Instructions Specic to Hazardous Area Installations
Page 12 June 2018VRX-UM-00374-EN-06
INSTRUCTIONS SPECIFIC TO HAZARDOUS AREA INSTALLATIONS
See the European ATEX Directive 94/9/EC, ANNEX II, 1.0.6 and the Vortex Intrinsically Safe Flow Meters Control Drawing for
RWG, RWBG and RNG Meters (shipped with the product; also available at badgermeter.com).
The following instructions apply to equipment covered by certificate number SIRA 03ATEX2543.
The certification marking is as follows:
1. The equipment may be used in zones 1 and 2 only with ammable gases and vapors with apparatus groups IIA and IIB and
with temperature classes T1, T2, T3 and T4. It is not suitable for zones where IIC gases or vapors may be present.
2. The equipment is only certied for use in ambient temperatures in the range –40° F (–40° C) to +176° F (+80° C) and should
not be used outside this range.
3. The equipment has not been assessed as a safety related device (as referred to by Directive 94/9/EC ANNEX II, Clause 1.5).
4. Installation, inspection and maintenance of this equipment shall be carried out by suitably trained personnel in
accordance with the manufacturer’s instructions and the applicable codes of practice (e.g., EN 60079-14 and EN 60079-17
in Europe).
5. Only spare parts supplied by Badger Meter may be used and installed in accordance with Badger Meter instructions.
WIRING
A two conductor foil shielded cable made of 14…22 AWG solid or stranded wire is required to make connections to the flow
meter (for example, Consolidated Wire P/N 5573-CL).
The shield is required to be attached to one of the shield ground points as illustrated in Figure 7 on page 11. The other end
of the shield should not be grounded.
When using the Zener Diode Barrier the maximum load resistance for the power depends on the supply voltage (see Figure 8
on page 14).
If a Barrier/Isolator is being installed, refer to the Barrier/Isolator manufacturers data sheet for maximum resistive loading on
the output. (Excitation voltage input to meter must be 15V DC minimum when output is at 20 mA)
The flow meter requires a minimum of 15V DC at the meter’s 4…20 mA (+) and (–) terminals to operate. With all loop loads
installed in the loop, the voltage at the meter must be at least 15V DC or the meter will operate erratically if at all. The
maximum load resistance for the meter depends on the supply voltage. The higher the supply voltage the greater the loop
load the meter will support.
The current sense resistor used in HART communications should be installed only for setup or troubleshooting as the current
sense resistor is an unnecessary loop load when the meter is operating under normal conditions.
OTE:N Current loops with large loads may work satisfactorily at low loop current outputs but cease to function as the output
current increases. The reason for this is that as the current increases the voltage drop across the sum of the loop loads
will increase in direct proportion to the current output. At some current output unique to that particular loop the
voltage drop across the sum of the loop loads will leave less than the minimum 15V DC required at the meters input
terminals.
If this occurs, the loop load must be reduced enough so that—at the maximum current output for the system—the
voltage at the meter’s power input terminals remains at least 15V DC
The external pressure sensor is limited to a 5 foot (1.5 meter) cable length.