(36)Parameter Configuration Flow Chart
PV
SV:default=50C
Level 1
Level 2
Level 3
Main output
Percentage
Range=0~100%
Aux. output
percentage
Range=0~100%
Alarm 1 Hi value
Range=0~99 ℃/℉
Alarm 2 value
Range=0~99℃/℉
PID auto tuning
:none
:Execute once
:execute every
times
Control mode
See Table 1
Main & Aux. O/P
Heating/cooling
Mode
See Table 2
Main O/P cycle
time
Range=0~60sec
Aux. O/P cycle
time
Range=0~60sec
Main O/P propor-
Tional band
Range=0~100C/F
Aux. O/P propor-
tional band
Range=0~100C/F
Main O/P different-
ial time
Range=0~250/0.1s
Aux. O/P D time
Range=0~250/0.1s
Level 4
Alarm 1 mode
See Table 3
Manual O/P mode
:enable
:disable
Alarm 1 dead
band
Range=0~10 ℃/℉
Alarm 2 mode
See Table 3
Alarm 2 dead
band
Range=0~10 ℃/℉
Analog O/P low
limit
Range=0~200
Analog O/P high
limit
Range=0~200
Password
Range=0000~9999
Thermocouple
type
See Table 4
Unit= or ℃ ℉
Input temp.offset
Range=-99~+99
℃/℉
Main O/P propor-
tional high limit
Range=0~200
Aux. O/P propor-
tional high limit
Range=0~200
Restore default
:usable
:disable
Main output hyst-
eresis band
Range:1~100℃/℉
Display in on/off
control mode
Aux. output hyst-
eresis band
Range:1~100℃/℉
Display in on/off
control mode
Main output I time
Range:
0~250/0.1sec
Aux. output I time
Range:
0~250/0.1sec
SV low limit
Range:Thermocouple
Low limit ~
(℃/℉)
SV high limit:
Range: ~
Thermocouple high limit
(℃/℉)
Take 5 Main O/P control model
use self tuning
control model
use auto tuning
control model
matters needing attention:
When use At control model.
Will have the excess temperature
phenomenon in at calculation process.
Finished until the calculation.
The calculation period PV right
bottom decimal point will glitter.
Level 2
Main & aux. output heating & cooling mode:
Set the control modes of main & aux. heat-
ing & cooling
Main output cycle time : Set the cycle time
of main output.
Aux. output cycle time : Set the cycle time
of aux. output.
Main output proportional band : Set the
value P of main output proportional band.
Main output differential time : Set the value
D of main output differential time.
Aux. output differential time : Set the value
D of aux. output differential time.
Aux. output proportional band : Set the
value P of aux. output proportional band.
Main output hysteresis band : Set the
value of main output hysteresis band
Display and adjust in on/off control mode
Aux. output hysteresis band : Set the
value of aux. output hysteresis band
Display and adjust in on/off control mode
Aux. output integral time : Set the
value of aux. output integral time
Main output integral time : Set the
value of main output integral time
SV high limit : Set the SV high limit from
SV low limit to the thermocouple high
limit
SV low limit : Set the SV low limit from
the thermocouple low range to SV high
limit
Cooling delay : Set the range of PV exceed
SV, the system will execute the cooling
Control mode : Set the control modes of
main and aux. output.
Table 1 Output control mode
Main : PID Aux. : PID
Main : on/off Aux. : on/off
Main : on/off Aux. : PID
Main : PID Aux. : on/off
Table 2 Output heating &cooling control mode
Main :heating Aux. :cooling
Main :cooling Aux. :heating
Table 3 Alarm mode
Table 4 Input thermocouple type
*DP:Decimal point
Parameter description
Level 1
Level 3
Level 4
Main output percentage : Display the perc-
entage of main output, and it was controled
by PID control function.
Alarm 2 value : Set the range of alarm 2
Aux. output percentage : Display the
Percentage of aux. output.
PID auto tuning : Execute the PID value
automatically.
Manual output mode : Switch usable & dis-
able for manual output.
Alarm 1 mode : Set the alarm 1 action mode
Alarm 1 hysteresis band : Set the value of
alarm 1 hysteresis band.
Alarm 2 mode : Set the alarm 2 action mode
Alarm 2 hysteresis band : Set the value of
alarm 2 hysteresis band.
Analog output low limit : Output the low limit
when analog output
Analog output high limit : Output the high
limit when analog output
Password : Set the password to change the
parameter using and setting.
Thermocouple type : Set the thermocouple
type.
Unit : or are selectable
Input temperature offset : Set offset value to
increase or decrease the present tempera-
ture.
Main output percentage high limit : Set the
percentage high limit of main output
Aux. output percentage high limit : Set the
percentage high limit of aux. output
Default value : Restore default from the
user settings.
Range=0~99 ℃/℉
Alarm 1 Low value
auto tuning switch
Yes:start AT tuning
NO:stop AT tuning
Main O/P
control model
Set Take 5
Cooling delay
Range:
0~30℃/℉
Alarm 1 value : Set the low alarm range of
alarm 1
Alarm 1 value : Set the Hi alarm range of
alarm 1
Auto tuning model switch
Main output control model:
Set the Auto tuning or Self tuning
J0 TYPE
J1 TYPE
K0 TYPE
K1 TYPE
PT0 TYPE
PT1 TYPE
(Take 6)
(Take 6)
(Take 6)
Soft start output
time range:
0~60min
Soft start output
Percent range:
0~100%
Soft start output time : Heater dehumidify
Time
Soft start output percent : Heater dehumidify
Output percent
(Take 6)
No alarm
Low limit
High limit
Lo/Hi limit
Low limit standby
Lo/Hi limit standby
Reverse Lo/Hi limit
Absolute
Reverse Lo limit
Reverse Hi limit
Reverse Absolute
Take 6 :
If the Main O/P control
model( ) set to mode
the PID parameter shows:
J TYPE without DP,Range: 0~900°C/32 1200°F
J TYPE with DP, Range: 0.0~900.0°C/32.0~999.9°F
K TYPE without DP,Range: 0~1200°C/32~1500°F
K TYPE with DP, Range: 0.0~999.9°C/32.0~999.9°F
PT TYPE without DP,Range: -200~500°C/-328~900°F
PT TYPE with DP, Range: -199.9~500.0°C/-199.9~900.0°F
~
Present value
digital filter time
0~60 sec