Eaton CurrentWatch EAC and EACR series Owner's manual

Type
Owner's manual

This manual is also suitable for

WARNING!
IN ORDER TO AVOID ELECTRIC SHOCK OR OTHER POSSIBLE INJURY:
• DO NOT USE THIS PRODUCT FOR HUMAN SAFETY APPLICATIONS. IT
WAS NOT DESIGNED, TESTED, OR RECOMMENDED FOR THIS USE.
• DO NOT USE THIS PRODUCT IN HAZARDOUS LOCATIONS (E.G.
EXPLOSIVE ATMOSPHERES). IT WAS NOT DESIGNED, TESTED, OR
RECOMMENDED FOR THIS USE.
• ENSURE THE PRODUCT IS PROPERLY WIRED TO THE CORRECT POWER
SUPPLY FOR THE APPLICATION. REFER TO THE SPECIFICATIONS AND
WIRING DIAGRAMS IN THIS PUBLICATION.
Catalog
Number
Description
EAC105SC Self-Powered, Solid Core, 0-5 VDC Output, 10/20/50 A Range
EAC205SC Self-Powered, Solid Core, 0-5 VDC Output, 100/150/200 A Range
EAC105SP Self-Powered, Split Core, 0-5 VDC Output, 10/20/50 A Range
EAC205SP Self-Powered, Split Core, 0-5 VDC Output, 100/150/200 A Range
EAC110SC Self-Powered, Solid Core, 0-10 VDC Output, 10/20/50 A Range
Catalog
Number
Description
EAC210SC Self-Powered, Solid Core, 0-10 VDC Output, 100/150/200 A Range
EAC110SP Self-Powered, Split Core, 0-10 VDC Output, 10/20/50 A Range
EAC210SP Self-Powered, Split Core, 0-10 VDC Output, 100/150/200 A Range
EAC0420SC 24 VDC Loop-Powered, Solid Core, 4-20 mA Output, 2/5 A Range
EAC1420SC 24 VDC Loop-Powered, Solid Core, 4-20 mA Output, 10/20/50 A Range
EAC2420SC 24 VDC Loop-Powered, Solid Core, 4-20 mA Output, 100/150/200 A Range
EAC0420SP 24 VDC Loop-Powered, Split Core, 4-20 mA Output, 2/5 A Range
EAC1420SP 24 VDC Loop-Powered, Split Core, 4-20 mA Output, 10/20/50 A Range
EAC2420SP 24 VDC Loop-Powered, Split Core, 4-20 mA Output, 100/150/200 A Range
EACR0420SC 24 VDC Loop-Powered, Solid Core, 4-20 mA Output, 2/5 A Range
EACR1420SC 24 VDC Loop-Powered, Solid Core, 4-20 mA Output, 10/20/50 A Range
EACR2420SC 24 VDC Loop-Powered, Solid Core, 4-20 mA Output, 100/150/200 A Range
EACR0420SP 24 VDC Loop-Powered, Split Core, 4-20 mA Output, 2/5 A Range
EACR1420SP 24 VDC Loop-Powered, Split Core, 4-20 mA Output, 10/20/50 A Range
EACR2420SP 24 VDC Loop-Powered, Split Core, 4-20 mA Output, 100/150/200 A Range
Models Covered In This Publication
CurrentWatch™ EAC and EACR Series
Current Sensors
Instructions Publication P51917
Effective July 2017
Supersedes March 2014
Instruction Leaflet
Montageanweisung
Notice d’installation
Instrucciones de montaje
Istruzioni per il montaggio
安装
Инструкция по монтажу
Montagehandleiding
Montagevejledning
Οδηγίες εγκατάστασης
Instruções de montagem
Monteringsanvisning
Asennusohje
Návod k montáži
Paigaldusjuhend
Szerelési utasítás
Montāžas instrukcija
Montavimo instrukcija
Instrukcja montażu
Navodila za montažo
Návod na montáž
Монтажни инструкции
Instrucţiuni de montaj
Upute za montažu
Electric current! Danger to life!
Only skilled or instructed persons may
carry out the following operations.
Lebensgefahr durch elektrischen Strom!
Nur Elektrofachkräfte und elektrotechnisch
unterwiesene Personen dürfen die im Folgenden
beschriebenen Arbeiten ausführen.
Tension électrique dangereuse !
Seules les personnes qualifiées et averties doivent
exécuter les travaux ci-après.
¡Corriente eléctrica! ¡Peligro de muerte!
El trabajo a continuación descrito debe ser realizado
por personas cualificadas y advertidas.
Tensione elettrica: Pericolo di morte!
Solo persone abilitate e qualificate possono eseguire
le operazioni di seguito riportate.
触电
只允许专业人员和受过专业训练的人员进行下列工作。
Электрический ток! Опасно для жизни!
Только специалисты или проинструктированные
лица могут выполнять следующие операции.
Levensgevaar door elektrische stroom!
Uitsluitend deskundigen in elektriciteit en
elektrotechnisch geïnstrueerde personen is het
toegestaan, de navolgend beschreven
werkzaamheden uit te voeren.
Livsfare på grund af elektrisk strøm!
Kun uddannede el-installatører og personer der
e instruerede i elektrotekniske arbejdsopgaver,
må udføre de nedenfor anførte arbejder.
en
de
fr
es
it
zh
ru
nl
da
Προσοχή, κίνδυνος ηλεκτροπληξίας!
Οι εργασίες που αναφέρονται στη συνέχεια θα
πρέπει να εκτελούνται μόνο από ηλεκτρολόγους
και ηλεκτροτεχνίτες.
Perigo de vida devido a corrente eléctrica!
Apenas electricistas e pessoas com formação
electrotécnica podem executar os trabalhos
que a seguir se descrevem.
Livsfara genom elektrisk ström!
Endast utbildade elektriker och personer som
undervisats i elektroteknik får utföra de arbeten
som beskrivs nedan.
Hengenvaarallinen jännite!
Vain pätevät sähköasentajat ja opastusta saaneet
henkilöt saavat suorittaa seuraavat työt.
Nebezpečí úrazu elektrickým proudem!
Níže uvedené práce smějí provádět pouze
osoby s elektrotechnickým vzděláním.
Eluohtlik! Elektrilöögioht!
Järgnevalt kirjeldatud töid tohib teostada ainult
elektriala spetsialist vői elektrotehnilise
instrueerimise läbinud personal.
Életveszély az elektromos áram révén!
Csak elektromos szakemberek és elektrotechnikában
képzett személyek végezhetik el a következőkben leírt
munkákat.
Elektriskā strāva apdraud dzīvību!
Tālāk aprakstītos darbus drīkst veikt tikai
elektrospeciālisti un darbam ar elektrotehniskām
iekārtām instruētās personas!
el
pt
sv
fi
cs
et
hu
lv
Pavojus gyvybei dėl elektros srovės!
Tik elektrikai ir elektrotechnikos specialistai gali
atlikti žemiau aprašytus darbus.
Porażenie prądem elektrycznym stanowi
zagrożenie dla życia!
Opisane poniżej prace mogą przeprowadzać tylko
wykwalifikowani elektrycy oraz osoby odpowiednio
poinstruowane w zakresie elektrotechniki.
Življenjska nevarnost zaradi
električnega toka!
Spodaj opisana dela smejo izvajati samo
elektrostrokovnjaki in elektrotehnično poučene osebe.
Nebezpečenstvo ohrozenia života
elektrickým prúdom!
Práce, ktoré sú nižšie opísané, smú vykonávat’
iba elektroodborníci a osoby s elektrotechnickým
vzdelaním.
Опасност за живота от електрически ток!
Операциите, описани в следващите раздели,
могат да се извършват само от
специалисти-електротехници и инструктиран
електротехнически персонал.
Atenţie! Pericol electric!
Toate lucrările descrise trebuie efectuate numai
de personal de specialitate calificat şi de persoane
cu cunoştiinţe profunde în electrotehnică.
Opasnost po život uslijed električne struje!
Radove opisane u nastavku smiju obavljati samo
stručni električari i osobe koje su prošle
elektrotehničku obuku.
lt
pl
sl
sk
bg
ro
hr
291002131
Introduction
The CurrentWatch EAC Series combine a
current sensor and signal conditioner into
a single package. The EAC Series are
available in solid or split core with 4-20 mA,
0-5 VDC or 0-10 VDC outputs.
The CurrentWatch EACR Series
provide “True RMS” output. Available
only with a 4-20 mA output. Select EACR
Series sensors for applications involving
variable speed or SCR-controlled loads.
To open:
Press tab inward
towards hinge
Important:
Keep contact areas clean
Installation
Considerations for all EAC and EACR Series models…
Run wire to be monitored through the aperture (opening) in the
switch body.
These sensors can be located in the same environment as
motors, contactors, heaters, pull-boxes and other electrical enclo-
sures.
Mounting can be done in any position or hung directly on a wire
with a wire tie.
Be sure to leave at least 1.0 in. (25.4 mm) distance between sen-
sor and other magnetic devices
Considerations for split-core models only…
Press the tab in the direction
shown in the diagram to the right.
After placing the wire in the
aperture, press the hinged portion
firmly downward until a click is
heard and the tab pops out fully.
Keep split-core contact areas
clean. Silicon grease is factory applied on the mating surfaces to
prevent rust and improve performance. Be careful not to allow
grit or dirt into the grease in the contact area, particularly on core
mating surfaces of split core models. Sensor operation could be
impaired if mating surfaces do not have good contact. Check visu-
ally before closing.
Quick Install Guide
The below steps can be followed to quickly install a CurrentWatch
EAC or EACR Series switch.
1. Run the wire to be monitored through the aperture.
2. Mount the sensor to a surface, if needed.
3. Connect output wiring:
a. Use up to 14 AWG copper wires.
b. If using a 0-5 or 0-10 VDC output model, make sure output
load is at least 1 megohm.
c. If using a 4-20 mA output model, make sure loop voltage is
correct (see Output Wiring” section).
4. Select range:
a. Choose the correct range by positioning the Range Jumper.
Output Wiring
Connect control or monitoring wires to the sensor. Use up to 14
AWG copper wire and tighten terminals to 7 in.-lbs / 0.79 N·m
maximum torque. Be sure the output load or loop power does not
exceed the sensor rating.
Connection Notes:
Captive screw terminals.
Use 14-22 AWG solid or stranded.
Observe polarity.
See label for ranges and jumper positions.
Model Wiring Diagram
Current Output
Models (4-20 mA)
Voltage Output
Models
(0-5/0-10 VDC)
Notes for Voltage Output Models:
• Recommended output load greater than 1 megohm
• Add 1.3% error for 100 kilohm
Loop Voltage Requirements:
EAC Series: Min. Loop Voltage = 5 V + (Loop Resistance x 20 mA)
EACR Series: Min. Loop Voltage = 12 V + (Loop Resistance x 20 mA)
Maximum Input Amps
Range
Maximum Amps
Continuous 6 sec. 1 sec.
0-2 A 80 A 125 A 250 A
0-5 A 100 A 125 A 250 A
0-10 A 80 A 125 A 250 A
0-20 A 110 A 150 A 300 A
0-50 A 175 A 215 A 400 A
0-100 A 200 A 300 A 600 A
0-150 A 300 A 450 A 800 A
0-200 A 400 A 500 A 1,000 A
Load (Controller, Meter...)
Power
Supply
Monitored
Wire
Load (Controller, Meter...)
Monitored
Wire
Range Selection
The CurrentWatch EAC Series sensors feature field selectable rang-
es. The ranges are factory calibrated, eliminating time consuming
and inaccurate field setting of zero or span.
Setting Range
1. Determine the normal operating amperage of your monitored
current.
2. Select the range this is equal to or slightly higher than the nor-
mal operating amperage.
3. Place the Range Jumper in the appropriate position.
2
EATON www.eaton.com
CurrentWatch™ EAC and EACR Series
Current Sensors
Instructions Publication P51917
Effective July 2017
Troubleshooting
Problem
Solution for Current
Output Models
Solution for Voltage
Output Models
Sensor has no
output.
Power supply is not properly
sized. Check power supply
voltage and current rating.
Monitored load is not AC or is
not on. Check that the moni-
tored load is AC and that it is
actually on.
Polarity is not properly matched. Check and correct wiring
polarity.
For split core models, the core contact area may be dirty. Open
the sensor and clean the contact area.
Output signal is
too low.
The jumper may be set in a range that is too high for current
being monitored. Move jumper to the correct range.
The load current is not
sinusoidal (EAC Series only).
Select an EACR Series sen-
sor that works on distorted
waveforms.
Output load may be too low.
Check output load, making
sure it is at least 100 kilohm
and preferably 1 megohm.
Monitored current is below minimum required. Loop the
monitored wire several times through the aperture until the
“sensed” current rises above minimum. (‘Sensed Amps’ is
equal to ‘Actual Amps’ multiplied by the ‘Number of Loops.’)
Output signal is
always at maxi-
mum.
The jumper may be set in a range that is too low for current
being sensed. Change the jumper position.
Output signal is
always at 4 mA.
Monitored load is not AC or is
not on. Check that the moni-
tored load is AC and that it is
actually on.
Specications
Specification
Models with
4-20 mA Output
Models with
0-5 VDC Output
Models with
0-10 VDC
Output
Power Supply 24 VDC
Loop-Powered
Self Powered–No Power Supply
Needed
Output Signal 4-20 mA 0-5 VDC 0-10 VDC
Output Limit EAC Series:
32 mA
EACR Series:
23 mA
10 VDC 15 VDC
Output Load Recommended 1 megohm, add 1.3%
error for 100 kilohm (see “Output
Wiring”)
Response Time EAC Series:
300 ms
EACR Series:
600 ms
100 ms
Frequency Range EAC Series:
20-100 Hz
EACR Series:
10-400 Hz
(Both Sinusoidal)
50-60 Hz (Sinusoidal)
Accuracy 1% FS
Isolation Voltage UL Listed to 1,270 VAC, Tested to 5,000 VAC
Sensing Aperture Solid Core Models: 0.75 in. (19 mm) dia.
Split Core Models: 0.85 in. (21.7 mm) sq.
Housing UL94 V0 Flammability Rated
Environmental Operating Temperature: -4 to +122°F (-20 to +50°C)
Humidity: 0-95% RH, Non-Condensing
Approvals UL Listed, E117028
UL Tested to Canadian Safety Standards
CE
RoHs Compliant
3
EATON www.eaton.com
Instructions Publication P51917
Effective July 2017
CurrentWatch™ EAC and EACR Series
Current Sensors
Eaton Industries GmbH
Hein-Moeller-Straße 7-11,
53115 Bonn, Germany
Eaton Corporation
W126 N7250 Flint Drive
Menomonee Falls,
WI 53051, USA
Contact your regional Eaton oce for additional technical support
Eaton is a registered trademark of
Eaton Corporation.
All other trademarks are property
of their respective owners.
Americas – Asia Pacic Europe – Middle East – Africa
Eaton Corporation
Electrical Sector – Sensors
+1.800.426.9184
www.eaton.com/sensors
Eaton Industries GmbH
Electrical Sector EMEA
+49 (0) 180 5 223822
www.eaton.eu/sensors
© 2017 by Eaton
All Rights Reserved
Printed in USA
Publication No. P51917 / 003
July 2017
CurrentWatch™ EAC and EACR Series
Current Sensors
Instructions Publication P51917
Effective July 2017
Eaton Industries GmbH
Hein-Moeller-Straße 7-11,
53115 Bonn, Germany
Eaton
W126 N7250 Flint Drive
Menomonee Falls,
WI 53051, USA
Eaton
Electrical Sector – Sensors
+1.800.426.9184
www.eaton.com/sensors
Eaton Industries GmbH
Electrical Sector EMEA
+49 (0) 180 5 223822
www.eaton.eu/sensors
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Contact your regional Eaton office for additional technical support
Americas – Asia Pacific Europe – Middle East – Africa
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Eaton CurrentWatch EAC and EACR series Owner's manual

Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI