Liebert® GXT5 Lithium-Ion UPS
Installer/User Guide
230V Input, 230V Output, 1000-3000VA
Vertiv™ | Liebert® GXT5 Lithium-Ion UPS
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/ for additional assistance.
The information contained in this document is subject to change without notice
and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages resulting from
use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and
materials to be used in performing procedures not specifically described in this
document.
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential and
proprietary information owned by Vertiv. Any copying, use or disclosure of it
without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
TABLE OF CONTENTS
1 Important Safety Instructions 1
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description 3
2.1 Available Models 3
2.2 Front Panel 4
2.3 Rear Panel 4
2.4 External Battery Cabinet 7
2.5 Major Internal Components and Operating Principle 7
2.6 UPS States and Operating Modes 8
2.6.1 Normal mode 8
2.6.2 Bypass mode 8
2.6.3 Battery mode 9
2.6.4 Frequency converter mode 9
2.6.5 ECO mode 9
3 Installation 11
3.1 Unpacking and Inspection 11
3.2 Pre-installation Preparation 11
3.2.1 Installation clearances 11
3.3 Installing the UPS 12
3.3.1 Tower installation 12
3.3.2 Rack installation 13
3.4 Installing External Battery Cabinets 14
3.5 Connecting AC Input Power 16
3.5.1 Connecting loads 17
3.6 Communication Connections 17
3.6.1 Connecting IntelliSlot communication 17
3.6.2 Connecting to the dry contact and REPO port 17
3.6.3 Connecting a Remote Emergency Power Off (REPO) switch 20
3.6.4 Connecting the USB cable 21
3.6.5 Connecting CLI communication cables 21
3.6.6 UPS management software 21
4 Operating the UPS 23
4.1 Silencing the Audible Alarm 23
4.2 Starting up the UPS 23
4.3 Transferring to Battery Mode 23
4.4 Transferring from Normal to Bypass Mode 24
4.5 Transferring from Bypass to Normal Mode 24
4.6 Shutting Down the UPS Completely 24
4.7 Remote Emergency Power Off (REPO) 24
i
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
5 Operation and Display Panel 25
5.1 LED Indicators 26
5.2 LCD Menu and Screens 27
5.2.1 Startup and flow screens 27
5.2.2 Main menu 27
5.2.3 Status screen 28
5.2.4 Settings submenu 30
5.2.5 Control screen 37
5.2.6 Log screen 37
5.2.7 About screen 41
5.3 Editing Display and Operation Settings 43
5.3.1 Settings prompts 43
5.3.2 Changing the password 44
5.3.3 Selecting the display language 44
5.3.4 Setting the date and time 45
6 Maintenance 47
6.1 Replacing Batteries 47
6.2 Charging Batteries 49
6.3 Checking UPS Operation 49
6.4 Cleaning the UPS 50
6.5 Installing or Replacing Optional Dust Filter 50
6.6 Firmware Updates 51
7 Troubleshooting 53
7.1 Symptoms that Require Troubleshooting 53
7.2 Audible Alarm (Buzzer) 53
7.2.1 Faults 53
7.3 Troubleshooting UPS Issues 54
8 Specifications 55
8.1 Battery Run Times 59
Appendices 62
Appendix A: Technical Support 62
ii
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
1 Important Safety Instructions
IMPORTANT! This manual contains important safety instructions that must be followed during the installation and
maintenance of the UPS and batteries. Read this manual thoroughly and the safety and regulatory information,
available at https://www.vertiv.com/ComplianceRegulatoryInfo, before attempting to install, connect to supply, or
operate this UPS.
1 Important Safety Instructions 1
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
1 Important Safety Instructions
2
Proprietary and Confidential ©2022 Vertiv Group Corp.
This page intentionally left blank
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description
The Liebert® GXT5 Lithium-Ion is a compact, online Uninterruptible Power System (UPS) that continuously conditions and
regulates its output voltage. The Liebert® GXT5 Lithium-Ion supplies microcomputers and other sensitive equipment with
clean sine wave input power.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags,
spikes, and complete failure that may interrupt computer operations, cause data loss, and damage equipment.
The Liebert® GXT5 Lithium-Ion protects equipment from these disturbances. The Liebert® GXT5 Lithium-Ion continuously
charges its batteries from the mains, enabling it to supply power to connected loads, even when the mains fail.
2.1 Available Models
The Liebert® GXT5 Lithium-Ion includes the following features. Table 2.1 below, lists the available models and power ratings.
Input power factor greater than 0.99.
Optional tower or rack installation to meet varying installation requirements.
Adapts to areas with unstable power mains supply via high frequency double conversion topology structure, with
high input power factor, wide input voltage range, and output immune to grid interference.
Programmable outlets allow for load shedding to protect key devices when load is heavy.
Operation and display panel with model specific color LCD offers simple configuration and control of the UPS.
ECO power supply mode and smart sleep mode help to save maximum amount of energy.
UPS Model Nominal Power Rating at 230 V Input
GXT5LI-1000IRT2UXL 1000 VA/1000 W
GXT5LI-1500IRT2UXL 1500 VA/1500 W
GXT5LI-2000IRT2UXL 2000 VA/2000 W
GXT5LI-3000IRT2UXL 3000 VA/2700 W
Table 2.1 UPS Models and Power Ratings
UPS Model EBC Model Maximum Number of EBCs
GXT5LI-1000IRT2UXL
VEBCLI-48VRT1U 8
GXT5LI-1500IRT2UXL
GXT5LI-2000IRT2UXL
GXT5LI-3000IRT2UXL
Table 2.2 UPS Models and Optional External Battery Cabinet (EBC)
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description 3
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
UPS Model Internal Battery Kit Model Quantity Required
GXT5LI-1000IRT2UXL GXT5LI-48VBATKIT1 1
GXT5LI-1500IRT2UXL
GXT5LI-48VBATKIT2 1GXT5LI-2000IRT2UXL
GXT5LI-3000IRT2UXL
Table 2.3 UPS Models and Internal Battery Kit
2.2 Front Panel
The various Liebert® GXT5 Lithium-Ion models have the same general appearance, with the main difference being the
receptacle types on the rear panel.
Figure 2.1 Front View
2.3 Rear Panel
Figure 2.2 below, Figure 2.3 on the facing page and Figure 2.4 on page6 detail the rear panel features for each Liebert® GXT5
Lithium-Ion model.
Figure 2.2 GXT5LI-1000/1500IRT2UXL
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description
4
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
Item Description
1 USB port
2 External Battery Cabinet (EBC) CAN ports
3 RS-232 port (used for CLI)
4 Dry contact communication terminal block
5 Remote Emergency Power Off (REPO)
6 EBC terminal
7 Input power plug (C14)
8 Non programmable output receptacles (C13)
9 Programmable output receptacles (C13)
10 Input circuit breaker (10 A)
11 Vertiv™ Liebert® IntelliSlot™ port
Figure 2.3 GXT5LI-2000IRT2UXL Rear Panel
Item Description
1 USB port
2 External Battery Cabinet (EBC) CAN ports
3 RS-232 port (used for CLI)
4 Dry contact communication terminal block
5 Remote Emergency Power Off (REPO)
6 Input circuit breaker (16 A)
7 Input power plug (C20)
8 Non programmable receptacles (C13)
9 Programmable receptacles (C13)
11 EBC terminal
12 Liebert® Intellislot™ port
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description 5
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
Figure 2.4 GXT5LI-3000IRT2UXL Rear Panel
Item Description
1 USB port
2 External Battery Cabinet (EBC) CAN ports
3 RS-232 port (used for CLI)
4 Dry contact communication terminal block
5 Remote Emergency Power Off (REPO)
6 Input circuit breaker (20 A)
7 Input power plug (C20)
8 Output circuit breakers (10 A)
9 Non programmable output receptacles (C13)
10 Programmable output receptacles (C13)
11 Non programmable output receptacle (C19)
12 EBC terminal
13 Vertiv™ Liebert® IntelliSlot™ port
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description
6
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
2.4 External Battery Cabinet
An optional external battery cabinet (VEBCLI-48VRT1U) is available for all UPS models. The external battery cabinet includes
a battery power cable and communication cable. Up to 8 battery cabinets may be connected in parallel to the UPS. By default,
the battery cabinets will be automatically detected by the UPS once connected. Auto detection can be changed in the
settings menu. See Settings submenu on page30 , for more information. See Table 9.3 on page57, for the cabinet
specifications. See Battery Run Times on page59 , for approximate battery run times with additional EBCs. See Installing
External Battery Cabinets on page14 , to connect the cabinets.
Figure 2.5 External Battery Cabinet
Item Description
1 Communication ports
2 Battery connectors
3 Battery breaker
2.5 Major Internal Components and Operating Principle
Figure 2.6 below, shows the UPS operating principle. Table 2.4 on the next page, describes the function of the major
components in the UPS.
NOTE: Figure 2.6 below, is one example of basic operation.
Figure 2.6 Basic Operating Principle Diagram
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description 7
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
Item Component Operation/Function
1
Transient Voltage
Surge Suppression
(TVSS) and
EMI/RFI Filters
Provide surge protection. Filter Electromagnetic Interference (EMI) and Radio Frequency Interference (RFI). Minimize
surges or interference present in the utility power and protect devices connected on the same branch as the UPS.
2
Rectifier/Power
Factor Correction
(PFC) Circuit
In normal operation, converts utility AC power to regulated DC power for use by the inverter while ensuring that the
wave shape of the input current used by the UPS is near ideal. Extracting this sine wave input current ensures efficient
use of utility power and reduces reflected harmonic distortion making cleaner power available to devices that are not
protected by the UPS.
3 Batteries
Lithium-ion batteries.
NOTE: The optimum battery ambient temperature range is 59°F-86°F (15°C-30°C).
4DC to DC
Converter
Raises the DC voltage from the battery to the optimum operating voltage for the inverter. This allows the inverter to
operate continuously at its optimum efficiency and voltage, thus increasing reliability.
5 Inverter
In normal operation, converts utility AC power to regulated DC power for use by the inverter while ensuring that the
wave shape of the input current used by the UPS is near ideal. Extracting this sine wave input current ensures efficient
use of utility power and reduces reflected harmonic distortion making cleaner power available to devices that are not
protected by the UPS.
6Dynamic Internal
Bypass
In the unlikely event of UPS failure such as overload or over temperature, automatically transfers the connected load to
bypass. To manually transfer the connected load from inverter to bypass, see Transferring from Normal to Bypass
Mode on page24 .
7 EMI/RFI Filters Filter Electromagnetic Interference (EMI) and Radio Frequency Interference (RFI). Minimize interference present in the
utility power and protect devices connected on the same branch as the UPS.
8 Outlet group Programmable output receptacles.
9 Outlet group General output receptacles.
10 Outlet group General output receptacles on 3000 VA models only.
Table 2.4 Major Components
2.6 UPS States and Operating Modes
NOTE: LED Indicators on page26 , for description of the run indicator and alarm indicator LEDs mentioned in this
section.
2.6.1 Normal mode
When utility power is normal, the Normal mode employs the rectifier and inverter to provide voltage and frequency stabilized
power to the load. The battery is charged in the normal mode. On the front panel display, the run indicator (green) is ON, the
alarm indicator is OFF, and the buzzer is silent. The LCD Flow screen displays energy flow from the input power source to the
battery and then to the UPS inverter.
2.6.2 Bypass mode
Bypass mode supplies power to the load from the bypass source (utility power), if an overload or fault occurs during normal
operation. On the front panel display, the run indicator (green) is ON, the alarm indicator (yellow) is ON, and the buzzer beeps
once each seconds. The LCD Flow screen displays energy flow from the input power source through the bypass path instead
of the UPS inverter.
NOTE: If utility power fails or the utility voltage goes outside of the permissible range during bypass mode operation,
the UPS shuts down and no output is supplied to the load.
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description
8
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
2.6.3 Battery mode
Battery mode supplies battery power to the load if utility power fails or if the utility voltage goes outside of the permissible
range. On the front panel display, the run indicator (green) is ON, the alarm indicator (yellow) is ON, and the buzzer beeps
once each second. The LCD Flow screen displays energy flow from the battery through the UPS inverter. The battery status
displays Discharge.
NOTE: The batteries are fully charged before shipment. However, transportation and storage inevitably cause some
loss of capacity. To ensure adequate backup time, it is recommended to charge the batteries for at least 2 hours
before first startup.
NOTE: If utility power fails and the batteries have charge then cold start the UPS in battery mode and use battery
power to extend system availability for a time. At least one external battery cabinet is required for cold start.
NOTE: Powering off the UPS when it is in battery mode results in loss of output power to the connected load.
2.6.4 Frequency converter mode
All models of the Vertiv™ Liebert® GXT5 Lithium-Ion are capable of frequency conversion. Frequency Conversion Mode can
be selected using the Settings menu. For more information on the Settings menu, see Settings submenu on page30 .
Allowable frequency operating modes include:
Auto Sensing - 50 Hz or 60 Hz – Bypass Enabled
Auto Sensing - 50 Hz or 60 Hz – Bypass Disabled
Frequency Converter - 50 Hz – Bypass Disabled
Frequency Converter - 60Hz – Bypass Disabled
NOTE: Auto Sensing at 50 Hz or 60 Hz and Bypass Enabled is set default for all models of the Liebert® GXT5 Lithium-
Ion.
2.6.5 ECO mode
The energy saving ECO mode reduces power consumption by powering the load via bypass if the bypass voltage is normal or
by powering the load via the inverter when the bypass voltage is abnormal. Make use of ECO mode to power equipment that is
not sensitive to power grid quality via bypass and reduce power consumption.
NOTE: During ECO mode, if a bypass failure or abnormal bypass voltage notification appears when the output is not
overloaded, the UPS will transfer to Normal Mode. However, if a notification showing bypass failure or abnormal
bypass voltage appears when the output is overloaded, the UPS will shut down the bypass and therefore the load will
shut down.
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description 9
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
2 Vertiv™ Liebert® GXT5 Lithium-Ion Description
10
Proprietary and Confidential ©2022 Vertiv Group Corp.
This page intentionally left blank
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
3 Installation
NOTE: Do not start the UPS until the installation is finished.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. Before starting with
installation, verify that all external overcurrent protection devices are open (Off), and that they are locked
out and tagged appropriately to prevent activation during the installation, verify with a voltmeter that power
is Off. And wear appropriate, OSHA approved personal protective equipment (PPE) per NFPA 70E. Failure to
comply can cause serious injury or death. Before proceeding with installation, read all instructions and follow
all local codes.
3.1 Unpacking and Inspection
Unpack the UPS and conduct the following checks:
Inspect the UPS for shipping damage. damage. If any shipping damage is found, report it to the carrier and the
local Vertiv.
Check the accessories included against the packing list. Contact local Vertiv representative immediately in the
case of any discrepancy.
CAUTION: The UPS is heavy (see Specifications on page55 , for the weight). Take proper precautions when
lifting or moving the unit.
3.2 Pre-installation Preparation
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. The installation
environment should meet the specifications listed in Specifications on page55 .
Place the UPS in an area of unrestricted air flow around the unit, away from water, flammable liquids, gases,
corrosives, and conductive contaminants. Avoid direct sunlight.
NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.
3.2.1 Installation clearances
Maintain at least 4 inches (100 mm) of clearance in the front and rear of the UPS. Do not obstruct the air inlets on the front
panel and rear panel of the UPS. Blocking the air inlets reduces ventilation and heat dissipation, shortens the service life of the
unit.
3 Installation 11
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
3.3 Installing the UPS
The UPS may be installed as a tower or in a rack, depending on available space and use considerations. Determine the type of
installation and follow the appropriate instructions. See Tower installation below or Rack installation on the facing page .
NOTE: When installing the UPS or making input and output connections, comply with all relevant safety codes and
standards.
3.3.1 Tower installation
To install the UPS as a tower:
1. Take the support bases out of the accessories box.
Figure 3.1 Support Bases
Item Description
1 Support bases
2
Spacers with connectors
NOTE: Two spacers are shown here. If installing without external battery cabinets no spacer is needed. One spacer is needed for
each additional battery cabinet.
2. If optional, Vertiv™ Liebert® external battery cabinets needs to be connected, take out the spacers shipped with
the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 3.1 above. Each Vertiv™ Liebert® GXT5 Lithium-
Ion requires 2 support bases, one in the front and one in the rear.
4. Place the Liebert® GXT5 Lithium-Ion and any battery cabinets on the 2 support bases and spacers (if applicable).
3 Installation
12
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
3.3.2 Rack installation
When installed in a rack enclosure, the Vertiv™ Liebert® GXT5 Lithium-Ion UPS and External Battery Cabinets (EBC) must be
supported by a shelf or rack mount rails.
Procedure:
1. Attach rail kit inner guides to the UPS.
2. Attach the handles to the UPS.
3. Install the rail kit outer guides in the rack.
NOTE: Align shelf of rack kit with rack U number for proper alignment.
4. Install the UPS in the rack.
5. Secure the handles to the rack.
Figure 3.2 UPSRack Installation
3 Installation 13
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
3.4 Installing External Battery Cabinets
Optional, External Battery Cabinets (EBC) may be connected in parallel to the UPS to provide additional battery run time. For
approximate battery run times with additional EBCs, see Battery Run Times on page59 . External battery cabinets are placed
on one side of the UPS in a tower configuration or stacked beneath the UPS in a rack configuration. Up to 8 EBCs may be
connected to the UPS. By default, battery cabinets will be automatically detected by the UPS once connected. Auto detection
can be changed in the settings menu. For more information, see Settings submenu on page30 .
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power
supplies before working with the UPS. Ensure that the unit is shut down and power has been disconnected
before performing any maintenance.
To install the EBCs:
1. Inspect the EBC for freight damage. Report damage to the carrier and the local dealer or Vertiv representative.
2. For tower installation:
An additional set of support base extensions shipped with each EBC.
See the steps in Tower installation on page12 , to connect the support extenders and install the bases.
- or –
3. For rack installation:
a. Attach rail kit inner guides onto the EBC.
b. Attach the handles to the EBC.
c. Install the rail kit outer guides in the rack.
NOTE: Align shelf of rack kit with rack U number for proper alignment.
d. Install the EBC in the rack.
e. Secure the handles to the rack.
3 Installation
14
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
Figure 3.3 EBC Rack Installation
4. Verify that the EBC breaker is in the “Off” position.
5. Connect the cables (included in the package) as per the following instructions, see Figure 3.4 on the next page
for reference:
a. Connect one end of the EBC cable to the UPS EBC terminal (1a in Figure 3.4 on the next page) and one
end to the battery cabinet EBC terminal (1b). Connect one end of the CAN communication cable (attached
to the EBC cable) to the UPS CAN port (1c) and the other end to the battery cabinet CAN port (1d).
b. If connecting more than one battery cabinet, connect one end of an additional EBC cable to the open EBC
terminal on the first battery cabinet (2a). Connect the other end to the EBC terminal of the second battery
cabinet (2b). Connect one end of the CAN communication cable to the CAN port of the first battery
cabinet (2c) and the other end to the CAN port of the second battery cabinet (2d).
c. Repeat step b for each battery cabinet. If desired for redundancy, an additional CAN communication cable
can be connected from the open CAN port of the last EBC (3a) to the open CAN port of the UPS (3b). This
cable is not provided, a standard Cat-5 network cable can be used for this connection.
3 Installation 15
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
Figure 3.4 EBCs Connected to the UPS
6. Turn the EBC breaker in each EBCto the “On” position. The additional backup run time is enabled.
NOTE: When removing an EBC, turn off the circuit breaker on the rear of the cabinet before disconnecting the cable.
NOTE: If shipping or storing the UPS for an extended time, disconnect the EBCs to minimize standby current drain on
the batteries and help maintain design life.
3.5 Connecting AC Input Power
Ensure that all the loads are turned off. Prepare an input power supply that is properly protected by a circuit breaker in
accordance with national and local electrical codes. The wall receptacle must be grounded. We recommend installing an
upstream circuit breaker of the same series as the input circuit breaker of the Vertiv™ Liebert® GXT5 Lithium-Ion.
Table 3.1 below, lists the specifications of the input circuit breaker on the rear panel by UPS model.
Model Rated Circuit Breaker
GXT5LI-1000IRT2UXL 10 A
GXT5LI-1500IRT2UXL 10 A
GXT5LI-2000IRT2UXL 16 A
GXT5LI-3000IRT2UXL 20 A
Table 3.1 Input Circuit Breaker Specifications
To connect AC input power, plug the input plug of the UPS into the input power connection.
NOTE: If the input plug will serve as the disconnecting device, the wall socket/outlet must be near the UPS and must
be easily accessible, per the National Electric Code/NFPA 70 requirements.
3 Installation
16
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70