GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) ITALY
Note
Change all menu parameters by
using the front panel buttons
GETTING STARTED
• Unpack Contents
• Verify model numberand application
• Power Controller
• Program for yourapplication
Program Your Gefran Controller
2
*Parametermaybeleftatdefaultvalueforinputtypes0...37
Input Sensor
Sensor Type Sensor Type
0 TCJ°C 30 PT100°C
1 TCJ°F 31 PT100°F
2 TCK°C 32 JPT100°C
3 TCK°F 33 JPT100°F
4 TCR°C 34 PTC°C
5 TCR°F 35 PTC°F
6 TCS°C 36 NTC°C
7 TCS°F 37 NTC°F
8 TCT°C 44 4...20mA
9 TCT°F 46 0...10V
Connect Your Controller
3
What’s Included
• 96x96 DIN 1300-RRR0-00-0-x
Gefran Controller x2
• Mounting Bracket
• Panel Sealing Gasket
• Screw Terminal Cover x2
• Multi-Language Manual
1
• Pressandhold
F
untilPASappears—ENTER99
• Press
F
once,Proappears—ENTER128
• Press
F
once,PASappears—ENTER99
• Pressandhold
F
untilHrdappears
• Press
F
twice,Ctrappears—ENTER14
• Press
F
twice,
butappears—ENTER1
• Pressandhold
F
until
CFGappears
• Pressandhold
F
until
C.Meappears
—ENTER 0 coolingwithAir
—ENTER 1 coolingwithOil
—ENTER 0 coolingwithWater
• Pressandhold
F
until1 nPappears
• Press
F
twice,tYPappears—ENTERtheInputSensornumberfromthelist
• Press
F
repeatedlyuntilLo.S*appears—ENTERtheminimumInputScalelimit
• Press
F
once,H i.S*appears—ENTERthemaximumInputScalelimit
• Press
F
repeatedlyuntilLo.L*appears—ENTERtheminimumAlarmScalelimit
• Press
F
once,H i.L*appears—ENTERthemaximumAlarmScalelimit
• Pressandhold
F
until
Outappears
• Press
F
threetimes,rl.1appears—ENTER1
• Press
F
twice,rl.3appears—ENTER 2
• Pressandhold
F
untilyoureturntothemainprocessdisplay.ThisisthedisplayafterPAS
andwillbeindicatedbytheProcessVariableifaninputsensorisconnected,orLo,H i,Sbr,
Errifnoinputisconnected.
• Usethe
and
buttonstoadjustthecontrolsetpoint(SV)fromthemaindisplay.
• Press
F
oncefromthemaindisplay,AL.1appearstoadjusttheAlarm1setpoint.
• Press the
buttontoswitchbetween automatic andmanualcontrol modes fromthe
maindisplay.LED1(
L1
)willlightwhileinmanualmode.
POWER
This Quick Start Guide provides basic information on
setting up the Gefran 1300 controller for the application
referenced above. Additional software and hardware
configuration information can be found in the User’s Manual
included with this controller or online at www.gefran.com
If needed, automatic tuning (Self-Tune) can be enabled
with the following steps
• Pressandhold
F
untilCFGappears
• Press
F
once,S.Tuappears—ENTER2
• Press
F
once
• Cyclepowertothecontroller
• LED3(
L3
)willflashduringthetuningprocess
Withthemachineatambienttemperatureand
thecontrolsetpoint(SV)set...
Self-TunewillautomaticallysavenewPID
valuesoncecomplete
Additional wiring
configurations are
available in the User’s
Manual and General
Setup Guide
Quick Start Guide
1300-RRR0-00-0-x Programmable PID Controller
12
13
1
+
2
-
5
7
8
11
10
6
ALARM
COOLING
HEATER
Heat - Cool - Alarm
THERMOCOUPLE