Ideal 61-065 Operating instructions

Category
Cable network testers
Type
Operating instructions

The Ideal 61-065 Vol-Test Voltage Tester is designed to measure AC/DC voltage, ranging from 100 to 600 volts. It features a low impedance design for accurate readings, and replaceable test leads for added versatility. The tester also includes a continuity function that indicates continuity with a bright LED when resistance is less than 500kΩ. Ideal for electricians, technicians, and DIY enthusiasts, the 61-065 is a valuable tool for a variety of electrical testing applications.

The Ideal 61-065 Vol-Test Voltage Tester is designed to measure AC/DC voltage, ranging from 100 to 600 volts. It features a low impedance design for accurate readings, and replaceable test leads for added versatility. The tester also includes a continuity function that indicates continuity with a bright LED when resistance is less than 500kΩ. Ideal for electricians, technicians, and DIY enthusiasts, the 61-065 is a valuable tool for a variety of electrical testing applications.

Vol-Con
®
Voltage/
Continuity Tester
(61-080, 61-076 )
Vol-Test™ Voltage Tester
(61-067, 61-065)
Instruction Manual
Register your product and access more information
at www.idealindustries.com
Read First: Safety Information
Understand and follow operating instructions
carefully. Use the tester and test leads only as
specified in this manual; otherwise, the protection
provided by the tester can be impaired.
WARNING
To avoid possible electric shock, personal
injury or death, follow these guidelines:
• Donotuseiftesterappearsdamaged.
Visually inspect the tester to ensure case
and is not cracked.
• Inspectandreplacetestleadsifinsulation
is damaged, metal is exposed, or probes are
cracked. Pay particular attention to the
insulation surrounding the connectors.
• Alwaysensurethetester,testleadsandall
accessories meet or exceed the measurement
category required in the working environment.
(i.e.CATrating)
• Notethatthemeasurementcategoryand
voltage rating of combinations of the tester,
the test leads, and the accessories is the lowest
of the individual components.
• Donotusetesterifitoperatesabnormallyas
protection maybe impaired.
• Donotuseduringelectricalstormsorinwet
weather.
• Donotusearoundexplosivegas,dust,vapor,
amperage or in damp or wet environments.
• Donotapplymorethantheratedvoltageto
the tester.
• Removethetestleadsfromtheinputjacks
before measuring current.
• Removethetestleadsfromthemeterpriorto
removing battery cover. (61-076,61-080)
• Donotusewithoutthebatteryandbattery
cover properly installed. (61-076,61-080)
• Donotattempttorepairthisunitasithasno
user-serviceable parts.
• Nevergroundyourselfwhentakingelectrical
measurements.
• Connecttheblackcommonleadtoground
or neutral before applying the red test lead to
potentialvoltage.Disconnecttheredtestlead
from the voltage first.
• Keepfingersbehindtheguardringsofthe
probe tips.
• Voltagesexceeding30VACor60VDCposea
shock hazard so use caution.
CAUTION
Toprotectyourself,think“SafetyFirst”:
• Complywithlocalandnationalsafetycodes.
• Useappropriatepersonalprotectiveequipment
such as face shields,
insulating gloves, insulating boots,
and/or insulating mats.
• Beforeeachuse:
- Perform a continuity test by touching the
test leads together to verify the functionality
of the battery and test leads.
- Usethe3PointSafetyMethod.(1)Verify
meter operation by measuring a known
voltage.(2)Applymetertocircuitundertest.
(3)Returntotheknownlivevoltageagainto
ensure proper operation.
• Alwaysworkwithapartner.
#61-080
#61-076
#61-067
#61-065
2
4
3
Neon Bulb
100-600V AC/DC
LEDs (61-076)
5-600V AC/DC
Continuity
Indicator
120-600V AC/DC
Features:
• VibrationModewithindicatormovement
• Auto-SwitchingVoltage/Continuity
Technology(61-076,61-080)
• Independentsolenoidandelectroniccircuitry
design provides back-up voltage indication
for added safety
• LowImpedance
• ReplaceableTestLeads
• Shieldedprobetips
• Ultrasonicallyweldedando-ringsealedfor
added durability
• Indicates:
•100-600VAC/DC(61-065,61-067)
• 5-600VAC/DC(61-076,61-080)
To Measure AC/DC Voltage:
• Ensurethattheplugforthetestleadsisfully
seatedintothebananajacks.
• Connectthetesterinparallelwiththeloador
circuit.
• Thetesterindicatesthevoltagetype,DC
polarity, and the voltage level.
Warning
Donotexceeddutycyclespecifiedontester.
To Test for Continuity (61-080,61-076):
• Ensurethattheplugforthetestleadsisfully
seatedintothebananajacks.
• Testforcontinuitybyconnectingthetesterto
the de-energized circuit.
• Ifcircuithas<500kΩ,theContinuityLED
lights.
• Reversingprodsonthecircuitundertest
verifiescontinuityversuslowvoltage+DC.
Applications:
• LocatingBlownFuses
With power off (61-076,
61-080):Placetesteracross
the suspected fuse to
perform continuity check.
IfcontinuityLEDlights,the
fuseisgood.Ifnot,the
fuse is defective.
Withpoweron:Placetesteracrossthe
“source”sideofonefuseandtheloadside
ofanadjoiningfuse.Ifnoorlowvoltageis
indicated, the fuse next to the load side prod is
blown.Iflinevoltageisindicated,thefuse
nexttotheloadsideprodisOK.Repeatthe
same test with the prods on the opposite side
of the same two fuses to check the other fuse.
5
5
• FindingGroundedSideofLine
(neutral)
Hold one test prod to the ground and touch
the other test prod to each of the line terminals
until one is found that does not give a voltage
indication.Thisisthegroundedsideofthe
line.
ThecontinuityLEDshouldalsolight.
(61-080,61-076)
• CheckingContinuityofCords,Motors,
Appliances, etc. (61-080,61-076)
Remove power source and place tester across
circuittobetested.ContinuityLEDlightsif
resistance is less than 500kΩ.
• LocatingExcessiveLeakagetoGround
(61-080,61-076)
Place tester across the neutral terminal and the
ground.ThesinglecontinuityLEDshouldindi-
cateneutralandgroundareconnected.Ifboth
LEDslight,thereis>5VAC(N-G)indicatinga
high resistance leakage to ground.
Battery Replacement
(61-080,61-076):
• Replacebatterieswhentouchingtheleads
togethernolongerlightsthecontinuityLED.
• Removetestleadsfromtester.
• Carefully,prythetwobatterycapsfromthe
bottom of the case using a screwdriver.
• Replacethebatteries.
• Snapthebatterycapsbackinplaceensuring
the cap is flush with the bottom of the case.
Accessories:
• 61-070Standardtestleads
(61-076,61-065)
• 61-072
Resistor-fused test leads (61-080,61-067)
• C-90Soft-sidedcarryingcase
• 61-010Leathercase
Maintenance:
• Clean the case with a damp cloth and mild
detergent.Donotuseabrasivesorsolvents.
6
Service, and Replacement Parts:
Forreplacementpartsortoinquireaboutservice
informationcontactTechnicalSupport:
1-877-201-9005 or visit our website
www.idealindustries.com.
Specifications:
VACRanges: 120V,240V,480V,600VAC.
VDCRanges: 120V,240V,600VDC
VoltsAccuracy: Relativeindicationonly
Continuity: LEDlightsat<500kΩ
Response time of 100ms.
Frequency: Operatesat25-60Hz
Overload 1000VDC/750VACrms.
protection:
Operating 32°Fto122°F
Environment: (0to50°C)(<70%humidity)
StorageTemp.: -4°Fto140°F(-20to60°C)
(<80%humidity)
Batteries:
Models61-080&61-076only
(4)1.5V(61-201,IECLR44)
BatteryLife: 200hourstypical.
Accessories TestLeads,(4)Batteries,
included: OperatingManual
Dimensions: 7.2”Hx2.4”Wx1.5”D
[183Hx61Wx38D]mm
Weight: 8.0oz(227g)
Safety: UL61010B-1,CATIII-600V
Double Insulation
Instrumenthasbeenevaluatedandcomplies
withinsulationcategoryIII(overvoltage
categoryIII).Pollutiondegree2inaccordance
withIEC-644.Indooruse.
Clamp Meter
10DB
7
Warranty Statement:
Thistesteriswarrantedtotheoriginalpurchaseragainst
defects in material and workmanship for two years from
thedateofpurchase.Duringthiswarrantyperiod,IDEAL
INDUSTRIES,INC.will,atitsoption,replaceorrepair
thedefectiveunit,subjecttoverificationofthedefector
malfunction.
Thiswarrantydoesnotcoverfuses,batteriesordam-
age from abuse, neglect, accident, unauthorized repair,
alteration, or unreasonable use of the instrument.
Anyimpliedwarrantiesarisingoutofthesaleofan
IDEALproduct,includingbutnotlimitedtoimplied
warranties of merchantability and fitness for a particular
purpose,arelimitedtotheabove.Themanufacturer
shall not be liable for loss of use of the instrument or
other incidental or consequential damages, expenses, or
economic loss, or for any claim or claims for such dam-
age, expenses or economic loss.
Statelawsvary,sotheabovelimitationsorexclusions
maynotapplytoyou.Thiswarrantygivesyouspecific
legal rights, and you may also have other rights which
vary from state to state.
Probador de voltaje/
continuidad Vol-Con
®
(61-080, 61-076 )
Voltímetro Vol-Test
®
(61-067, 61-065)
Manual de instrucciones
Registre su producto y acceda a más información
en www.idealindustries.com
Lea Primero: Información de Seguridad
Entiendaysigalasinstruccionesdeoperación
cuidadosamente. Use el multímetro, las sondas
y todos los accesorios únicamente como se
especifica en este manual;de lo contrario, la
protección que proporciona el multímetro puede
verseperjudicada.
ADVERTENCIA
Para evitar posibles riesgos de descarga eléctrica,
lesionesolamuerte,sigaestasdirectrices:
• Nouseelmultímetrosielmismo
pareceestardañado.Inspecciónelovisualmente
para asegurarse de que la cubierta y la pinza no
estén quebradas.
• Inspeccioneyreemplaceloscablessiel
aislamiento está dañado, hay metal expuesto
o las sondas están quebradas. Preste atención
especial al aislante alrededor de los conectores.
• Siempreasegúresedequeel
multímetro, las sondas y todos los accesorios
cumplan o excedan la categoría de medición
necesariaenelambientedetrabajo.(Por
ejemplo,clasificaciónCAT)
• Tomenotadequelacategoríademediciónyla
clasificacióndevoltajedecombinacionesdel
multímetro, la sondas y los accesorios es la
másbajadeloscomponentesindividuales.
8
#61-080
#61-076
#61-067
#61-065
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Ideal 61-065 Operating instructions

Category
Cable network testers
Type
Operating instructions

The Ideal 61-065 Vol-Test Voltage Tester is designed to measure AC/DC voltage, ranging from 100 to 600 volts. It features a low impedance design for accurate readings, and replaceable test leads for added versatility. The tester also includes a continuity function that indicates continuity with a bright LED when resistance is less than 500kΩ. Ideal for electricians, technicians, and DIY enthusiasts, the 61-065 is a valuable tool for a variety of electrical testing applications.