JUNG SL280 Operating instructions

Type
Operating instructions
Automatic switch/system sensor 180 UP
Ref.nos. .. 180-2 .., ..280-2.., 200 UE
A 25
System sensor – Technical data
ref.nos. .. 180-2..,.. 280-2 ..
Covered area 180°
Type of protection IP 20 / IP 44
(depending on design)
Cover with lens for 1.1 m mounting height
Nominal range, frontal 10 m
Nominal range, lateral 2 x 6 m
Recommended installation
height for rated range 1.10 m
Number of zones/levels 18 / 2
Cover with lens for 2.2 m mounting height
Nominal range, frontal 12 m
Nominal range, lateral 2 x 6 m
Recommended installation
height for rated range 2.20 m
Number of zones/levels 18 / 2
Sensitivity adjustable
from 100 % – 20 %
Time delay and light threshold values are
determined by other systems components.
Wiring e.g. JY-ST-Y
2 x 2 x 0.6
JY-ST-Y 2 x 2 x 0.8
or YR 4 x 0.8
each max.100 m long
Number of system sensors
max. 8 on system performance unit
WL 2200 WW
max. 8 on system performance unit
WL 2200 REG
max. 16 on system performance unit
WL 2200-2 REG
Type of protection
IP 20
Connection terminals
Lx Brightness signal
S Switch signal
+, – Power supply
Settings
The time and brightness settings are adjusted
on the system performance unit.
Connection diagrams
Line wiring
A maximum of 8 system sensors can be
connected to 1-channel system performance
units for surface mounting and series embo-
diment or 16 system sensors on 2-channel
system performance unit for series embodi-
ment.
The brightness is only measured by one
system sensor (unit 1 in diagram) and send
to the system performance unit (A).
Star wiring
A maximum of 8 system sensors can be
connected to 1-channel system performance
units for surface mounting and series embo-
diment or 16 system sensors on 2-channel
system performance unit for series embodi-
ment.
The brightness is only measured by one
system sensor (unit 1 in diagram) and send
to the system performance unit (A).
max. 100 m
Lx S–+
Lx S–+
Lx S–+
max. 100 m
Lx S–+
Lx S–+
Lx S–+
max. 100 m
max. 100 m
Lx S–+
A
Lx S +
+
S
Lx
L
N
+
S
Lx
L
N
Lx S–+
1
2
8
A
max. 100 m
Lx S–+
A
Lx S–+
A
Maximum length of system sensor wiring
a) Line wiring:
Keep line losses low.Stick to max. cable
length of 100 m between system perfor-
mance unit (I-system performance unit for
surface mounting, II-system performance unit
for series embodiment) and last system
sensor.
b) Star wiring:
Keep line losses low.Stick to max. cable
length of 100 m between system perfor-
mance unit (I-system power unit for surface
mounting, II-system power unit series embo-
diment) and each system sensor.
Lx S–+
Lx S–+
Lx S–+
1
2
8
A
max. 100 m
Warning!
Each system sensor has a brightness sensor,
however only the brightness sensor of one
system sensor may be connected with the
power unit, i.e.only one system sensor may
be connected with the Lx-line. Only this
system sensor measures the brightness and
passes this value onto the system perfor-
mance unit for evaluation.
Looping of Lx signals (brightness signals) on
remaining system sensors to the power unit.
The connection of several performance
units to one system sensor lead is not per-
mitted as this would cause a malfunction.