Ideal 61-534 is an automatic circuit identifier that comes with a digital receiver and a 120V GFCI receptacle tester. It helps to quickly and easily locate the correct circuit breaker supplying power to an AC outlet or a lighting fixture. The device features a non-contact voltage sensor that can detect voltage from 80 to 300VAC, and a transmitter that works on 120VAC circuits. It also tests GFCIs wired to 3 conductors and verifies the wiring configuration. The low battery indicator ensures that the device is always ready to use.

Ideal 61-534 is an automatic circuit identifier that comes with a digital receiver and a 120V GFCI receptacle tester. It helps to quickly and easily locate the correct circuit breaker supplying power to an AC outlet or a lighting fixture. The device features a non-contact voltage sensor that can detect voltage from 80 to 300VAC, and a transmitter that works on 120VAC circuits. It also tests GFCIs wired to 3 conductors and verifies the wiring configuration. The low battery indicator ensures that the device is always ready to use.

61-534
Automatic Circuit Identifier
With Digital Receiver and
120V GFCI Receptacle Tester
The task of locating AC circuits is now made quick and easy. No more guessing
or trial and error when it comes to locating the correct circuit breaker supplying
power to an AC outlet or lighting fixture.
WARNING: Read and understand operating instructions before using product.
WARNING: Use extreme care when working around AC circuits, severe shock
hazards exist. If used on a circuit controlled by a dimmer, turn the dimmer to the
highest on position. Do not use in cardiac care areas. Do not use during electrical storms or in wet weather
• Do not use around explosive gas, dust, vapor or in damp or wet environments. Do not submerge or expose the meter
to water and do not use if the meter has ever been exposed to water or other fluids.
• Do not apply more than the rated voltage.
• Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
Features:
• Automatically and quickly indicates the correct breaker
• Non-contact voltage sensor from 80-300VAC
• Transmitter works on 120VAC Hot to Neutral circuits
• Tests GFCIs wired to 3 conductors with a continuous ground
path back to the panel.
• Verifies wiring configuration
• Low battery indicator
OPERATION:
Self-Test
Depress the receiver’s power switch forward to the ON position. The unit will perform a self-test to ensure proper operation.
Low Battery Detection
After performing the self-test, the receiver will verify the voltage of the 9Vdc battery. If the battery voltage is below 7.3 volts, the
receiver will beep three times and turn itself off. Remove the old battery, and replace it with a standard 9Vdc battery.
Idle Mode
Provided the battery is good, the receiver will enter the idle mode. Both the receiver’s LEDs will remain on and the receiver will
continually check for any active signals.
Non-Contact Voltage Test
Point the receiver’s nose towards a live AC receptacle or power cord. Once an AC Voltage field of > 80V is sensed, the receiver will
switch to Voltage Sensor mode. The red LED remains lit and the receiver will beep. The beeping speed increases when the receiver
is moved closer to the AC power source, and slows when the receiver is moved further away. Once the receiver senses a signal
from the transmitter, it will switch to the circuit identifier mode. The circuit identifier mode is indicated by a steady green LED.
Note that if a steady Green light is on, then the unit is no longer in the Non-Contact Voltage (NCV) function. To re-enter NCV
mode, power the unit off and then on again. Certain loads mimic the breaker mode signal and may cause the unit to exit NCV
mode and enter the breaker search mode, even if the transmitter is not plugged in. Use caution if the unit indicates that no voltage
is present. Always verify that the green light is not on when using the NCV function.
Locating A Circuit Breaker or Fuse:
1. Plug the transmitter into the receptacle.
2. Go to the circuit breaker panel box.
3. Turn the receiver on and allow it to complete its self-test away from power.
4. Place the flat surface of the tapered end of the receiver directly onto the circuit
breaker or fuse as shown. If the receiver is held at any other angle, inaccurate
readings may occur.
5. Slide the nose of the receiver down each breaker along both sides of the panel. Note
that the receiver will beep frequently as it measures the relative signal strength.
6. Move the receiver down each breaker once more. On the second pass, the receiver
will beep and the green LED will flash only at the circuit breaker powering
the transmitter.
7. Trip the breaker off and check that the LED’s of the transmitter in the outlet are off to confirm you have selected the correct
breaker or fuse.
Locating a Circuit Breaker or Fuse Controlling an Incandescent Light Fixture
1. If the incandescent light fixture is controlled by a wall switch, make sure the wall switch is OFF.
2. Remove light bulb.
3. Install a Screw-in socket adapter (not included).
4. Plug the transmitter into the adapter. Note that a 3 prong to 2 prong adapter will be required.
5. Turn on the wall switch and follow the procedure described in Locating a Circuit Breaker or Fuse, steps 3 through 7.
NEVER plug the transmitter into the output of a dimmer switch or lighting ballast. Damage to the transmitter may occur.
Receiver Auto Power Off:
If the receiver is left on and not utilized for 10 minutes (no energized AC circuit or transmitter signals are detected), it will
automatically shut down to conserve its battery life.
Battery Replacement:
Unscrew and remove battery cover. Insert new 9V battery into battery compartment and re-install battery cover.
LEDs
Power Switch
Battery Compartment
Red LED
Green LED
Verifying Receptacles for Correct Wiring:
Plug the transmitter into a standard 120 VAC receptacle. The three LEDs on the transmitter will indicate the wiring configuration
while the label on the transmitter interprets the LED lighting combinations.
Caution: The tester is for indication purposes only and a correct indication does not guarantee the integrity of the wiring. Any
incorrect or unclear indications should be referred to a licensed electrician for investigation and correction.
GFCI Testing (61-534)
1. Consult the GFCI device manufacturer’s instructions to determine that the GFCI is installed in accordance with the manufac-
turer’s specifications.
2. Check for correct wiring of the receptacle and all remotely connected receptacles on the branch circuit.
3. Operate the test button on the GFCI installed in the circuit. The test light will turn on, indicating the activation of the GFCI
test. The GFCI must trip. If the GFCI does not trip, consult a qualified electrician. If it does trip, reset the GFCI.
4. Activate the test button on the GFCI tester for a minimum of 6 seconds when testing the GFCI condition. Visible indication
on the GFCI tester must cease when tripped.
5. If the tester fails to trip the GFCI, it suggests: (a) a wiring problem with a totally operable GFCI, or (b) proper wiring with a
faulty GFCI. Consult with an electrician to check the condition of the wiring and the GFCI.
CAUTION: When testing GFCIs installed in 2-wire systems (no ground wire available), the tester may give a false indication
that the GFCI is not functioning properly. If this occurs, recheck the operation of the GFCI using the test and reset buttons. The
GFCI button test function will demonstrate proper operation.
NOTE:
• All appliances or equipment on the circuit being tested should be unplugged to help avoid erroneous readings.
• Not a comprehensive diagnostic instrument but a simple instrument to detect nearly all probable common improper wiring
conditions.
• Refer all indicated problems to a qualified electrician.
• Will not indicate quality of ground.
• Will not detect 2 hot wires in circuit.
• Will not detect a combination of defects.
• Will not indicate reversal of grounded and grounding conductors.
Clean with a dry cloth.
SPECIFICATIONS:
Operating Range: 100-120VAC
Operating Frequency: 47-63Hz
Maximum Load: 18A (4ms) at 120VAC, 200mW max, at 120VAC
Duty Cycle: Max: 4mS every 16.6mS (continuous), (.24%)
Weight (excluding battery): Transmitter approx 50gr., Receiver approx. 85 gr.
Power Supply: 9VDC battery
Operating Temperature: 0 to 50ºC
WARNING: This product contains chemicals known to the state of California to cause cancer, birth defects or other
reproductive harm.
IDEAL INDUSTRIES, INC.
Sycamore, IL 60178, U.S.A.
800-435-0705
www.idealind.com
ND 5416-7 Made in China
WARRANTY STATEMENT:
This tester is warranted to the original purchaser against defects in material and workmanship for two years from the date of
purchase. During this warranty period, IDEAL INDUSTRIES, INC. will, at its option, replace or repair the defective unit, subject
to verification of the defect or malfunction. Your original receipt from an authorized distributor of IDEAL INDUSTRIES, INC. is
your proof of purchase. Register your product at: http://www.idlim.net/support/registration/.
Any implied warranties arising out of the sale of an IDEAL product, including but not limited to implied warranties of
merchantability and fitness for a particular purpose, are limited to the above. The manufacturer shall not be liable for loss of
use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim or claims for
such damage, expenses or economic loss.
State laws vary, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and
you may also have other rights which vary from state to state.
Warranty does not cover batteries.
Disposal of waste electrical and electronic equipment
In order to preserve, protect and improve the quality of environment, protect human health and utilize natural
resources prudently and rationally, the user should return unserviceable product to relevant facilities in accordance
with statutory regulations. The crossed-out wheeled bin indicates the product needs to be disposed of separately
and not as municipal waste.
Disposal of used batteries/accumulators!
The user is legally obliged to return used batteries and accumulators. Disposing of used batteries in the household
waste is prohibited! Batteries/accumulators containing hazardous substances are marked with the crossed-out
wheeled bin. The symbol indicates that the product is forbidden to be disposed of via the domestic refuse. The
chemical symbols for the respective hazardous substances are Cd = Cadmium, Hg = Mercury, Pb = Lead. You can return used
batteries/accumulators free of charge to any collecting point of your local authority, our stores, or where batteries/accumulators
are sold. Consequently you comply with your legal obligations and contribute to environmental protection.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Ideal Automatic Circuit Identifier Operating instructions

Type
Operating instructions

Ideal 61-534 is an automatic circuit identifier that comes with a digital receiver and a 120V GFCI receptacle tester. It helps to quickly and easily locate the correct circuit breaker supplying power to an AC outlet or a lighting fixture. The device features a non-contact voltage sensor that can detect voltage from 80 to 300VAC, and a transmitter that works on 120VAC circuits. It also tests GFCIs wired to 3 conductors and verifies the wiring configuration. The low battery indicator ensures that the device is always ready to use.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI