FRICK
QUANTUM™ LX AcuAir
CONTROL PANEL S90-510 CS (MAR 08)
COMMUNICATIONS SETUP Page 15
Ethernet network must be assigned a unique identifying
number, called an IP Address (this is similar in concept
to the Quantum™ LX panel ID number). The IP
address is how the network identifies each device that
is attached. A typical IP address would look like this:
• 216.27.61.137
Gateway Address – Four setpoint boxes are provided
here. This is the IP address for the computer or device
onto which your local network is connected to. This
gateway device allows data to be routed to other
gateways and networks. A router is a Gateway device that
routes packets between different physical networks. A
gateway is a network point that acts as an entrance to
another network.
Subnet Mask - A TCP/IP number used to determine to
which TCP/IP subnet a device belongs. Devices in the
same subnet can be communicated with locally without
going through a router (to the outside world). When a
TCP/IP device tries to communicate with another device
the bits of the TCP/IP destination address are "ANDed"
with the subnet mask to determine whether the address is
a local address (broadcastable) or must be reached
through a router. A subnet mask of 255.255.255.0 used by
a computer with a TCP/IP address of 10.10.10.1 would
include the addresses 10.10.10.0 through 10.10.10.255 in
the local network, basically telling the computer to try a
router if it's transmitting to any other IP address. This is all
part of the TCP/IP protocol.
Web Server Port – This is the port, or channel, that a
web server uses to communicate through. Just as a
computer sends data to a printer through a printer
port, a web server sends and receives data through
the web server port. By default, the port number for a
web server is 80.
NAMING DATA
NOTE: The IP Address Type must be set to DHCP
(Dynamic) for this section to work.
Host Name – Enter here a distinct name that you wish to
be able to identify this particular compressor by (for
example; Unit1). The Host Name can be up to fifteen
characters in length, and must consist exclusively of letters
and numbers (spaces are not permitted). It is similar in
concept to the function of the Panel ID, and basically allows
the network router to interpret the actual IP address of a
particular unit as this host name. When using a web
browser within the system network, this name can be
entered as the web location that you wish to visit (instead of
having to type in the IP address). After modifying a Host
Name, you will be required to cycle power. The network
router could take up to fifteen minutes to recognize the
change.
Work Group – All of the Quantum™ LX units within a
network may be grouped into different categories. These
categories could be unit locations, or perhaps
categorized by unit function. For instance, if you wanted
to group the units by function, and had 10 units, and
three of them were air handlers, then ACUair1 could be
the name of a work group. Another three units may be
High Stage compressors, this work group could be
named HighStage1, and the remaining four units could
be standard compressors, and they could be named
Comp1. So name each unit by these functional Work
Group names. The Work Group name must be fifteen
characters or less in length, and can use numerals and
upper and lower case letters. When using the network
neighborhood feature of Windows® Internet Explorer, and
look at your Network Neighbor hood, you would see the
name of the Work Group, and within that work group you
would see the individual Host Names of each unit within
that work group. After modifying a Work Group name,
you will be required to cycle power. The network router
could take up to fifteen minutes to recognize the change.
Server String – This is a comment area that can be
used in conjunction with the Host Name. For example,
if the Host Name is Booster1, you could set the
Server String to print something like DockBooster, or
some other additional information about the unit. The
Server String has no control function, it is strictly a
descriptive field.
E-MAIL DATA
The purpose of the email data feature is to allow the
controller to send a warning or shutdown message to
defined listing of recipients.
Email Notification On Warning Or Shutdown – For
the email notification feature to work, it must be
enabled (it is disabled as a default). The following
drop-down menu is provided:
• Disabled
• Enabled
Local Email Address - Use this setpoint box to
enter a valid email address that has been assigned to
the internet account.
Alias Name For Local Email Address – Enter here
a custom name to identify more clearly the local email
address. When a message is sent to all recipients,
this is the name that will appear in the email FROM
column.
Subject - Enter here a custom subject that you would
like to have appear when a failure message is sent.
When a message is sent to all recipients, this is the
wording that will appear in the email SUBJECT field.
SMTP Server Name OR IP Address - SMTP stands for
Simple Mail Transfer Protocol. SMTP servers handle
outgoing email, and accept email from other domains. When
you set up an email client, you must specify an outgoing
server (sometimes called an SMTP server). Often, this server
is designated in the form of smtp.domain.com. But this can
vary, so be sure to check with your email service provider or
LAN administrator to find out their outgoing server.
SMTP Server Port Number - This value is in almost
all cases going to be 25. This should be set by the
network or LAN administrator.
Comma-Delimited List Of Email Recipients - This
is simply the list of the Email addresses that you
would like to have messages sent to. Separate each
email address with a comma.