ThebasicprinciplesforaDHWcircuit,type1
(examplereferringtoP330.4)
Bymeansofaweekschedule(upto3'Comfort'periods/day),the
DHWcircuitcanbein'Comfort'or'Saving'mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS10).
TheDHWheatingtemperaturesensorS9isthemostimportant
sensor.IfthemeasuredDHWtemperature(S10)getslowerthanthe
desiredDHWtemperature,theDHWheatingpump(P7)isswitched
ON.Themotorizedcontrolvalve(M3)iscontrolledinorderto
maintaintheDHWheatingtemperatureatS9.TheDHWheating
temperatureisdeterminedbythedesiredDHWtemperatureatS10
plusthechargingdifference.WhentheDHWheatingtemperature
isreached,theDHWchargingpumpP5isswitchedON.TheDHW
heatingtemperatureatS9istypically5–10degreeshigherthan
thedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S10):
WhenthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperature,theDHWheatingpump(P7)andthe
DHWchargingpump(P5)areswitchedOFF.Thepost-runtimecan
besetindividually.
DHWtankwith2temperaturesensors(S10,upperandS2,
lower):
IfthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperatureandthetemperature(atS2)getshigher
thanthecut-outtemperature,theDHWheatingpump(P7)and
theDHWchargingpump(P5)areswitchedOFF.Thepost-runtime
canbesetindividually.
TheDHWcirculationcanbethroughtheDHWtank(connectionA)
orthroughtheheat-exchanger(connectionB).Thesolutionwith
connectionAresultsinclosingofthemotorizedcontrolvalveafter
theDHWtankchargingprocedure.Thesolutionwithconnection
BisusedtocompensatefortheheatlossintheDHWcirculation
pipe.Furthermore,afterDHWtankcharging,theDHWheating
temperature(atS9)iscontrolledaccordingtothedesiredDHW
temperature.
Thereturntemperature(S7)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS9canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.Inboiler-basedheatingsupplythereturn
temperatureshouldnotbetoolow(sameadjustmentprocedure
asabove).
Aflow/powerlimitationcanbearrangedbyusinganM-busbased
signalfromaflow/heatmeter.
Generalinformation:
The‘Frostprotection’modemaintainsaselectabletemperature,
forexample10°C.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P8)hasaweekscheduleforupto3
ONperiodsperday.
ApplicationP330.4:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexampleDHWcircuit,type1(P330.4):
S1
Outdoortemperaturesensor
S2
(Optional)LowerDHWtanktemperaturesensor
S7
(Optional)Returntemperaturesensor
S9
Flowtemperaturesensor
S10
UpperDHWtanktemperaturesensorr
M3
Motorizedcontrolvalve
P5
DHWchargingpump
P7
DHWheatingpump
P8
DHWcirculationpump
A1
Alarm
6|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330