Danfoss ECL Comfort 210 / 296 / 310, A266 Operating instructions

Category
Heat pumps
Type
Operating instructions
OperatingGuide
ECLComfort210/296/310,applicationA266
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................14
2.3Mounting...........................................................15
2.4Placingthetemperaturesensors................................19
2.5Electricalconnections.............................................21
2.6InsertingtheECLApplicationKey..............................29
2.7Checklist............................................................35
2.8Navigation,ECLApplicationKeyA266.........................36
3.0Dailyuse.........................................................56
3.1Howtonavigate...................................................56
3.2Understandingthecontrollerdisplay..........................57
3.3Ageneraloverview:Whatdothesymbolsmean?...........60
3.4Monitoringtemperaturesandsystem
components........................................................61
3.5Influenceoverview................................................62
3.6Manualcontrol.....................................................63
3.7Schedule............................................................64
4.0Settingsoverview............................................65
5.0Settings...........................................................68
5.1IntroductiontoSettings..........................................68
5.2Flowtemperature..................................................69
5.3Roomlimit..........................................................72
5.4Returnlimit.........................................................74
5.5Flow/powerlimit.................................................80
5.6Optimization........................................................85
5.7Controlparameters................................................92
5.8Application.........................................................99
5.9Heatcut-out......................................................107
5.10Alarm..............................................................110
5.11Alarmoverview..................................................116
5.12Anti-bacteria......................................................117
6.0Commoncontrollersettings............................119
6.1Introductionto‘Commoncontrollersettings..............119
6.2Time&Date.......................................................120
6.3Holiday............................................................121
6.4Inputoverview...................................................123
6.5Log.................................................................124
6.6Outputoverride..................................................125
6.7Keyfunctions.....................................................126
6.8System.............................................................128
7.0Miscellaneous................................................135
7.1ECA30/31setupprocedures.................................135
7.2Overridefunction................................................143
7.3Severalcontrollersinthesamesystem......................146
7.4Frequentlyaskedquestions....................................149
7.5Definitions........................................................152
7.6Type(ID6001),overview.......................................155
7.7ParameterIDoverview..........................................156
©Danfoss|2018.01VI.KT.X4.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA266
(ordercodeno.087H3800).
TheECLApplicationKeyA266contains4subtypes,allapplicablein
ECLComfort210and310:
A266.1:HeatingandDHW
A266.2:HeatingandadvancedDHW
A266.9:HeatinginclusivepressuremonitoringandDHW.
Returntemperaturemonitoringonheatingside.
A266.10:HeatingandDHW.Returntemperaturemonitoringon
heatingside.
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort210forbasic
solutionsandinECLComfort310foradvancedsolutions,for
exampleM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA266complieswithECLComfort210and
ECLComfort310controllersasofsoftwareversion1.11(visible
atstart-upofthecontrollerandin'Commoncontrollersettings'
in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedandthebuilt-inroomtemperaturesensorcanbe
utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://heating.danfoss.com/download
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
VI.KT.X4.02
©Danfoss|2018.01|3
OperatingGuideECLComfort210/296/310,applicationA266
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
4|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.KT.X4.02
©Danfoss|2018.01|5
OperatingGuideECLComfort210/296/310,applicationA266
2.0Installation
2.1Beforeyoustart
TheECLApplicationkeyA266contains4subtypes,A266.1,
A266.2,A266.9andA266.10whicharealmostidentical.
TheapplicationA266.1isveryflexible.Thesearethebasic
principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’
or‘Savingmode(twovaluesforthedesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperaturedoesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Thecirculationpump,P2,isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.Furthermorethe
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.WhentheA266.1isusedinanECLComfort310theflow/
energysignalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
DHW(circuit2):
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
Thereturntemperature(S6)canbelimitedtoafixedvalue.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
TypicalA266.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S4
DHWflowtemperaturesensor,circuit2
S5
(Optional)Returntemperaturesensor,circuit1
S6
(Optional)DHWreturntemperaturesensor,circuit2
S7
(Optional)Flow/energymeter(pulsesignal)
P1
Circulationpump,DHW,circuit2
P2
Circulationpump,heating,circuit1
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
A1
Alarm
6|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
A266.1,ingeneral:
AlarmA1(=relay4)canbeactivatediftheactualflowtemperature
differsfromthedesiredflowtemperature.
HolidayprogramsarepresentforHeatingandDHW.Besides,a
holidayprogramispresentfortheentirecontroller.
WhenthesubtypeA266.1hasbeenuploaded,theECLComfort
controllerstartsinmanualmode.Thiscanbeusedforcheckingthe
controlledcomponentsforcorrectfunctionality.
VI.KT.X4.02
©Danfoss|2018.01|7
OperatingGuideECLComfort210/296/310,applicationA266
TheapplicationA266.2isveryflexible.Thesearethebasic
principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’
or‘Savingmode(twovaluesforthedesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperaturedoesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Thecirculationpump,P2,isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.Furthermorethe
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.WhentheA266.2isusedinanECLComfort310theflow/
energysignalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
DHW(circuit2):
TheDHWtemperatureatS4ismaintainedat‘Comfort’levelata
DHWdraw-off(DHWtapping)(theflowswitch(S8)isactivated).
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
TheDHWtemperaturecontrolisinrelationtoactualsupply
temperature(S6).Inordertocompensateforthereactiontime,the
motorizedcontrolvalvecanbepre-activatedatthestartofaDHW
draw-off(DHWtapping).Anidletemperaturecanbemaintainedat
eitherS6orS4whenthereisnodraw-off(DHWtapping).
Thereturntemperature(S5)canbelimitedtoafixedvalue.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
TypicalA266.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S4
DHWflowtemperaturesensor,circuit2
S5
(Optional)Returntemperaturesensor,circuit1,circuit
2orbothcircuits
S6
(Optional)Supplytemperaturesensor,circuit2
S7
(Optional)Flow/energymeter(pulsesignal)
S8
Flowswitch,DHWdraw-off,circuit2
P1
Circulationpump,DHW,circuit2
P2
Circulationpump,heating,circuit1
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV
A1
Alarm
8|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
A266.2,ingeneral:
AlarmA1(=relay4)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature
ifthetemperatureatS3exceedsanalarmvalue
HolidayprogramsarepresentforHeatingandDHW.Besides,a
holidayprogramispresentfortheentirecontroller.
IfthetemperatureatS3exceedsthealarmvalue'Max.flowT',the
circulationpumpP2isswitchedOFFafterelapseofthe'Delay'.
P2isswitchedONagainwhenthetemperatureatS3getsbelow
alarmvalue.
WhenthesubtypeA266.2hasbeenuploaded,theECLComfort
controllerstartsinmanualmode.Thiscanbeusedforcheckingthe
controlledcomponentsforcorrectfunctionality.
VI.KT.X4.02
©Danfoss|2018.01|9
OperatingGuideECLComfort210/296/310,applicationA266
TheapplicationA266.9isveryflexible.Thesearethebasic
principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’
or‘Savingmode(twovaluesforthedesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thecirculationpump,P2,isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thesecondaryreturntemperature(S2)isusedformonitoring.The
pressuremeasuring(S7)isusedtoactivateanalarmiftheactual
pressureishigherorlowerthanthechosensettings.
WhentheA266.9isusedinanECLComfort310,aconnected
floworenergymeterbasedonM-bussignalcanlimittheflowor
energytoasetmaximumvalue.Furthermorethelimitationcanbe
inrelationtotheoutdoortemperature.Typically,thelowerthe
outdoortemperature,thehighertheacceptedflow/power.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
DHW(circuit2):
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.IfthedesiredDHWtemperaturecannot
bereached,theheatingcircuitcanbeclosedgraduallytoallow
moreenergytotheDHWcircuit.
ThereturntemperatureS6canmeasure,formonitoringpurpose,
thereturntemperatureonthesecondaryside.Analternative
positionforS6canbeinthereturnontheprimarysideinorderto
limitthereturntemperaturetoafixedvalue.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
TypicalA266.9application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Returntemperaturesensor,circuit1,for
monitoring
S3
Flowtemperaturesensor,circuit1
S4
DHWflowtemperaturesensor,circuit2
S5
(Optional)Returntemperaturesensor,circuit1
S6
(Optional)Returntemperaturesensor,secondaryside,
circuit2.Alternativeposition:Return,primaryside
S7
(Optional)Pressuretransmitter,circuit1
S8
(Optional)Alarminput
P1
Circulationpump,DHW,circuit2
P2
Circulationpump,heating,circuit1
M1
Motorizedcontrolvalve,circuit2
M2
Motorizedcontrolvalve,circuit1
A1
Alarm
10|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
A266.9,ingeneral:
AlarmA1(=relay4)canbeactivated:
ifthetemperatureatS3exceedsanalarmvalue
ifthepressureatS7isnotinsideanacceptablepressurerange
ifthealarminputS8isactivated
IfthetemperatureatS3exceedsthealarmvalue'Max.flowT',the
circulationpumpP2isswitchedOFFafterelapseofthe'Delay'.
P2isswitchedONagainwhenthetemperatureatS3getsbelow
alarmvalue.
WhenthesubtypeA266.9hasbeenuploaded,theECLComfort
controllerstartsinscheduledmode.
VI.KT.X4.02
©Danfoss|2018.01|11
OperatingGuideECLComfort210/296/310,applicationA266
TheapplicationA266.10isveryflexible.Thesearethebasic
principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’
or‘Savingmode(twovaluesforthedesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thecirculationpump,P2,isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thesecondaryreturntemperature(S2)isusedformonitoring.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimitthe
floworenergytoasetmaximumvalue.Furthermorethelimitation
canbeinrelationtotheoutdoortemperature.Typically,thelower
theoutdoortemperature,thehighertheacceptedflow/power.
WhentheA266.10isusedinanECLComfort310theflow/energy
signalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
DHW(circuit2):
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.IfthedesiredDHWtemperaturecannot
bereached,theheatingcircuitcanbeclosedgraduallytoallow
moreenergytotheDHWcircuit.
ThereturntemperatureS6canmeasure,formonitoringpurpose,
thereturntemperatureonthesecondaryside.Analternative
positionforS6canbeinthereturnontheprimarysideinorderto
limitthereturntemperaturetoafixedvalue.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
TypicalA266.10application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Returntemperaturesensor,circuit1,for
monitoring
S3
Flowtemperaturesensor,circuit1
S4
DHWflowtemperaturesensor,circuit2
S5
(Optional)Returntemperaturesensor,circuit1
S6
(Optional)Returntemperaturesensor,secondaryside,
circuit2.Alternativeposition:Return,primaryside
S7
(Optional)Flow/energymeter(pulsesignal)
S8
(Optional)Alarminput
P1
Circulationpump,DHW,circuit2
P2
Circulationpump,heating,circuit1
M1
Motorizedcontrolvalve,circuit2
M2
Motorizedcontrolvalve,circuit1
A1
Alarm
12|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
A266.10,ingeneral:
AlarmA1(=relay4)canbeactivated:
ifthetemperatureatS3exceedsanalarmvalue
ifthealarminputS8isactivated
IfthetemperatureatS3exceedsthealarmvalue'Max.flowT',the
circulationpumpP2isswitchedOFFafterelapseofthe'Delay'.
P2isswitchedONagainwhenthetemperatureatS3getsbelow
alarmvalue.
WhenthesubtypeA266.10hasbeenuploaded,theECLComfort
controllerstartsinscheduledmode.
A266,ingeneral:
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.TheECLcontrollersintheECL485system
canworkinmaster-slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdata(ECLComfort310)canfurthermorebetransferred
totheModbuscommunication.
AlarmA1(=relay4)canbeactivated:
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
VI.KT.X4.02
©Danfoss|2018.01|13
OperatingGuideECLComfort210/296/310,applicationA266
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
14|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
VI.KT.X4.02
©Danfoss|2018.01|15
OperatingGuideECLComfort210/296/310,applicationA266
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
16|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
VI.KT.X4.02
©Danfoss|2018.01|17
OperatingGuideECLComfort210/296/310,applicationA266
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
18|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
VI.KT.X4.02
©Danfoss|2018.01|19
OperatingGuideECLComfort210/296/310,applicationA266
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
20|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162