Quad Fiber Remote SFP
COMPLIANCE
CAUTION: Electrostatic Discharge (ESD) can damage electronic modules.
When handling modules, wear an antistatic discharge wrist
strap to prevent damage to electronic components. Place
modules in antistatic packing material when transporting or
storing. When working on modules, always place them on an
approved antistatic mat that is electrically grounded.
The Quad Fiber Remote SFP (P/N 1181307L8) is NRTL Listed to
the applicable UL standards. The QDFRS meets or exceeds all
the applicable requirements of NEBS, Telcordia GR-63-CORE,
GR-78-CORE, and GR-1089-CORE.
The QDFRS is intended for deployment in Central Office type
facilities, EEEs, EECs, and locations where the NEC applies
(ex. Customer Premises). Install the QDFRS in a restricted
access location.
This device complies with Part 15 of the FCC rules. Operation is subject
to the following two conditions:
1. This device may not cause harmful interference
2. This device must accept any interference received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void
the user's authority to operate this equipment.
CAUTION: Per GR-1089-CORE Section 9, the QDFRS does not have an
internal DC connection between battery return and frame
ground. The QDFRS can be installed in a DC-I (isolated) or
DC-C (common) installation. If the QDFRS is installed in a
DC-C (common) installation, the ampacity of the conductor
connecting the equipment frame to the battery return conductor
shall be equal to or greater than the ampacity of the associated
battery return conductor.
NOTE: The DSX-1 ports are classified as Type 2 or 4, as defined in
Appendix B of GR-1089-CORE Issue 4, and are suitable for
connection to intra-building or unexposed wiring or cabling only. Do
not metallically connect these ports to interfaces which connect to
the Outside Plant (OSP) or to OSP wiring.
The DSX-1 ports are designed for use as intra-building interfaces
only (Type 2 or Type 4 ports as described in GR-1089-CORE Issue
4) and require isolation from exposed OSP cabling. The addition of
Primary Protectors is not sufficient protection in order to connect
these interfaces metallically to OSP wiring.
The OC-3 SFP port is optical and therefore is not classified as any
type of port as defined in Appendix B of GR-1089-CORE Issue 4.
Current limiting protectors are not required.
The QDFRS is designed to operate with a nominal operating voltage
of ±24 VDC or ±48 VDC and a minimum operating voltage of ±20
VDC. The QDFRS will not be damaged by any steady state voltage
below –56.7 VDC.
Configuration Code Input Output
Power Code (PC) F C
Telecommunication Code (TC) – –
Installation Code (IC) A –
Test Jack
The test jack has two modes (selected on the QDFCS):
♦ Monitor Mode (non-intrusive): looks at a port in either direction
♦ Intrusive Mode: “breaks” a port in either direction
MAINTENANCE
The QDFRS does not require routine hardware maintenance for normal
operation. ADTRAN does not recommend that repairs be attempted in
the field. Repair services may be obtained by returning the defective unit
to ADTRAN.
Field support for software is provided through upgrade facilities. Refer to
“Warranty” for further information.
PROVISIONING
Most provisioning is handled through remote management from the
QDFCS. To directly access the QDFRS via the rear-panel DB-9 craft
port, connect a VT100 (or compatible) terminal, set to:
♦ 9600 bps
♦ 8 data bits
♦ No parity
♦ No flow control
♦ 1 stop bit
Connection is directly to the QDF Main menu, with no login step. To
traverse the menus, select the desired entry and press
ENTER. To return
to the previous menu, press
ESC.
The QDFRS retains provisioning data in nonvolatile memory, in case of
a loss of power.
Factory Defaults
On installation, the QDFRS is provisioned to factory default settings.
The table below lists default values for key Provisioning options.
Option Settings (Default in Bold)
DSX-1 Line Build Out 0-133 Feet; 133-266 Feet; 266-399 Feet;
399-533 Feet; 533-655 Feet
DSX-1/DS1 Line Code AMI; B8ZS
NIU Loopback Disabled; Enabled
Loopback Timeout None; 120 Min
DS1 TX Level 0 dB; –7.5 dB; –15 dB
Customer Loss Indicator AIS; Loopback
Port Service State In Service; Out of Service–Maintenance;
Out of Service–Unassigned
For more information, refer to Total Access 3000/3010 QDFCS and QDFRS Installation and Maintenance
Practice (P/N 61181307L8-5) available online at www.adtran.com
.
Warranty: ADTRAN will replace or repair this product within the warranty period if it does not meet its
published specifications or fails while in service. Warranty information can be found online at
www.adtran.com/warranty
.
©2008 ADTRAN, Inc. All Rights Reserved.
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
*61181307L8-22B*
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
CLEI: SIM5110B_ _
Product P/N: 1181307L8
Issue Date: 0809
Document P/N: 61181307L8-22B