Danfoss ECL Comfort 310, A319 Operating instructions

Category
Thermostats
Type
Operating instructions
OperatingGuide
ECLComfort310,applicationA319
1.0TableofContents
1.0TableofContents...............................................1

2.0Installation........................................................6








3.0Dailyuse.........................................................37







4.0Settingsoverview............................................44
5.0Settings...........................................................46







6.0Commoncontrollersettings..............................76








7.0Miscellaneous..................................................92










OperatingGuideECLComfort310,applicationA319
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
































http://district-heating.danfoss.com/download/tools/












OperatingGuideECLComfort310,applicationA319






http://heating.danfoss.com/.
SafetyNote



















OperatingGuideECLComfort310,applicationA319
Automaticupdateofcontrollersoftware(rmware)




Progressbar






























OperatingGuideECLComfort310,applicationA319
DisposalNote







OperatingGuideECLComfort310,applicationA319
2.0Installation
2.1Beforeyoustart
A319.1
A319.2.

A319.1:
Temperaturecontrolofbuffer




























AND



AND


NOTE:Post-runisnotrespectedifchargingtemperatureS3islower
thandesiredchargingtemperature.


TypicalA319.1application:



Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S1
Outdoortemperaturesensor
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S4
(monitoringonly)Flowtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Upperbuffertemperaturesensor
S7
notused
S8
(mandatory)Lowerbuffertemperaturesensor
S9
Pressuredifferencetransmitter(0-10V)
S10
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm



OperatingGuideECLComfort310,applicationA319










































OperatingGuideECLComfort310,applicationA319
A319.2:





TypicalA319.2application:



Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S1
Outdoortemperaturesensor
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S4
(mandatory)Flowtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Upperbuffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
Pressuredifferencetransmitter(0-10V)
S10
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm



OperatingGuideECLComfort310,applicationA319
2.2Identifyingthesystemtype
Sketchyourapplication
















A319.1,ex.a

Sensoradvice:





OperatingGuideECLComfort310,applicationA319
A319.2,ex.a

Sensoradvice:





OperatingGuideECLComfort310,applicationA319
2.3Mounting
2.3.1MountingtheECLComfortcontroller








LockingtheECLComfort210/310controller

















OperatingGuideECLComfort310,applicationA319
Mountingonawall



MountingonaDINrail(35mm)



DismountingtheECLComfortcontroller











OperatingGuideECLComfort310,applicationA319
2.3.2MountingtheRemoteControlUnitsECA30/31




Mountingonawall



Mountinginapanel









OperatingGuideECLComfort310,applicationA319
2.3.3MountingtheinternalI/OmoduleECA32orECA35




ECA32
ECA35



OperatingGuideECLComfort310,applicationA319
2.4Placingthetemperaturesensors





Outdoortemperaturesensor(ESMT)



Flowtemperaturesensor(ESMU,ESM-11orESMC)





Returntemperaturesensor(ESMU,ESM-11orESMC)


Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)



Boilertemperaturesensor(ESMU,ESM-11orESMC)


Airducttemperaturesensor(ESMB-12orESMUtypes)

DHWtemperaturesensor(ESMUorESMB-12)


Slabtemperaturesensor(ESMB-12)











OperatingGuideECLComfort310,applicationA319
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
-50
80 0
90 0
10 0 0
11 0 0
12 0 0
13 0 0
14 0 0
15 0 0
16 0 0
-25 0 25 50 75 10 0 12 5 15 0
°C
803
843
882
922
961
1000
1039
1078
1117
1155
1194
1232
1271
1309
1347
1385
1423
1461
1498
1535
1573
°C
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150



OperatingGuideECLComfort310,applicationA319
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote












L
N
87 H1 631 .10
Da n fos s





OperatingGuideECLComfort310,applicationA319
2.5.2Electricalconnections,230Va.c.,powersupply,pumps,motorizedcontrolvalvesetc.
Connections,ingeneral.


Relayterminals


Triac(electronicrelay)terminals




2.5.3Electricalconnections,24Va.c.,powersupply,pumps,motorizedcontrolvalvesetc.
Connections,ingeneral.


Relayterminals


Triac(electronicrelay)terminals










OperatingGuideECLComfort310,applicationA319
Electricalconnections,ECA32/ECA35
Connections,ingeneral.


Terminals
ECA32ECA35















OperatingGuideECLComfort310,applicationA319
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals,0-10Voltinputandpressuredifferencetransmitter
A319
TerminalSensor/description
Type
(recom.)














































































  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116