedisplayinthe
directionofeachothertoaverticalposition.
2.Pushthefrontpanelupwardsandpullit
outwardstodisengagethelockingdeviceat
thetopoftheenclosure.
3.Liftthefrontpanelfreeofthetwoslotsatthe
bottomoftheenclosure.
FloorAnchoring
Therearetwoooranchoringoptionsthatcanbeuseddependingontherequirementsintheinstallation
area:
Forstability:ReusetheL-shapedbracketsthatsecuredtheenclosuretothepalletduringshipment
forastand-aloneUPS.
Forseismicanchoring:UseabayingkitthatincludesU-shapedseismicanchoringbrackets.
Note:Allowforenoughworkingspacebehindtheenclosureforelectricalworktobecarried
out(e.g.ifyouwanttoinstallanXRBatteryEnclosureatalaterstage).Minimumrear
clearanceis100mm(3.93in)andmustcomplywithapplicablenationalandlocalcodes.
600mm(23.6in)isrecommended.
Note:Holepositionsareguidelinesonly.
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
9
HolePositionsforaStand-aloneUPSEnclosurewithL-shaped
AnchoringBrackets
Note:RecommendedminimumnumberofscrewsperenclosurefortheL-shapedbracketsis
four;oneineachcorner.Recommendedoorboltsize:M8.
ModelWidth:352mm(13.85in)and523mm(20.59in)
HolePositionsforUptoFourUPSUnitsinParallelwithU-shaped
AnchoringBrackets
Note:Recommendedminimumnumberofoorscrewsforthetwocongurationsbelow
is10.
ModelWidth:352mm(13.85in)
10
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
ModelWidth:523mm(20.59in)
ConnectFloorAnchoringBracketstotheUPSandXRBattery
EnclosureforStability
Note:FlooranchoringboltsarenotprovidedwiththeUPS.Purchasetheboltslocally
(minimumsize:M8).Followthespecicationsgivenbythemanufactureroftheoor
anchoringsystemwhenboltingtheUPSsystemtotheoor.
1.InstalltheL-shapedooranchoringbrackets
(reusethetwotransportbrackets)andsecure
withtheM6screwsandnuts(provided).
2.Drilltwotosixholesintheoorforeach
bracketandattachthesewithbolts.
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
11
RemovetheBatteryModules
Note:Twopeopleareneededtoliftthebatterymodules.
Note:TheXRBatteryEnclosuresshipwithtwobatterymodules.Allbatterymodulesin
theUPSandtheXRBatteryEnclosure(s)mustberemovedbeforeinterconnectingthese
enclosures.
Note:Whenyouremovebatterymodules,startfromthehighestrowandworkyourway
down.
1
2
3
1.Removeallbatterysecuringbrackets(usedtosecurethebatteriesduringtransport)byremoving
theM6Torxscrews.
2.Removetheblindplate.
3.Toreleasethebatteryfromitslockmechanism,gentlypushthebatteryupwardsandthenpullit
outwhilesupportingthebatterywithyourotherhand.
12
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
InstalltheBayingKit(Optional)forInterconnectionofEnclosuresand
SeismicAnchoring
Caution:Bayingkitsarerequiredinseismicareas.
1.Removethesidepanelsfromtheenclosure(s)togetaccesstotheholesinthebottomframe.
UPS UPS
Note:Makesurethattheenclosuresarelevelsothattheycanbeanchoredtoeachother.
2.PositiontwoU-shapedooranchoringbracketsunderoneenclosure;oneoneachside.
2
2
Note:TheU-shapedanchoringbracketsare1-2mmhigherthantheopeningbelowthe
enclosuretoinactivatethecasters.Therefore,theenclosuremustbetiltedwhenplacingthe
U-shapedanchoringbracketsundertheenclosure.
990-1957C-001
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
13
3.OneachsideofthesameenclosureinsertamaximumofnineandaminimumoftwoM8screws
(notprovided)throughholesinthebottomoftheenclosureandthroughholesintheU-shaped
ooranchoringbrackets,andintothepre-drilledoorholes.
3
4.Fastenthescrews.
4
5.MovetheadjacentenclosureonitscastersclosetotheenclosurewiththeU-shapedoor
anchoringbrackets.
Note:Iftheadjacentenclosureisonitslevelingfeet,useaforkliftorpalletjacktomoveit
intopositiontoavoiddamagingthelevelingfeet.
14
MGE™Galaxy™350010-30kV A208/220VSingleandParallelInstallation
990-1957C-001
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52