  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 310, P330 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort310,applicationP330
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................12
2.3Mounting...........................................................31
2.4Placingthetemperaturesensors................................35
2.5Electricalconnections.............................................37
2.6InsertingtheECLApplicationKey..............................50
2.7Checklist............................................................56
2.8Navigation,ECLApplicationKeyP330.........................57
3.0Dailyuse.........................................................62
3.1Howtonavigate...................................................62
3.2Understandingthecontrollerdisplay..........................63
3.3Ageneraloverview:Whatdothesymbolsmean?...........66
3.4Monitoringtemperaturesandsystem
components........................................................67
3.5Influenceoverview................................................68
3.6Manualcontrol.....................................................69
3.7Schedule............................................................70
4.0Settingsoverview............................................71
5.0Settings...........................................................73
5.1IntroductiontoSettings..........................................73
5.2Flowtemperature..................................................74
5.3Roomlimit..........................................................77
5.4Returnlimit.........................................................79
5.5Flow/powerlimit.................................................83
5.6Optimization........................................................86
5.7Controlparameters................................................91
5.8Application.........................................................94
5.9Tanktemperature................................................101
5.10Anti-bacteria......................................................107
5.11Alarm..............................................................109
6.0Commoncontrollersettings............................111
6.1Introductionto‘Commoncontrollersettings..............111
6.2Time&Date.......................................................113
6.3Holiday............................................................114
6.4Inputoverview...................................................116
6.5Log.................................................................117
6.6Outputoverride..................................................118
6.7Keyfunctions.....................................................119
6.8System.............................................................121
7.0Miscellaneous................................................128
7.1ECA30/31setupprocedures.................................128
7.2Overridefunction................................................136
7.3Severalcontrollersinthesamesystem......................139
7.4Frequentlyaskedquestions....................................142
7.5Definitions........................................................145
7.6Type(ID6001),overview.......................................148
7.7ParameterIDoverview..........................................149
©Danfoss|2017.08VI.GU.O3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyP330
(ordercodeno.087H3840).
ThefunctionsarerealizedinECLComfort310foradvanced
solutions,e.g.M-bus,ModbusandEthernet(Internet)
communication.
P330applicationscancommunicate(viaModbusconnections)
withtheDECS2.0system(DanfossEnergyControlSystem).
PleaseseeDECS2.0relatedliteratureontheDanfosswebsite:
http://heating.danfoss.com/xxDocxx/1_MNU17429744_SIT54.html.
Searchfor‘DECS2.0’ .
TheapplicationP330complieswithECLComfortcontrollers310as
ofsoftwareversion1.40(visibleatstart-upofthecontrollerandin
‘Commoncontrollersettingsin‘System’).
AdditionaldocumentationforECLComfort310,modulesand
accessoriesisavailableonwww.ecl.doc.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
2|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
VI.GU.O3.02
©Danfoss|2017.08|3
OperatingGuideECLComfort310,applicationP330
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
2.0Installation
2.1Beforeyoustart
The14differentapplicationsP330.1...P330.14areheatingand
DHWapplicationsinvariouscombinations.
Thebasicprinciplesforaheatingcircuit
(examplereferringtoP330.1)
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.
TheflowtemperaturesensorS3isthemostimportantsensor.The
desiredflowtemperatureatS3iscalculatedintheECLcontroller,
basedontheoutdoortemperature(S1)andthedesiredroom
temperature.Thelowertheoutdoortemperature,thehigherthe
desiredflowtemperature.
Bymeansofaweekschedule(upto3'Comfort'periods/day),
theheatingcircuitcanbein'Comfort'or'Saving'mode(two
differenttemperaturevaluesforthedesiredroomtemperature).
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.Inboiler-basedheatingsupplythe
returntemperatureshouldnotbetoolow(sameadjustment
procedureasabove).
Aflow/powerlimitationcanbearrangedbyusinganM-busbased
signalfromaflow/heatmeter.Furthermore,thelimitationcanbe
inrelationtotheoutdoortemperature.
Ifthemeasuredroomtemperature,S13orviatheremotecontrol
unitECA30doesnotequalthedesiredroomtemperature,the
desiredflowtemperaturecanbeadjusted.
Generalinformation:
In’Saving’modetheheatingcanbereducedortotallyswitched
off.The‘Frostprotectionmodemaintainsaselectableflow
temperature,forexample10°C.
Thecirculationpump(P2)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thedesiredflowtemperatureofheatingcircuit1can,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
Exerciseofcirculationpumpandcontrolvalvecanbearranged.
ApplicationP330.1:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexampleheatingcircuit1(P330.1):
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
(Optional)Returntemperaturesensor
S8
(Optional)Externaltemperaturecontrol,notillustrated
S13
(Optional)Roomtemperaturesensor
M1
Motorizedcontrolvalve
P2
Circulationpump
A1
Alarm
VI.GU.O3.02
©Danfoss|2017.08|5
OperatingGuideECLComfort310,applicationP330
ThebasicprinciplesforaDHWcircuit,type1
(examplereferringtoP330.4)
Bymeansofaweekschedule(upto3'Comfort'periods/day),the
DHWcircuitcanbein'Comfort'or'Saving'mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS10).
TheDHWheatingtemperaturesensorS9isthemostimportant
sensor.IfthemeasuredDHWtemperature(S10)getslowerthanthe
desiredDHWtemperature,theDHWheatingpump(P7)isswitched
ON.Themotorizedcontrolvalve(M3)iscontrolledinorderto
maintaintheDHWheatingtemperatureatS9.TheDHWheating
temperatureisdeterminedbythedesiredDHWtemperatureatS10
plusthechargingdifference.WhentheDHWheatingtemperature
isreached,theDHWchargingpumpP5isswitchedON.TheDHW
heatingtemperatureatS9istypically5–10degreeshigherthan
thedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S10):
WhenthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperature,theDHWheatingpump(P7)andthe
DHWchargingpump(P5)areswitchedOFF.Thepost-runtimecan
besetindividually.
DHWtankwith2temperaturesensors(S10,upperandS2,
lower):
IfthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperatureandthetemperature(atS2)getshigher
thanthecut-outtemperature,theDHWheatingpump(P7)and
theDHWchargingpump(P5)areswitchedOFF.Thepost-runtime
canbesetindividually.
TheDHWcirculationcanbethroughtheDHWtank(connectionA)
orthroughtheheat-exchanger(connectionB).Thesolutionwith
connectionAresultsinclosingofthemotorizedcontrolvalveafter
theDHWtankchargingprocedure.Thesolutionwithconnection
BisusedtocompensatefortheheatlossintheDHWcirculation
pipe.Furthermore,afterDHWtankcharging,theDHWheating
temperature(atS9)iscontrolledaccordingtothedesiredDHW
temperature.
Thereturntemperature(S7)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS9canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.Inboiler-basedheatingsupplythereturn
temperatureshouldnotbetoolow(sameadjustmentprocedure
asabove).
Aflow/powerlimitationcanbearrangedbyusinganM-busbased
signalfromaflow/heatmeter.
Generalinformation:
The‘Frostprotectionmodemaintainsaselectabletemperature,
forexample10°C.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P8)hasaweekscheduleforupto3
ONperiodsperday.
ApplicationP330.4:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexampleDHWcircuit,type1(P330.4):
S1
Outdoortemperaturesensor
S2
(Optional)LowerDHWtanktemperaturesensor
S7
(Optional)Returntemperaturesensor
S9
Flowtemperaturesensor
S10
UpperDHWtanktemperaturesensorr
M3
Motorizedcontrolvalve
P5
DHWchargingpump
P7
DHWheatingpump
P8
DHWcirculationpump
A1
Alarm
6|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
ThebasicprinciplesforaDHWcircuit,type2
(examplereferringtoP330.5)
Bymeansofaweekschedule(upto3'Comfort'periods/day),the
DHWcircuitcanbein'Comfort'or'Saving'mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS10).
WhenthemeasuredDHWtemperature(S10)getslowerthanthe
desiredDHWtemperature,theDHWheatingpump(P7)andthe
DHWchargingpump(P5)areswitchedON.
DHWtankwith1temperaturesensor(S10):
WhenthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperature,theDHWheatingpump(P7)andthe
DHWchargingpump(P5)areswitchedOFF.Thepost-runtimecan
besetindividually.
DHWtankwith2temperaturesensors(S10,upperandS2,
lower):
WhenthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperatureandthetemperature(atS2)getshigher
thanthecut-outtemperature,theDHWheatingpump(P7)and
theDHWchargingpump(P5)areswitchedOFF.Thepost-runtime
canbesetindividually.
TheDHWcirculationcanbethroughtheDHWtank(connectionA)
orthroughtheheat-exchanger(connectionB).Thesolutionwith
connectionAresultsinclosingofthemotorizedcontrolvalveafter
theDHWtankchargingprocedure.Thesolutionwithconnection
BisusedtocompensatefortheheatlossintheDHWcirculation
pipe.AfterDHWtankcharging,theDHWchargingpumpP5stops.
TheheatingpumpP7continuesbeingswitchedON.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P8)hasaweekscheduleforupto3
ONperiodsperday.
Generalinformation:
The‘Frostprotectionmodemaintainsaselectabletemperature,
forexample10°C.
ApplicationP330.5:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexampleDHWcircuit,type2(P330.5):
S1
Outdoortemperaturesensor
S2
(Optional)LowerDHWtanktemperaturesensor
S10
UpperDHWtanktemperaturesensor
P5
DHWchargingpump
P7
DHWheatingpump
P8
DHWcirculationpump
A1
Alarm
VI.GU.O3.02
©Danfoss|2017.08|7
OperatingGuideECLComfort310,applicationP330
Thebasicprinciplesforthemastercircuit
(examplereferringtoP330.10)
ThedesiredflowtemperatureatS3isadjustedaccordingtothe
demandfromthesub-circuits(heatingandDHWcircuits).Theflow
temperaturesensorS3isthemostimportantsensor.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thecirculationpump(P1)isONatheatdemandoratfrost
protection.
Generalinformation:
Thedesiredflowtemperatureofthemastercircuitcan,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ApplicationP330.10:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexamplemastercircuit(P330.10):
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
(Optional)Returntemperaturesensor
S8
(Optional)Externaltemperaturecontrol,notillustrated
M1
Motorizedcontrolvalve
P1
Circulationpump
A1
Alarm
8|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
Thebasicprinciplesforthemastercircuitwithbuffer
(examplereferringtoP330.14)
Thehighestdemandfromthesub-circuits(heatingandDHW
circuits)plusadifference('Demandoffset')determinethedesired
buffertanktemperatureatS11.
Whenthemeasuredbuffertanktemperature(S11)getslowerthan
thedesiredbuffertanktemperature,thechargingpump(P1)is
switchedON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain
thebuffertankheatingtemperatureatS3.Themotorizedcontrol
valveisopenedgraduallywhentheflowtemperatureislowerthan
thedesiredflowtemperatureandviceversa.
TheflowtemperaturesensorS3isthemostimportantsensor.
ThedesiredtemperatureatS3isdeterminedbythedesiredbuffer
tanktemperatureatS11plusachargingtemperaturedifference.
ThebuffertankheatingtemperatureatS3istypically5–10degrees
higherthanthedesiredbuffertanktemperature.
Buffertankwith1temperaturesensor(S11):
Whenthemeasuredbuffertanktemperature(S11)getshigher
thanthedesiredbuffertanktemperature,thechargingpump(P1)
isswitchedOFF.Thepost-runtimecanbeset.
Buffertankwith2temperaturesensors(S11,upperandS12,
lower):
Whenthemeasuredupperbuffertanktemperature(S11)gets
higherthanthedesiredbuffertanktemperatureandthemeasured
lowerbuffertanktemperature(S12)getshigherthanthecut-out
temperature,thechargingpump(P1)isswitchedOFF.Thepost-run
timecanbeset.
IfS12isnotconnected,S11willbeusedforONandOFFcontrolof
thechargingpump.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Whenthemeasuredbuffertemperature(S11)getshigherthan
thedesiredbuffertemperature,thedesiredtemperatureatS3is
loweredtotypically10°C.Hereafterthechargingpump(P1)is
switchedOFF.Thepost-runtimecanbeset.
ApplicationP330.14:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexamplemastercircuitwithbuffer(P330.14):
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
(Optional)Returntemperaturesensor
S8
(Optional)Externaltemperaturecontrol,notillustrated
S11
Upperbuffertanktemperaturesensor
S12
(Optional)Lowerbuffertanktemperaturesensor
M1
Motorizedcontrolvalve
P1
Buffertankchargingpump
A1
Alarm
VI.GU.O3.02
©Danfoss|2017.08|9
OperatingGuideECLComfort310,applicationP330
ApplicationP330.14:
InordertoavoidadischargingoftheDHWcircuit(ahigher
DHWtemperaturegoestoalowerbuffertanktemperature)two
parameterscanbeset:
*
Theparameter("Tankstartdiff.",IDno13192)determinesan
acceptabletemperaturedifferencebetweenS10andS11in
ordertostarttheDHWcharging.
*
Theparameter("Tankstopdiff.",IDno13196)determinesan
acceptabletemperaturedropofthedifferencebetweenS10
andS11inordertostoptheDHWcharging.
Generalinformation:
Thedesiredflowtemperatureofthemastercircuitcan,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
10|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
ApplicationP330.1P330.5:
Heatingcircuits2,3,4andDHWcircuitscanbeconnectedafter
heatingcircuit1.Circuit1actsasmasterandcanreactonthe
sub-circuitsdemand.Ifso,thedesiredflowtemperatureatS3can
beinfluencedbythedesiredflowtemperatureatS4,S9,S10and
DHWchargingtemperaturerespectively.
Thedesiredflowtemperatureofheatingcircuit1can,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ApplicationP330.6P330.15:
HeatingcircuitsandDHWcircuitsaretypicallyconnected
afterthemastercontrolledcircuit(M).Whenso,thedesired
flowtemperatureatS3canbeinfluencedbythedesiredflow
temperatureatS4,S9,S10andDHWchargingtemperatures.
Thedesiredflowtemperatureofthemastercircuitcan,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ApplicationP330ingeneral:
UptotwoRemoteControlUnits,theECA30(oneforeachheating
circuit)canbeconnectedtooneECLcontrollerinordertomeasure
theroomtemperatureandcontroltheECLcontrollerremotely.
WhentheDHWcircuitisactiveduringthechargingprocedure,
selectedheatingcircuitscanbeclosedinordertogivehigher
prioritytotheDHWcharging.
Oneormoreconnectedfloworenergymeters(basedonM-bus
signal)canlimitthefloworenergytoasetmaximum(DHW
circuits)andinrelationtotheoutdoortemperature(heatingand
mastercircuits).
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
InputS8canbeusedtocontrolthedesiredflowtemperatureof
heatingcircuit1orthemastercircuit.Theappliedvoltagesignalin
therange0-10voltisconvertedintheECLcontrollertothedesired
flowtemperature.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdatacanfurthermorebetransferredtotheModbus
communication.
Alarmrelay(R6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature.
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
VI.GU.O3.02
©Danfoss|2017.08|11
OperatingGuideECLComfort310,applicationP330
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
P330.1
Twoheatingcircuits
12|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
SpecialsettingsfortypeP330.1:
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit(circuit2)
Heatingcircuit2canbeasub-circuittoheatingcircuit1.
Settingsforsub-circuitinordertosenddemandtocircuit1:
MENU\Settings\Application:‘SenddesiredT’
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit:
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit
VI.GU.O3.02
©Danfoss|2017.08|13
OperatingGuideECLComfort310,applicationP330
P330.2
Threeheatingcircuits
SpecialsettingsfortypeP330.2:
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit(circuit2and3)
Heatingcircuit2and3canbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
14|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
P330.3
Fourheatingcircuits.TheMCVincircuit4iscontrolledby010V.
SpecialsettingsfortypeP330.3
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit(circuit2,3and4)
Heatingcircuit2,3and4canbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
VI.GU.O3.02
©Danfoss|2017.08|15
OperatingGuideECLComfort310,applicationP330
P330.4
TwoheatingcircuitsandoneDHWchargingcircuitwithcontrolledheatingtemperature.
SpecialsettingsfortypeP330.4:
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit2andDHWcircuit
Heatingcircuit2andtheDHWcircuitcanbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
DHWcirculationpipe
TheDHWcirculationpipecanbeconnectedtotheDHWtankat'A'forinternal
circulationortotheheatexchangerat'B'forexternalcirculation.
(InternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'1x054OFF
(ExternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'1x054ON
16|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
P330.5
ThreeheatingcircuitsandoneDHWchargingcircuit.
SpecialsettingsfortypeP330.5
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit2and3andDHWcircuit
Heatingcircuit2and3andtheDHWcircuitcanbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
DHWcirculationpipe
TheDHWcirculationpipecanbeconnectedtotheDHWtankat'A'forinternal
circulationortotheheatexchangerat'B'forexternalcirculation.
(InternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'
1x054
OFF
(ExternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'
1x054
ON
VI.GU.O3.02
©Danfoss|2017.08|17
OperatingGuideECLComfort310,applicationP330
P330.6
Onemastercircuitandoneheatingcircuitassub-circuit.
SpecialsettingsfortypeP330.6:
Navigation:IDno.:
Recommendedsetting:
Themastercircuitreactsondemandinthesub-circuit.
Sub-circuit
Settingsforsub-circuitinordertosenddemandtomastercircuit:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Mastercircuit
Settingsformastercircuitinordertoreactondemandinsub-circuit:
MENU\Settings(M)\Application:'Demandoffset'
1x017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit
18|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
P330.7
Onemastercircuitandtwoheatingcircuitsassub-circuits.
SpecialsettingsfortypeP330.7
Navigation:IDno.:
Recommendedsetting:
Themastercircuitreactsondemandinthesub-circuit(s).
Sub-circuit(s)
Settingsforsub-circuit(s)inordertosenddemandtomastercircuit:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Mastercircuit
Settingsformastercircuitinordertoreactondemandinsub-circuit(s):
MENU\Settings(M)\Application:'Demandoffset'
1x017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
VI.GU.O3.02
©Danfoss|2017.08|19
OperatingGuideECLComfort310,applicationP330
P330.8
Onemastercircuitandthreeheatingcircuitsassub-circuits.TheMCVincircuit3iscontrolledby010V.
SpecialsettingsfortypeP330.8
Navigation:IDno.:
Recommendedsetting:
Themastercircuitreactsondemandinthesub-circuit(s).
Sub-circuit(s)
Settingsforsub-circuit(s)inordertosenddemandtomastercircuit:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Mastercircuit
Settingsformastercircuitinordertoreactondemandinsub-circuit(s):
MENU\Settings(M)\Application:'Demandoffset'
1x017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
20|©Danfoss|2017.08
VI.GU.O3.02