INSTALLATION
1. Push tab on top and bottom of the back plate and lift the cover from the back plate.
(See Figure 1).
2. Selectthemountinglocation,awayfromdiffusers,lights,oranyexternalinuences.
3. Mount transmitter on a vertical surface to a standard electrical box using the two #6
M2C type screws provided.
4. Pull wires through the sub base hole and make the necessary connections
according to wiring section.
5. Reattach cover to back plate.
Series BTT-E/N Wall Mount Temperature Transmitter
Specications - Installation and Operating Instructions
Bulletin T-BTT-W
The Series BTT-E/N Wall Mount Temperature Transmitter is used to monitor the
temperature in a room or indoor building space and transmit the measurement to
a remote display, building management system, or control system. The transmitter
signal output offers more reliable signal accuracy over long wire runs when compared
to standard thermistor or RTD sensors.
SPECIFICATIONS
Temperature Sensor:Pt1000ΩRTDDINClassA0.00385Ω/°C.
Range:32to122°F(0to50°C).
Temperature Limits:32to122°F(0to50°C).
Accuracy:±0.5°C@25°C.
Thermal Effect:±0.01%/°C.
Response Time: 100 ms.
Power Requirements:13to36VDCforcurrentmodels,13to36VDCor16to28
VACforvoltagemodels.
Output Signal:4to20mAor0to10VDC(dependingonmodel).
Electrical Connections: Screw terminal block.
Enclosure Rating:IP20.
Weight: 2.6 oz (73.7 g).
Agency Approvals: CE.
European Style
North American Style
TABS
SUB
BASE HOLE
SUB
TABS
Figure 1
Use electrostatic discharge precautions (e.g., use of wrist
straps) during installation and wiring to prevent equipment
damage.
NOTICE
Disconnect power supply before installation to prevent electrical
shock and equipment damage. Make sure all connections are
in accordance with the job wiring diagram and in accordance with national and local
electrical codes. Use copper connectors only.
WARNING
Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present.
NOTICE
Do not exceed ratings of this device, permanent damage not
coveredbywarrantymayresult.The4-20 mAmodelsarenot
designedforACvoltageoperation.
NOTICE
MODEL CHART
Model Housing Output
BTT-N00-3
BTT-N00-4
BTT-E00-3
BTT-E00-4
NorthAmericanStyle
NorthAmericanStyle
European Style
European Style
4to20mA
0 to 10 VDC
4to20mA
0 to 10 VDC
4-1/2
[114.30]
2-51/64
1-3/32
[27.69]
35/64
[14.02]
3-1/64
[76.56]
2X-11/64
[4.47]
31/64
[12.32]
[92.96]
3-9/16
[90.42]
[27.05]
3X-3/8
[9.36]
21/64
[8.38]
1-3/16
[30.00]
1-5/32
[29.39]
[3.87]
European Style
North American Style
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057