Toshiba 1600 User manual

Category
Power supply units
Type
User manual
TOSHIBA
INTERNATIONAL CORPORATION
Houston Texas, USA
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
TOSHIBA INTERNATIONAL CORPORTION AND SHALL NOT
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
TITLE
DRAWING NO. REV.
1
2
3
4
5
6
7
8
9
10
NOTES
DRAWN BY
APPROVED
DATE
A B C D E F G H I J
DATE
1
2
3
4
5
6
7
8
9
10
JE 10/11/05
UE3G2L060C61T
Input
208,240V
50/60Hz,
Output
208/240/120V
50/60Hz
1600 EP Series
6 kVA Model 208/240V Input
208/240/120V Output
UPS Cabinet
1.0
INV
CONV
+
-
Static Bypass
Transformer
Internal Battery Modules
THY. SW.
CHOPPER
50Amp
Input Breaker
1. If AC input power is 240Vac rated, terminals 12 and 13 must be shorted by
jumper wire
2. If AC input power is 208Vac rated, terminals 11 and 12 must be shorted by
jumper wire (factory set)
Customer
supplied
wiring
Customer
supplied
wiring
#10 AWG wire
16543287
L1 NX2X1GL2 GX3
208/240 Vac
Input Cables from
Distribution Panel
#10 AWG wire
240V
208V
120V120V
Hardwire Configuration
131211 17161514
240
COM208
REMOTEEPO2EPO1
208V 240V
Jumper Selection
See Note 1,2
Remote Run/Stop
Command
GM 10/11/05
  • Page 1 1

Toshiba 1600 User manual

Category
Power supply units
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI