Danfoss ECL Comfort 310, P330 Operating instructions

Type
Operating instructions
OperatingGuide
ECLComfort310,applicationP330
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................12
2.3Mounting...........................................................31
2.4Placingthetemperaturesensors................................35
2.5Electricalconnections.............................................37
2.6InsertingtheECLApplicationKey..............................50
2.7Checklist............................................................56
2.8Navigation,ECLApplicationKeyP330.........................57
3.0Dailyuse.........................................................62
3.1Howtonavigate...................................................62
3.2Understandingthecontrollerdisplay..........................63
3.3Ageneraloverview:Whatdothesymbolsmean?...........66
3.4Monitoringtemperaturesandsystem
components........................................................67
3.5Influenceoverview................................................68
3.6Manualcontrol.....................................................69
3.7Schedule............................................................70
4.0Settingsoverview............................................71
5.0Settings...........................................................73
5.1IntroductiontoSettings..........................................73
5.2Flowtemperature..................................................74
5.3Roomlimit..........................................................77
5.4Returnlimit.........................................................79
5.5Flow/powerlimit.................................................83
5.6Optimization........................................................86
5.7Controlparameters................................................91
5.8Application.........................................................94
5.9Tanktemperature................................................101
5.10Anti-bacteria......................................................107
5.11Alarm..............................................................109
6.0Commoncontrollersettings............................111
6.1Introductionto‘Commoncontrollersettings..............111
6.2Time&Date.......................................................113
6.3Holiday............................................................114
6.4Inputoverview...................................................116
6.5Log.................................................................117
6.6Outputoverride..................................................118
6.7Keyfunctions.....................................................119
6.8System.............................................................121
7.0Miscellaneous................................................128
7.1ECA30/31setupprocedures.................................128
7.2Overridefunction................................................136
7.3Severalcontrollersinthesamesystem......................139
7.4Frequentlyaskedquestions....................................142
7.5Definitions........................................................145
7.6Type(ID6001),overview.......................................148
7.7ParameterIDoverview..........................................149
©Danfoss|2017.08VI.GU.O3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyP330
(ordercodeno.087H3840).
ThefunctionsarerealizedinECLComfort310foradvanced
solutions,e.g.M-bus,ModbusandEthernet(Internet)
communication.
P330applicationscancommunicate(viaModbusconnections)
withtheDECS2.0system(DanfossEnergyControlSystem).
PleaseseeDECS2.0relatedliteratureontheDanfosswebsite:
http://heating.danfoss.com/xxDocxx/1_MNU17429744_SIT54.html.
Searchfor‘DECS2.0’ .
TheapplicationP330complieswithECLComfortcontrollers310as
ofsoftwareversion1.40(visibleatstart-upofthecontrollerandin
‘Commoncontrollersettingsin‘System’).
AdditionaldocumentationforECLComfort310,modulesand
accessoriesisavailableonwww.ecl.doc.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
2|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
VI.GU.O3.02
©Danfoss|2017.08|3
OperatingGuideECLComfort310,applicationP330
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
2.0Installation
2.1Beforeyoustart
The14differentapplicationsP330.1...P330.14areheatingand
DHWapplicationsinvariouscombinations.
Thebasicprinciplesforaheatingcircuit
(examplereferringtoP330.1)
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.
TheflowtemperaturesensorS3isthemostimportantsensor.The
desiredflowtemperatureatS3iscalculatedintheECLcontroller,
basedontheoutdoortemperature(S1)andthedesiredroom
temperature.Thelowertheoutdoortemperature,thehigherthe
desiredflowtemperature.
Bymeansofaweekschedule(upto3'Comfort'periods/day),
theheatingcircuitcanbein'Comfort'or'Saving'mode(two
differenttemperaturevaluesforthedesiredroomtemperature).
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.Inboiler-basedheatingsupplythe
returntemperatureshouldnotbetoolow(sameadjustment
procedureasabove).
Aflow/powerlimitationcanbearrangedbyusinganM-busbased
signalfromaflow/heatmeter.Furthermore,thelimitationcanbe
inrelationtotheoutdoortemperature.
Ifthemeasuredroomtemperature,S13orviatheremotecontrol
unitECA30doesnotequalthedesiredroomtemperature,the
desiredflowtemperaturecanbeadjusted.
Generalinformation:
In’Saving’modetheheatingcanbereducedortotallyswitched
off.The‘Frostprotectionmodemaintainsaselectableflow
temperature,forexample10°C.
Thecirculationpump(P2)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thedesiredflowtemperatureofheatingcircuit1can,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
Exerciseofcirculationpumpandcontrolvalvecanbearranged.
ApplicationP330.1:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexampleheatingcircuit1(P330.1):
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
(Optional)Returntemperaturesensor
S8
(Optional)Externaltemperaturecontrol,notillustrated
S13
(Optional)Roomtemperaturesensor
M1
Motorizedcontrolvalve
P2
Circulationpump
A1
Alarm
VI.GU.O3.02
©Danfoss|2017.08|5
OperatingGuideECLComfort310,applicationP330
ThebasicprinciplesforaDHWcircuit,type1
(examplereferringtoP330.4)
Bymeansofaweekschedule(upto3'Comfort'periods/day),the
DHWcircuitcanbein'Comfort'or'Saving'mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS10).
TheDHWheatingtemperaturesensorS9isthemostimportant
sensor.IfthemeasuredDHWtemperature(S10)getslowerthanthe
desiredDHWtemperature,theDHWheatingpump(P7)isswitched
ON.Themotorizedcontrolvalve(M3)iscontrolledinorderto
maintaintheDHWheatingtemperatureatS9.TheDHWheating
temperatureisdeterminedbythedesiredDHWtemperatureatS10
plusthechargingdifference.WhentheDHWheatingtemperature
isreached,theDHWchargingpumpP5isswitchedON.TheDHW
heatingtemperatureatS9istypically5–10degreeshigherthan
thedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S10):
WhenthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperature,theDHWheatingpump(P7)andthe
DHWchargingpump(P5)areswitchedOFF.Thepost-runtimecan
besetindividually.
DHWtankwith2temperaturesensors(S10,upperandS2,
lower):
IfthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperatureandthetemperature(atS2)getshigher
thanthecut-outtemperature,theDHWheatingpump(P7)and
theDHWchargingpump(P5)areswitchedOFF.Thepost-runtime
canbesetindividually.
TheDHWcirculationcanbethroughtheDHWtank(connectionA)
orthroughtheheat-exchanger(connectionB).Thesolutionwith
connectionAresultsinclosingofthemotorizedcontrolvalveafter
theDHWtankchargingprocedure.Thesolutionwithconnection
BisusedtocompensatefortheheatlossintheDHWcirculation
pipe.Furthermore,afterDHWtankcharging,theDHWheating
temperature(atS9)iscontrolledaccordingtothedesiredDHW
temperature.
Thereturntemperature(S7)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS9canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.Inboiler-basedheatingsupplythereturn
temperatureshouldnotbetoolow(sameadjustmentprocedure
asabove).
Aflow/powerlimitationcanbearrangedbyusinganM-busbased
signalfromaflow/heatmeter.
Generalinformation:
The‘Frostprotectionmodemaintainsaselectabletemperature,
forexample10°C.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P8)hasaweekscheduleforupto3
ONperiodsperday.
ApplicationP330.4:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexampleDHWcircuit,type1(P330.4):
S1
Outdoortemperaturesensor
S2
(Optional)LowerDHWtanktemperaturesensor
S7
(Optional)Returntemperaturesensor
S9
Flowtemperaturesensor
S10
UpperDHWtanktemperaturesensorr
M3
Motorizedcontrolvalve
P5
DHWchargingpump
P7
DHWheatingpump
P8
DHWcirculationpump
A1
Alarm
6|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
ThebasicprinciplesforaDHWcircuit,type2
(examplereferringtoP330.5)
Bymeansofaweekschedule(upto3'Comfort'periods/day),the
DHWcircuitcanbein'Comfort'or'Saving'mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS10).
WhenthemeasuredDHWtemperature(S10)getslowerthanthe
desiredDHWtemperature,theDHWheatingpump(P7)andthe
DHWchargingpump(P5)areswitchedON.
DHWtankwith1temperaturesensor(S10):
WhenthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperature,theDHWheatingpump(P7)andthe
DHWchargingpump(P5)areswitchedOFF.Thepost-runtimecan
besetindividually.
DHWtankwith2temperaturesensors(S10,upperandS2,
lower):
WhenthemeasuredDHWtemperature(S10)getshigherthanthe
desiredDHWtemperatureandthetemperature(atS2)getshigher
thanthecut-outtemperature,theDHWheatingpump(P7)and
theDHWchargingpump(P5)areswitchedOFF.Thepost-runtime
canbesetindividually.
TheDHWcirculationcanbethroughtheDHWtank(connectionA)
orthroughtheheat-exchanger(connectionB).Thesolutionwith
connectionAresultsinclosingofthemotorizedcontrolvalveafter
theDHWtankchargingprocedure.Thesolutionwithconnection
BisusedtocompensatefortheheatlossintheDHWcirculation
pipe.AfterDHWtankcharging,theDHWchargingpumpP5stops.
TheheatingpumpP7continuesbeingswitchedON.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P8)hasaweekscheduleforupto3
ONperiodsperday.
Generalinformation:
The‘Frostprotectionmodemaintainsaselectabletemperature,
forexample10°C.
ApplicationP330.5:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexampleDHWcircuit,type2(P330.5):
S1
Outdoortemperaturesensor
S2
(Optional)LowerDHWtanktemperaturesensor
S10
UpperDHWtanktemperaturesensor
P5
DHWchargingpump
P7
DHWheatingpump
P8
DHWcirculationpump
A1
Alarm
VI.GU.O3.02
©Danfoss|2017.08|7
OperatingGuideECLComfort310,applicationP330
Thebasicprinciplesforthemastercircuit
(examplereferringtoP330.10)
ThedesiredflowtemperatureatS3isadjustedaccordingtothe
demandfromthesub-circuits(heatingandDHWcircuits).Theflow
temperaturesensorS3isthemostimportantsensor.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thecirculationpump(P1)isONatheatdemandoratfrost
protection.
Generalinformation:
Thedesiredflowtemperatureofthemastercircuitcan,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ApplicationP330.10:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexamplemastercircuit(P330.10):
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
(Optional)Returntemperaturesensor
S8
(Optional)Externaltemperaturecontrol,notillustrated
M1
Motorizedcontrolvalve
P1
Circulationpump
A1
Alarm
8|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
Thebasicprinciplesforthemastercircuitwithbuffer
(examplereferringtoP330.14)
Thehighestdemandfromthesub-circuits(heatingandDHW
circuits)plusadifference('Demandoffset')determinethedesired
buffertanktemperatureatS11.
Whenthemeasuredbuffertanktemperature(S11)getslowerthan
thedesiredbuffertanktemperature,thechargingpump(P1)is
switchedON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain
thebuffertankheatingtemperatureatS3.Themotorizedcontrol
valveisopenedgraduallywhentheflowtemperatureislowerthan
thedesiredflowtemperatureandviceversa.
TheflowtemperaturesensorS3isthemostimportantsensor.
ThedesiredtemperatureatS3isdeterminedbythedesiredbuffer
tanktemperatureatS11plusachargingtemperaturedifference.
ThebuffertankheatingtemperatureatS3istypically5–10degrees
higherthanthedesiredbuffertanktemperature.
Buffertankwith1temperaturesensor(S11):
Whenthemeasuredbuffertanktemperature(S11)getshigher
thanthedesiredbuffertanktemperature,thechargingpump(P1)
isswitchedOFF.Thepost-runtimecanbeset.
Buffertankwith2temperaturesensors(S11,upperandS12,
lower):
Whenthemeasuredupperbuffertanktemperature(S11)gets
higherthanthedesiredbuffertanktemperatureandthemeasured
lowerbuffertanktemperature(S12)getshigherthanthecut-out
temperature,thechargingpump(P1)isswitchedOFF.Thepost-run
timecanbeset.
IfS12isnotconnected,S11willbeusedforONandOFFcontrolof
thechargingpump.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Whenthemeasuredbuffertemperature(S11)getshigherthan
thedesiredbuffertemperature,thedesiredtemperatureatS3is
loweredtotypically10°C.Hereafterthechargingpump(P1)is
switchedOFF.Thepost-runtimecanbeset.
ApplicationP330.14:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents,forexamplemastercircuitwithbuffer(P330.14):
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
(Optional)Returntemperaturesensor
S8
(Optional)Externaltemperaturecontrol,notillustrated
S11
Upperbuffertanktemperaturesensor
S12
(Optional)Lowerbuffertanktemperaturesensor
M1
Motorizedcontrolvalve
P1
Buffertankchargingpump
A1
Alarm
VI.GU.O3.02
©Danfoss|2017.08|9
OperatingGuideECLComfort310,applicationP330
ApplicationP330.14:
InordertoavoidadischargingoftheDHWcircuit(ahigher
DHWtemperaturegoestoalowerbuffertanktemperature)two
parameterscanbeset:
*
Theparameter("Tankstartdiff.",IDno13192)determinesan
acceptabletemperaturedifferencebetweenS10andS11in
ordertostarttheDHWcharging.
*
Theparameter("Tankstopdiff.",IDno13196)determinesan
acceptabletemperaturedropofthedifferencebetweenS10
andS11inordertostoptheDHWcharging.
Generalinformation:
Thedesiredflowtemperatureofthemastercircuitcan,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
10|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
ApplicationP330.1P330.5:
Heatingcircuits2,3,4andDHWcircuitscanbeconnectedafter
heatingcircuit1.Circuit1actsasmasterandcanreactonthe
sub-circuitsdemand.Ifso,thedesiredflowtemperatureatS3can
beinfluencedbythedesiredflowtemperatureatS4,S9,S10and
DHWchargingtemperaturerespectively.
Thedesiredflowtemperatureofheatingcircuit1can,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ApplicationP330.6P330.15:
HeatingcircuitsandDHWcircuitsaretypicallyconnected
afterthemastercontrolledcircuit(M).Whenso,thedesired
flowtemperatureatS3canbeinfluencedbythedesiredflow
temperatureatS4,S9,S10andDHWchargingtemperatures.
Thedesiredflowtemperatureofthemastercircuitcan,viaS8,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ApplicationP330ingeneral:
UptotwoRemoteControlUnits,theECA30(oneforeachheating
circuit)canbeconnectedtooneECLcontrollerinordertomeasure
theroomtemperatureandcontroltheECLcontrollerremotely.
WhentheDHWcircuitisactiveduringthechargingprocedure,
selectedheatingcircuitscanbeclosedinordertogivehigher
prioritytotheDHWcharging.
Oneormoreconnectedfloworenergymeters(basedonM-bus
signal)canlimitthefloworenergytoasetmaximum(DHW
circuits)andinrelationtotheoutdoortemperature(heatingand
mastercircuits).
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
InputS8canbeusedtocontrolthedesiredflowtemperatureof
heatingcircuit1orthemastercircuit.Theappliedvoltagesignalin
therange0-10voltisconvertedintheECLcontrollertothedesired
flowtemperature.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdatacanfurthermorebetransferredtotheModbus
communication.
Alarmrelay(R6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature.
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
VI.GU.O3.02
©Danfoss|2017.08|11
OperatingGuideECLComfort310,applicationP330
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
P330.1
Twoheatingcircuits
12|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
SpecialsettingsfortypeP330.1:
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit(circuit2)
Heatingcircuit2canbeasub-circuittoheatingcircuit1.
Settingsforsub-circuitinordertosenddemandtocircuit1:
MENU\Settings\Application:‘SenddesiredT’
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit:
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit
VI.GU.O3.02
©Danfoss|2017.08|13
OperatingGuideECLComfort310,applicationP330
P330.2
Threeheatingcircuits
SpecialsettingsfortypeP330.2:
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit(circuit2and3)
Heatingcircuit2and3canbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
14|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
P330.3
Fourheatingcircuits.TheMCVincircuit4iscontrolledby010V.
SpecialsettingsfortypeP330.3
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit(circuit2,3and4)
Heatingcircuit2,3and4canbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
VI.GU.O3.02
©Danfoss|2017.08|15
OperatingGuideECLComfort310,applicationP330
P330.4
TwoheatingcircuitsandoneDHWchargingcircuitwithcontrolledheatingtemperature.
SpecialsettingsfortypeP330.4:
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit2andDHWcircuit
Heatingcircuit2andtheDHWcircuitcanbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
DHWcirculationpipe
TheDHWcirculationpipecanbeconnectedtotheDHWtankat'A'forinternal
circulationortotheheatexchangerat'B'forexternalcirculation.
(InternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'1x054OFF
(ExternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'1x054ON
16|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
P330.5
ThreeheatingcircuitsandoneDHWchargingcircuit.
SpecialsettingsfortypeP330.5
Navigation:IDno.:
Recommendedsetting:
Heatingcircuit2and3andDHWcircuit
Heatingcircuit2and3andtheDHWcircuitcanbesub-circuitstoheatingcircuit1.
Settingsforsub-circuit(s)inordertosenddemandtocircuit1:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Heatingcircuit(circuit1)
Settingsforcircuit1inordertoreactondemandinsub-circuit(s):
MENU\Settings\Application:'Demandoffset'
11017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
DHWcirculationpipe
TheDHWcirculationpipecanbeconnectedtotheDHWtankat'A'forinternal
circulationortotheheatexchangerat'B'forexternalcirculation.
(InternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'
1x054
OFF
(ExternalDHWcirculation)MENU\Settings\Application:'Cont.Tcontrol'
1x054
ON
VI.GU.O3.02
©Danfoss|2017.08|17
OperatingGuideECLComfort310,applicationP330
P330.6
Onemastercircuitandoneheatingcircuitassub-circuit.
SpecialsettingsfortypeP330.6:
Navigation:IDno.:
Recommendedsetting:
Themastercircuitreactsondemandinthesub-circuit.
Sub-circuit
Settingsforsub-circuitinordertosenddemandtomastercircuit:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Mastercircuit
Settingsformastercircuitinordertoreactondemandinsub-circuit:
MENU\Settings(M)\Application:'Demandoffset'
1x017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit
18|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
P330.7
Onemastercircuitandtwoheatingcircuitsassub-circuits.
SpecialsettingsfortypeP330.7
Navigation:IDno.:
Recommendedsetting:
Themastercircuitreactsondemandinthesub-circuit(s).
Sub-circuit(s)
Settingsforsub-circuit(s)inordertosenddemandtomastercircuit:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Mastercircuit
Settingsformastercircuitinordertoreactondemandinsub-circuit(s):
MENU\Settings(M)\Application:'Demandoffset'
1x017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
VI.GU.O3.02
©Danfoss|2017.08|19
OperatingGuideECLComfort310,applicationP330
P330.8
Onemastercircuitandthreeheatingcircuitsassub-circuits.TheMCVincircuit3iscontrolledby010V.
SpecialsettingsfortypeP330.8
Navigation:IDno.:
Recommendedsetting:
Themastercircuitreactsondemandinthesub-circuit(s).
Sub-circuit(s)
Settingsforsub-circuit(s)inordertosenddemandtomastercircuit:
MENU\Settings\Application:'SenddesiredT'
1x500
ON
Mastercircuit
Settingsformastercircuitinordertoreactondemandinsub-circuit(s):
MENU\Settings(M)\Application:'Demandoffset'
1x017
3K*
*Thisvalueisaddedtotheheatdemandvaluefromsub-circuit(s)
20|©Danfoss|2017.08
VI.GU.O3.02
OperatingGuideECLComfort310,applicationP330
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162