Instruction Manual for Compliance
with UL/c-UL Standard
(MDS-B-SVJ2, MDS-B-SPJ2 and MR-J2-CT Series)
The instructions of UL/c-UL listed products are described in this manual.
The descriptions of this manual are conditions to meet the UL/c-UL
standard for the UL/c-UL listed products. To obtain the best performance,
be sure to read this manual carefully before use.
To ensure proper use, be sure to read specification manual carefully for
each product before use.
1. Operation surrounding air ambient temperature
The recognized operation ambient temperatures of each unit are as
shown in the table below. The recognized operation ambient
temperatures are the same as an original product specification for all
of the units.
Classification Unit name
operation ambient
temperature
Power supply unit 0~55°C
Servo drive unit 0~55°C
Spindle drive unit 0~55°C
Option unit 0~55°C
Battery unit 0~55°C
AC servo/
spindle system
Servo motor, Spindle motor 0~40°C
2. Notes for AC servo/spindle system
2-1 General Precaution
It takes 10 minutes to discharge the bus capacitor. (The capacitor
discharge time is one minute for MDS-B-SVJ2-01, 03, 04; two minutes
for MDS-B-SVJ2-06 and three minutes for MDS-B-SVJ2-07, 10, 20.)
When starting wiring or inspection, shut the power off and wait for
more than 15 minutes to avoid a hazard of electrical shock.
2-2 Installation
MDS-B-SVJ2, MDS-B-SPJ2 and MR-J2-CT Series have been
approved as the products which have been installed in the electrical
enclosure.
The minimum enclosure size is based on 150 percent of each
MDS-B-SVJ2, SPJ2 and MR-J2-CT Series combination. And also,
design the enclosure so that the ambient temperature in the enclosure
is 55°C (131°F) or less, refer to the specifications manual.
(MDS-B-SVJ2: BNP-B3937, MDS-B-SPJ2: BNP-B2164, MR-J2-CT:
BNP-B3944)
"The user must include the use of a 100 cfm fan spaced 4 in. above
the drive."
2-3 Short-circuit ratings
Suitable for use in a circuit capable of delivering not more than 100 kA
rms symmetrical amperes, 500 volts maximum.
2-4 Peripheral device
To comply with UL/c-UL Standard, use the peripheral devices which
conform to the corresponding standard.
- Fuses
Applicable
drive unit
UL Fuse
type
UL Voltage
rating, Vac
UL Current
rating, A
MDS-B-SVJ2-01 K5 250 10
MDS-B-SVJ2-03 K5 250 10
MDS-B-SVJ2-04 K5 250 15
MDS-B-SVJ2-06 K5 250 20
MDS-B-SVJ2-07 K5 250 20
MDS-B-SVJ2-10 K5 250 25
MDS-B-SVJ2-20 K5 250 40
MDS-B-SPJ2-02 K5 250 10
MDS-B-SPJ2-04 K5 250 15
MDS-B-SPJ2-075 K5 250 20
MDS-B-SPJ2-15 K5 250 40
MDS-B-SPJ2-22 K5 250 40
MDS-B-SPJ2-37 K5 250 60
MDS-B-SPJ2-55 K5 250 90
MDS-B-SPJ2-75 K5 250 125
MDS-B-SPJ2-110 K5 250 175
Applicable
drive unit
UL Fuse
type
UL Voltage
rating, Vac
UL Current
rating, A
MR-J2-10CT K5 250 10
MR-J2-20CT K5 250 10
MR-J2-40CT K5 250 15
MR-J2-60CT K5 250 20
MR-J2-70CT K5 250 20
MR-J2-100CT K5 250 25
MR-J2-200CT K5 250 40
MR-J2-350CT K5 250 70
- Circuit Breaker for of spindle motor Fan
Select the Circuit Breaker by doubling the spindle motor fan rated.
A rush current that is approximately double the rated current will
flow, when the fan is started
<Notice>
- For installation in United States, branch circuit protection must be
provided, in accordance with the National Electrical Code and any
applicable local codes.
- For installation in Canada, branch circuit protection must be
provided, in accordance with the Canada Electrical Code and any
applicable provincial codes.
2-5 Motor Over Load Protection
Servo drive unit MDS-B-SVJ2, MDS-B-SPJ2 and MR-J2-CT series
have each solid state motor over load protection.
(The motor full load
current is the same as rated current.)
When adjusting the level of motor over load, set the parameter as
follows.
2-5-1 MDS-B-SVJ2 Series
Para-
meter
No.
Para-
meter
abbr.
Parameter
name
Setting procedure
Standard
setting
value
Setting
range
SV021 OLT Overload
time
constant
Set the time constant for
overload detection.
(Unit: 1 second.)
60s 1~300s
SV022 OLL Overload
detection
level
Set the overload current
detection level with a
percentage (%) of the
stall rating.
150% 1~500
%
2-5-2 MDS-B-SPJ2 Series
Para-
meter
No.
Para-
meter
abbr.
Parameter
name
Setting
procedure
Standard
setting
value
Setting
range
SP063 OLT Overload
time
constant
Set the time constant for
overload detection.
(Unit: 1 second.)
60s 0~1000
s
SP064 OLL Overload
detection
level
Set the overload current
detection level with a
percentage (%) of the
rating.
120% 0~200
%
2-5-3 MR-J2-CT Series
The overload current detection level is 150% of the rated current.