JUNG 245TLREG Operating instructions

Type
Operating instructions

This manual is also suitable for

A 46
The devices are of a modular design.They
are snapped onto a top hat rail.
Max. installed power is 500 W for 230 V
incandescent lamps or 230 V halogen lamps
or max. 14 TRONIC transformers, 035 W
or max. 08 TRONIC transformers, 060 W
or max. 07 TRONIC transformers, 070 W
or max. 04 TRONIC transformers, 105 W
or max. 03 TRONIC transformers, 150 W
or max. 02 TRONIC transformers, 200 W
Observe the above max. number of parallel
transformers to guarantee optimal spike
noise protection of the dimmer/transformer
combination.
The total installed power of all lamps must not
exceed 500 W.
Connecting inductive loads (iron-core trans-
formers) is not allowed.
In-circuit ripple pulse produced by the elec-
tricity suppliers may result in a short flicker if
the dimmer ist set low.
Depending on the total load on the SE TRONIC
dimmer, up to 10 SE TRONIC amplifiers or
built-in TRONIC amplifiers can be connected
(see diagram
) to extend the installed power.
Observe the technical terminal conditions set
by your electricity supplier.
Technical data, Ref.no. 245 TD REG
Nominal voltage AC 230 V, 50 HZ
Nominal current 50 – 500 W
TRONIC transformers,
incandescent lamps,
230 V halogen lamps,
load mix of the speci-
fied loads possible
Ambient temperature
(Ta) 45 °C
Housing temperature
(Tc) 75 °C
Dimensions 70 x 65 x 90 mm
Type of protection IP 20
Interfer. suppression interference class N
in acc. with EN55014
Max. number of
amplifiers 10
Satellites (mechanical) mechanical push-
button (make contact)
No. of satellites unlimited
Terminals 1, L,
Technical data 245 NL REG
Nominal voltage AC 230 V, 50 HZ
Connected load 100 VA to 450 VA
incandescent lamps,
230 V halogen lamps
with inductive trans-
former, load mix of
the specified types
possible
Softstart approx. 1 – 2 sec
Short-circuit cutout
protection within approx.
100 ms
Ambient temperature
(Ta) 45 °C
Housing temperature
(Tc) 75 °C
Dimensions 70 x 65 x 90 mm
Type of protection IP 20
Terminals , N,1, L
TRONIC-
power amplifier 500 W
Ref.no. 245 TL REG
Inductive
amplifier 450 W
Ref.no. 245 NL REG
Use the same phase conductor for inductive
dimmer and inductive amplifiers. Do not get
L and N confused when connecting the
amplifier because non-compliance will lead
to malfunction.
If you use inductive series embodied
amplifiers, always put a direct load by in-
ductive transformers or 230 V incandescent
lamps on the dimmer according to dimmer
specifications (see diagram
).
Small differences of illuminance between
dimmer load and load on the inductive
amplifier may occur, depending on the mains
voltage and the selected lamp. Overall load
(including transformer leak current) must not
exceed 450 VA.
During installation, observe the technical
terminal conditions set by your electricity
supplier.
Build up 2 circuits connected to the same
phase conductor if you are installing a lighting
system with a power of more than 3500 W.
Mechanically link the automatic circuit-
breaker of the two circuits to guarantee
disconnection of all poles of the lighting
system.
Use the same phase conductor for TRONIC
dimmer and amplifier.Do not get L and N confu-
sed when connecting the amplifier because non-
compliance will lead to malfunction.
If you use amplifiers, always put a direct load
by TRONIC transformers or lamps on the dim-
mer according to dimmer specifications (see
diagram
).
Max. installed power is 500 W for 230 V
incandescent lamps or 230 V halogen lamps
or max. 14 TRONIC transformers, 035 W
or max. 08 TRONIC transformers, 060 W
or max. 07 TRONIC transformers, 070 W
or max. 04 TRONIC transformers, 105 W
or max. 03 TRONIC transformers, 150 W
or max. 02 TRONIC transformers, 200 W
Observe the above max. number of parallel
transformers to guarantee optimal spike
noise protection of the dimmer/transformer
combination.
The total installed power of all lamps must
however not exceed 500 W.You can connect
up to 10 TRONIC SE amplifiers to the TRONIC
dimmer.
During installation, observe the technical
terminal conditions set by your electricity
supplier.
Build up 2 circuits connected to the same
phase conductor if you are installing a
lighting system with a power of more than
3500 W. Mechanically link the automatic cir-
cuit-breaker of the two circuits to guarantee
disconnection of all poles of the lighting
system.
Technical data, Ref.no. 245 TL REG
Nominal voltage AC 230 V, 50 HZ
Nominal current 100 W to 500 W
TRONIC transformers,
incandescent lamps,
230 V halogen lamps,
load mix of the speci-
fied loads possible
Ambient temperature
(Ta) 45 °C
Housing temperature
(Tc) 75 °C
Dimensions 70 x 65 x 90 mm
Type of protection IP 20
Interference interference class N
suppression in acc. with EN 55014
Terminals , N,1, L
1
1
AC 230 V
L
N
Satellite
e.g. touch dimmer
load (max. 500 VA)
inductive amplifier for
series embodiment
load (max. 450 VA)
NL1
N
L
1
N
L
AC 230 V
AC 12 V
1
· L
N ·
OFF
ON
1L
Satellite
TRONIC dimmer for
series embodiment
Built-in TRONIC amplifier
Load (max. 700 W)
TRONIC amplifier for
series embodiment
N
AC 230 V
NL1
N
L
AC 230 V
AC 12 V
Load (max. 500 W)
N
L
AC 230 V
AC 12 V
Load (max. 500 W)
Wiring diagrams
TRONIC-
dimmer 500 W
Ref.no. 245 TD REG
R,C
R,C
R,L
The symbols used to identify dimmer loads desig-
nate the type or the electrical
behaviour of loads connected to dimmers:
R = ohmic, C = capacitive, L = inductive
  • Page 1 1

JUNG 245TLREG Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI